background image

3-40 Ramp 1 Type
Option:
*Linear ........................................................................... [0]
Function:
Select the ramp type, depending on requirements 
for acceleration/deceleration. A linear ramp will 
give constant acceleration during ramping.

3-41 Ramp up time running (sec)
Range:
0.01 - 3600.00 s ...................................................* 9.00s
Function:
Enter the ramp-up time, i.e. the acceleration time 
to reach the system requiered motor speed.

3-42 Ramp Down Time running (sec)
Range:
0.01 - 3600.00 s ...................................................* 0.30s
Function:
Enter the ramp-down time, i.e. the deceleration 
time to reach compressor minimum motor speed.

3-82 Starting Ramp-up Time
Compressor dependent, factory set : read only

Parameters: Limits/Warnings
Parameter group for configuring limits and warnings.

4-1* Motor Limits
4-10 Motor Speed Direction
*Clockwise  .................................................................. [0]
Because previous settings rotation is always 
clockwise (positive), but be sure that CD302 U, V, 
W terminals are connected to the correspondant 
compressor motor terminals.

4-11 Motor Speed Low Limit [RPM]
Compressor dependent, factory set : read only

4-12 Motor Speed Low Limit [Hz]
Compressor dependent, factory set : read only

4-13 Motor Speed High Limit [RPM]
Compressor dependent, factory set : read only

4-14 Motor Speed High Limit [Hz]
Compressor dependent, factory set : read only

4-16 Torque Limit Motor Mode
Compressor dependent, factory set : read only

4-18 Current Limit
Range:
0.0 - Variable Limit % ................. Set to UL MMT 
Value:
The current can be adjusted in regards to the 
compressor operation.

4-19 Max Output Frequency
Compressor dependent, factory set : read only

4-5* Adj. Warnings
Adjustable warning limits for current, speed, refe-
rence and feedback.
Warnings are shown on display, programmed 
output or serial bus.

4-51 Warning Current High
* As par. 1-24 Compressor dependent, factory set 
: read only
Function:
When the motor current exceeds this limit (IHIGH), 
the display reads CURRENT HIGH. Then the CD302 

frequency converter adjusts automatically the mo-
tor compressor speed in order to reduce the load 
and control the current value below the limit.

4-52 Warning Speed Low
* As par. 4-11 Compressor dependent, factory set 
: read only
When motor compressor speed reach this value 
or less during a period of time of two seconds 
then the compressor is stopped by the CD302 
frequency converter and automatically restart 
after a delay set in Par. 14-21

4-53 Warning Speed High
* As par. 4-13 Compressor dependent, factory set 
: read only

4-58 Missing Motor Phase Function
Option:
Off ................................................................................... [0]
*On ................................................................................. [1]
Function:
Select 

On

, to display an alarm in the event of a 

missing motor phase. Select 

Off

, for no alarm in 

the event of a missing motor phase. However, if 
the motor runs on only two phases, it can be da-
maged by overheating. Retaining the On setting 
is therefore strongly recommended.
This parameter cannot be adjusted while the 
motor is running.

Parameters: Digital In/Out
Parameter group for configuring the digital input 
and output.

5-0* Digital In/Out Mode
5-00 Digital In/Out Mode
Option:
*PNP ............................................................................... [0]
NPN  ................................................................................ [1]
Function:
Digital inputs and programmed digital outputs 
are pre-programmable for operation either in 
PNP or NPN systems.
Select 

PNP [0] 

systems for action on positive di-

rectional pulses ().

5-01 Terminal 27 Mode
Option:
*Input  ............................................................................ [0]
Output ........................................................................... [1]
Function:
Select 

Input [0]

 to define terminal 27 as a digital 

input.
Select

 Output [1] 

to define terminal 27 as a digital 

output.
This parameter cannot be adjusted while the 
motor is running.

5-02 Terminal 29 Mode
Similar to Terminal 27

5-1* Digital Inputs
Parameters for configuring the input functions 
for the input terminals.
The digital inputs are used for selecting various 
functions in the frequency converter.

5-10 Terminal 18 Digital Input
Function:
Start ................................................................................ [8]

5-11 Terminal 19 Digital Input

Function:
No operation   ............................................................. [0]

5-12 Terminal 27 Digital Input
Function:
Coast inverse   ............................................................. [2]

5-13 Terminal 29 Digital Input
Function:
No operation   ............................................................. [0]

5-14 Terminal 32 Digital Input
Function:
No operation   ............................................................. [0]

5-15 Terminal 33 Digital Input
Function:
No operation   ............................................................. [0]

Parameters: Analog In/Out
Parameter group for configuration of the analog 
input and output.

6-0* Analog In/Out Mode
Parameter group for setting up the analog In/Out 
configuration.
CD 302 is equipped with 2 analog inputs: Terminal 
53 and 54. The analog inputs on CD 302 can freely be 
allocated to either voltage (-10 V - +10 V) or current 
input (0/4 - 20 mA).

6-1* Analog Input 1
Parameters for configuring the scaling and limits 
for analog input 1 (terminal 53). Note: that Analog 
input 53 is preset for usage with “opent loop” 
control on 0-10 Volt. Terminal 54 is preset for 
“Process Loop” control using a pressure sensor AKS 
with a pessure range of -1 : 12 bar.

6-10 Terminal 53 Low Voltage
Range:
-10.0 - par. 6-11  ................................................. * 0.00V
This analog input scaling value should correspond 
to the minimum reference value, set in par. 3-02.

6-11 Terminal 53 High Voltage
Range:
6-10 to 10 V .......................................................* 10.00V
This analog input scaling value should correspond  
to the maximum reference value, set in par. 3-03.

6-12 Terminal 53 Low Current
Range:
0.0 to par. 6-13 mA  ........................................ * 4.0mA
This reference signal should correspond to the 
minimum reference value, set in par. 3-02.

6-13 Terminal 53 High Current
Range:
6-12 to 20 mA  ...............................................* 20.0mA
This reference signal should correspond to the 
maximum reference value, set in par. 3-02.

6-14 Terminal 53 Low Ref./Feedb. Value
As Par. 3-02 but not linked

6-15 Terminal 53 High Ref./Feedb. Value
As Par. 3-03 but not linked

Instructions

AN000086420674en-000201 | 19

© Danfoss | DCS (CC) | 2019.04

Summary of Contents for Compressor Drive CD302

Page 1: ...t has been disconnected from mains Also make sure that other voltage inputs have been disconnected such as load sharing linkage of DC intermediate circuit Using CD 302 Com pressor Drives wait at least...

Page 2: ...and switch S202 Voltage mode Switch S201 switch S202 OFF U Voltage level 10 to 10 V scaleable Input resistance Ri approx 10 k Max voltage 20 V Current mode Switch S201 switch S202 ON I Current level...

Page 3: ...C dera ting of the frequency converter will become rele vant The service life of the frequency converter is reduced if derating for ambient temperature is not taken into account Mechanical dimensions...

Page 4: ...rth connection terminal 99 on decoupling plate with screws from the accessory bag Insert terminals 96 U 97 V 98 W and motor compressor cable to terminals labelled MOTOR Fasten screened cable to decoup...

Page 5: ...ent anti overload and lock rotor motor compressor protection see description in the application manual The frequency converter is protected against short circuits on compressor terminals U V W If a ma...

Page 6: ...mounted to the terminal To remove the cable from the terminal 1 Insert a screw driver in the square hole 2 Pull out the cable Basic Wiring Example 1 Mount terminals from the accessory bag to the fron...

Page 7: ...0BA025 17 91 L1 92 L2 93 L3 PE 88 89 50 10V OUT 53 A IN 54 A IN 55 COM A IN 0 4 20 mA 12 24V OUT 13 24V OUT 37 D IN 18 D IN 20 COM D IN 10Vdc 15mA 130 200mA U 96 V 97 W 98 PE 99 COM A OUT 39 A OUT 42...

Page 8: ...interrupt device If the interrupt device and the frequency converter are placed in the same installation panel you can use a regular cable instead of a protected one Electrical Installation EMC prote...

Page 9: ...filled See the para graph EMC test results Safety earth connection The frequency converter has a high leakage cur rent and must be earthed appropriately for safety reasons acording to EN 50178 The ear...

Page 10: ...4 20 mA 0 4 20 mA COM 68 69 4 5 0 10 V or 4 20 mA Open Loop input 0 10V between 53 55 to external Frequency converter CD302 Compressor Drive TM RS 485 Analog output Analog input 6 Incorporate securit...

Page 11: ...if the motor compressor remains in the coasted state 4 Then send Reset signal via Bus Digital I O or Reset key The test step is passed if the motor compressor gets operational again 5 The commissioni...

Page 12: ...iping oil return Reset start Power output from CD302 drive Yes No Check Alarm 14 15 30 31 32 38 Earth Fault Output side Short circuit Output side Motor phase missing Internal fault Check motor cable C...

Page 13: ...pass Or recycled Missing CD 302 back side Metal sheet Turn off power Reset Start 24V supply to terminal 37 direct wire external controls inserted Check Alarm continue Speed limit low Automatic restart...

Page 14: ...I No need to change any other parameter this is factory setting Quick setup The following lines describe the basic procedure to run the CD302 1 Connect the power supply to the terminals L1 L2 and L3...

Page 15: ...the keys to move the cursor OK is used for choosing a parameter marked by the cursor and for enabling the change of a para meter Local Control Keys for local control are found at the bottom of the con...

Page 16: ...Change from Open Loop factory set to Pro cess Loop Select Quick Menu Select Q3 PID Closed Loop Par 1 00 change to 3 Process Par 3 01 change to 71 bar Par 3 02 enter pressure sensor low range value fac...

Page 17: ...rameter will be ignored 0 61 Access to Main Menu w o Password Option Full access 0 Read only 1 No access 2 Function Select Full access 0 to disable the password defi ned in par 0 60 Main Menu Password...

Page 18: ...Minimum Reference unit matches the choice of configuration in par 1 00 Confi guration Mode for Speed closed loop 1 the unit selected in par 3 01 Reference Feedback Unit 3 03 Maximum Reference Enter th...

Page 19: ...y two phases it can be da maged by overheating Retaining the On setting is therefore strongly recommended This parameter cannot be adjusted while the motor is running Parameters Digital In Out Paramet...

Page 20: ...eded by the integrator to reach the same gain as the proportional gain 7 35 Process PID Differentiation Time Range 0 00 10 00 s 0 00s Function Enter the PID differentiation time The differen tiator do...

Page 21: ...54 Cut in pressure is set at 3 000 bar in parameter 13 12 0 Comparator value Cut out pressure is set 1 000 bar in parameter 13 12 1 Comparator value Anti short cycle by adjusting minimum dura tion bet...

Page 22: ...trolled by a switch connected to terminal 18 05 12 Terminal 27 Coast inverse Stop function coast inverse linked to safety line of the system HP LP switches 06 10 Terminal 53 Low Voltage 0 Minimum valu...

Page 23: ...rminal 54 Low Voltage 1V Minimum value in V for the pressure transmitter s range Depends on output from the feedback device Nor mally no changes are needed 06 21 Terminal 54 High Voltage 5V Maximum va...

Page 24: ...ref Feedb value 6 25 r w 12 Param Designation Param number Customer access Common parameters for all compressors Speed PID Feedback Source 7 00 Read Motor Feedb P1 02 PID Gain 7 02 Read 0 005 PID Inte...

Page 25: ...90 RPM 90 RPM 90 RPM Speed limit for stop function 1 81 Read 1800 1800 1500 1500 1500 1500 1500 Min reference 3 02 r w 2100 2100 1800 1800 1800 1800 1800 Max reference 3 03 r w 5400 5400 5400 5100 540...

Page 26: ...PM 90 RPM Speed limit for stop function 1 81 Read 1800 1800 1500 1500 Min reference 3 02 r w 2100 2100 1800 1800 Max reference 3 03 r w 5400 5400 5400 5100 Ramp down time running sec 3 42 r w 0 3 0 3...

Page 27: ...RPM Speed limit for stop function 1 81 Read 1800 1800 1500 1500 1500 1500 1500 Min reference 3 02 r w 2100 2100 1800 1800 1800 1800 1800 Max reference 3 03 r w 5400 5400 5400 5100 5400 5400 5100 Ramp...

Page 28: ...the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specification...

Reviews: