background image

when the power is cycled to the frequency converter.
Select 

Normal operation 

[0] for normal operation 

of the frequency converter with the motor in the 
selected application.
Select 

Control card test

 [1] to test the analog and digital 

inputs and outputs and the +10 V control voltage. The 
test requires a test connector with internal connections. 
Use the following procedure for the control card test:
  1. Select 

Control card test

 [1].

  2. Disconnect the mains supply and wait for 
the light in the display to go out.
  3. Set switches S201 (A53) and S202 (A54) = ON. / I.
  4. Insert the test plug (see below).
  5. Connect to mains supply.
  6. Carry out various tests.
  7. The results are displayed on the LCP and the 
frequency converter moves into an infinite loop.
  8. Par. 14-22 is automatically set to Normal 
operation. Carry out a power cycle to start up in 
Normal operation after a control card test.
If the test is OK:
LCP read-out: Control Card OK. Disconnect the 
mains supply and remove the test plug. The 
green LED on the Control Card will light up.
If the test fails:
LCP read-out: Control Card I/O failure.
Replace the frequency converter or Control card.
The red LED on the Control Card is turned on.
Test plugs (connect the following terminals to 
each other): 18 - 27 - 32; 19 - 29 - 33; 42 - 53 - 54

Select 

Initialization

 [2] to reset all parameter va-

lues to default settings, except for par. 15-03, 15-

04, and 15-05. The frequency converter will reset 
during the next power-up.
Par. 14-22 will also revert to the default setting 

Normal operation 

[0].

14-25 Trip Delay at Torque Limit
Option:
Off

14-26 Trip Delay at Inverter Fault
Option:
0 - 30 s ..........................................................................* 2s
Compressor dependent, factory set : read only

14-52 Fan Control
Option:
*Auto .............................................................................. [0]
On 50% .......................................................................... [1]
On 75% .......................................................................... [2]
On 100% ....................................................................... [3]
Function:
Select the minimum speed of the internal fan.
Select 

Auto 

[0] to run the fan only when the internal 

temperature of the frequency converter is in the 
range 35 °C . approx. 55°C. The fan will run at low 
speed at 35C, and at full speed at approx. 55°C.

Parameters: Smart Logic Control
SLC (Smart Logic Controler is not active by fac-
tory setting for “Open Loop” system conrol. For 
“Process Loop” factory setting” have been done in 
order to manage:
-  Pump-down function (by mean of suction 
pressure sensor on input 54)
Cut-in pressure is set at 3.000 bar in parameter 
13-12.0 (Comparator value)
Cut-out pressure is set 1.000 bar in parameter 13-
12.1 (Comparator value)
- Anti-short cycle by adjusting minimum dura-
tion between two starts set at 5 minutes.
These 5 minutes are set in parameter 13-20.0 (SL 
Controller timer).
Oil return management by having a minimum 
On-Time at each start-up. Default setting is 0 
(zero) seconds by security. This parameter has to 
be adjusted in regards to each system, recom-
mandation is about 30 seconds.
Setting is done on parameter 13-20.1 (SL Control-
ler Timer)

The complete description of these parameter va-
lues and operand is done on the previous table” 
CD302 main parameters for VTZ Compressors”

Smart Logic Control (SLC) is essentially a sequence 
of user defined actions (see par. 13-52 [x]) execu-
ted by the SLC when the associated user defined 
event (see par. 13-51 [x]) is evaluated as TRUE by 
the SLC. Events and actions are each numbered 
and linked together in pairs. This means that when 

event

 [0] is fulfilled (attains the value TRUE), 

action

 

[0] is executed. After this, the conditions of 

event

 

[1] will be evaluated and if evaluated TRUE, 

action

 

[1] will be executed and so on. Only one event will 
be evaluated at any time. If an event is evaluated 
as FALSE, nothing happens (in the SLC) during the 
current scan interval and no other events will be 
evaluated. This means that when the SLC starts, it 
evaluates 

event

 [0] (and only 

event

 [0]) each scan 

interval. Only when event [0] is evaluated TRUE, 
will the SLC execute 

action

 [0] and start evaluating 

event [1]. It is possible to programme from 1 to 20 
events and actions. When the last event / action 
has been executed, the sequence starts over again 
from 

event

 [0] / 

action 

[0]. 

Starting and stopping the SLC:
Starting and stopping the SLC can be done by 
selecting .On [1]. or .Off [0]. in par. 13-00. The SLC 
always starts in state 0 (where it evaluates event 
[0]). The SLC starts when the Start Event (defined 
in par. 13-01 Start Event) is evaluated
as TRUE (provided that On [1] is selected in par. 
13-00). The SLC stops when the Stop Event and 
reset the Smart Logic Control.

13-00 SL Controller Mode
Option:
*Off  ................................................................................ [0]
On ................................................................................... [1]
Function:
Select 

On 

[1] to enable the Smart Logic Control to 

start when a start command is present, e.g. via a 
digital input.
Select 

Off [

0] to disable the Smart Logic Control.

Instructions

AN000086420674en-000201 | 21

© Danfoss | DCS (CC) | 2019.04

Summary of Contents for Compressor Drive CD302

Page 1: ...t has been disconnected from mains Also make sure that other voltage inputs have been disconnected such as load sharing linkage of DC intermediate circuit Using CD 302 Com pressor Drives wait at least...

Page 2: ...and switch S202 Voltage mode Switch S201 switch S202 OFF U Voltage level 10 to 10 V scaleable Input resistance Ri approx 10 k Max voltage 20 V Current mode Switch S201 switch S202 ON I Current level...

Page 3: ...C dera ting of the frequency converter will become rele vant The service life of the frequency converter is reduced if derating for ambient temperature is not taken into account Mechanical dimensions...

Page 4: ...rth connection terminal 99 on decoupling plate with screws from the accessory bag Insert terminals 96 U 97 V 98 W and motor compressor cable to terminals labelled MOTOR Fasten screened cable to decoup...

Page 5: ...ent anti overload and lock rotor motor compressor protection see description in the application manual The frequency converter is protected against short circuits on compressor terminals U V W If a ma...

Page 6: ...mounted to the terminal To remove the cable from the terminal 1 Insert a screw driver in the square hole 2 Pull out the cable Basic Wiring Example 1 Mount terminals from the accessory bag to the fron...

Page 7: ...0BA025 17 91 L1 92 L2 93 L3 PE 88 89 50 10V OUT 53 A IN 54 A IN 55 COM A IN 0 4 20 mA 12 24V OUT 13 24V OUT 37 D IN 18 D IN 20 COM D IN 10Vdc 15mA 130 200mA U 96 V 97 W 98 PE 99 COM A OUT 39 A OUT 42...

Page 8: ...interrupt device If the interrupt device and the frequency converter are placed in the same installation panel you can use a regular cable instead of a protected one Electrical Installation EMC prote...

Page 9: ...filled See the para graph EMC test results Safety earth connection The frequency converter has a high leakage cur rent and must be earthed appropriately for safety reasons acording to EN 50178 The ear...

Page 10: ...4 20 mA 0 4 20 mA COM 68 69 4 5 0 10 V or 4 20 mA Open Loop input 0 10V between 53 55 to external Frequency converter CD302 Compressor Drive TM RS 485 Analog output Analog input 6 Incorporate securit...

Page 11: ...if the motor compressor remains in the coasted state 4 Then send Reset signal via Bus Digital I O or Reset key The test step is passed if the motor compressor gets operational again 5 The commissioni...

Page 12: ...iping oil return Reset start Power output from CD302 drive Yes No Check Alarm 14 15 30 31 32 38 Earth Fault Output side Short circuit Output side Motor phase missing Internal fault Check motor cable C...

Page 13: ...pass Or recycled Missing CD 302 back side Metal sheet Turn off power Reset Start 24V supply to terminal 37 direct wire external controls inserted Check Alarm continue Speed limit low Automatic restart...

Page 14: ...I No need to change any other parameter this is factory setting Quick setup The following lines describe the basic procedure to run the CD302 1 Connect the power supply to the terminals L1 L2 and L3...

Page 15: ...the keys to move the cursor OK is used for choosing a parameter marked by the cursor and for enabling the change of a para meter Local Control Keys for local control are found at the bottom of the con...

Page 16: ...Change from Open Loop factory set to Pro cess Loop Select Quick Menu Select Q3 PID Closed Loop Par 1 00 change to 3 Process Par 3 01 change to 71 bar Par 3 02 enter pressure sensor low range value fac...

Page 17: ...rameter will be ignored 0 61 Access to Main Menu w o Password Option Full access 0 Read only 1 No access 2 Function Select Full access 0 to disable the password defi ned in par 0 60 Main Menu Password...

Page 18: ...Minimum Reference unit matches the choice of configuration in par 1 00 Confi guration Mode for Speed closed loop 1 the unit selected in par 3 01 Reference Feedback Unit 3 03 Maximum Reference Enter th...

Page 19: ...y two phases it can be da maged by overheating Retaining the On setting is therefore strongly recommended This parameter cannot be adjusted while the motor is running Parameters Digital In Out Paramet...

Page 20: ...eded by the integrator to reach the same gain as the proportional gain 7 35 Process PID Differentiation Time Range 0 00 10 00 s 0 00s Function Enter the PID differentiation time The differen tiator do...

Page 21: ...54 Cut in pressure is set at 3 000 bar in parameter 13 12 0 Comparator value Cut out pressure is set 1 000 bar in parameter 13 12 1 Comparator value Anti short cycle by adjusting minimum dura tion bet...

Page 22: ...trolled by a switch connected to terminal 18 05 12 Terminal 27 Coast inverse Stop function coast inverse linked to safety line of the system HP LP switches 06 10 Terminal 53 Low Voltage 0 Minimum valu...

Page 23: ...rminal 54 Low Voltage 1V Minimum value in V for the pressure transmitter s range Depends on output from the feedback device Nor mally no changes are needed 06 21 Terminal 54 High Voltage 5V Maximum va...

Page 24: ...ref Feedb value 6 25 r w 12 Param Designation Param number Customer access Common parameters for all compressors Speed PID Feedback Source 7 00 Read Motor Feedb P1 02 PID Gain 7 02 Read 0 005 PID Inte...

Page 25: ...90 RPM 90 RPM 90 RPM Speed limit for stop function 1 81 Read 1800 1800 1500 1500 1500 1500 1500 Min reference 3 02 r w 2100 2100 1800 1800 1800 1800 1800 Max reference 3 03 r w 5400 5400 5400 5100 540...

Page 26: ...PM 90 RPM Speed limit for stop function 1 81 Read 1800 1800 1500 1500 Min reference 3 02 r w 2100 2100 1800 1800 Max reference 3 03 r w 5400 5400 5400 5100 Ramp down time running sec 3 42 r w 0 3 0 3...

Page 27: ...RPM Speed limit for stop function 1 81 Read 1800 1800 1500 1500 1500 1500 1500 Min reference 3 02 r w 2100 2100 1800 1800 1800 1800 1800 Max reference 3 03 r w 5400 5400 5400 5100 5400 5400 5100 Ramp...

Page 28: ...the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specification...

Reviews: