background image

may cause a stopped motor to start. CD 302 with 
Safe Stop provides a certain degree of protec-
tion against such unintended start, if the Safe 
Stop Terminal 37 is on low voltage level or dis-
connected.

Safe Stop of CD 302
The CD 302 can perform the safety function Safe 
Torque Off (As defined by draft CD IEC 61800-5-
2) or Stop Category 0 (as defined in EN 60204-1).
It is designed and approved suitable for the requi-
rements of Safety Category 3 in EN 954-1.
This functionality is called Safe Stop. Prior to inte-
gration and use of Safe Stop in an installation, a 
thorough risk analysis on the installation must 
be carried out in order to determine whether the 
Safe Stop functionality and safety category are 
appropriate and sufficient. In order to install and 
use the Safe Stop function in accordance with the 
requirements of Safety Category 3 in EN 954-1, 
the related information and instructions of the 
CD 302 Design Guide must be followed!
The information and instructions of the Opera-
ting Instructions are not sufficient for a correct 
and safe use of the Safe Stop functionality!

General Specifications 
Mains supply (L1, L2, L3)
• Supply voltage: 200-240 V ±10%
• Supply voltage: 380-480 V ±10%
• Supply voltage: 525-600 V ±10%
• Supply frequency: 50/60 Hz
• Maximbalance temporary between mains 

phases: 3.0 % of rated supply voltage

• True Power Factor (λ): ≥ 0.9 nominal at rated 

load

• Displacement Power Factor (cos φ) near unity:  

(> 0.98)

• Switching on input supply L1, L2, L3 (power-

ups) ≤ 7.5 kW: maximum 2 times/min.

• Switching on input supply L1, L2, L3 (power-

ups) ≥ 11 kW: maximum 1 time/min.

• Environment according to EN60664-1: overvol-

tage category III/pollution degree 2

The unit is suitable for use on a circuit capable of 
delivering not more than 100.000 RMS symmetri-
cal Amperes, 240/500/600 V maximum.

Motor compressor output (U, V, W)
• Output voltage: 0 - 100% of supply voltage
• Switching on output: see param number 14-01 
in table page 28.

Digital inputs
• Voltage level: 0 - 24 V DC
• Voltage level, logic.0. PNP: < 5 V DC
• Voltage level, logic.1. PNP: > 10 V DC
• Voltage level, logic .0. NPN2): > 19 V DC
• Voltage level, logic .1. NPN2): < 14 V DC
• Maximum voltage on input: 28 V DC
• Input resistance, Ri: approx. 4 kΩ

Safe stop Terminal 37
Terminal 37 is fixed PNP logic
• Voltage level: 0 - 24 V DC
• Voltage level, logic.0. PNP: < 4 V DC
• Voltage level, logic.1. PNP: >20 V DC
• Nominal input current at 24 V: 50 mA rms
• Nominal input current at 20 V: 60 mA rms
• Input capacitance: 400 nF

All digital inputs are galvanically isolated from 
the supply voltage (PELV) and other high-voltage 
terminals.

 1) Terminals 27 and 29 can also be programmed 
as output.
 2) Except safe stop input Terminal 37.
 3) Terminal 37 can only be used as safe stop input.
Terminal 37 is suitable for category 3 installations 
according to EN 954-1 (safe stop according to 
category 0 EN 60204-1) as required by the EU 
Machinery Directive 98/37/EC. Terminal 37 and 
the Safe Stop function are designed in confor-
mance with EN 60204-1, EN 50178, EN 61800-2, 
EN 61800-3, and EN 954-1. For correct and safe 
use of the Safe Stop function follow the related 
information and instructions in the Design Guide.

Analog inputs
• Number of analog inputs: 2
• Terminal number: 53, 54
• Modes: Voltage or current
• Mode select: Switch S201 and switch S202
• Voltage mode: Switch S201/switch S202 = OFF 

(U)

• Voltage level: -10 to +10 V (scaleable)
• Input resistance, Ri: approx. 10 kΩ
• Max. voltage: ± 20 V
• Current mode: Switch S201/switch S202 = ON 

(I)

• Current level: 0/4 to 20 mA (scaleable)
• Input resistance, Ri: approx. 200 Ω
• Max. current: 30 mA
• Resolution for analog inputs: 10 bit (+ sign)
• Accuracy of analog inputs: Max. error 0.5% of 

full scale

• Bandwidth: 100 Hz
The analog inputs are galvanically isolated from 
the supply voltage (PELV) and other high-voltage 
terminals.

Digital output
• Programmable digital/pulse outputs: 2
• Terminal number: 27, 29
• Voltage level at digital/frequency output: 0 - 24 

V

• Max. output current (sink or source): 40 mA
• Max. load at frequency output: 1 kΩ
• Max. capacitive load at frequency output: 10 nF
• Minimum output frequency at frequency 

output: 0 Hz

• Maximum output frequency at frequency 

output: 32 kHz

• Accuracy of frequency output: Max. error: 0.1 % 

of full scale

• Resolution of frequency outputs: 12 bit

1) Terminal 27 and 29 can also be programmed as 
input.
The digital output is galvanically isolated from the 
supply voltage (PELV) and other high-voltage ter-
minals.

Analog output
• Number of programmable analog outputs: 1
• Terminal number: 42
• Current range at analog output: 0/4 - 20 mA
• Max. load to common at analog output: 500 Ω
• Accuracy on analog output: Max. error: 0.5 % of 
full scale
• Resolution on analog output: 12 bit
The analog output is galvanically isolated from 
the supply voltage (PELV) and other high-voltage 
terminals.

Control card, 24 V DC output
• Terminal number: 12, 13
• Max. load: 200 mA
The 24 V DC supply is galvanically isolated from 
the supply voltage (PELV), but has the same po-

tential as the analog and digital inputs and out-
puts.
Control card, 10 V DC output
• Terminal number: 50
• Output voltage: 10.5 V ±0.5 V
• Max. load: 15 mA
The 10 V DC supply is galvanically isolated from 
the supply voltage (PELV) and other high-voltage 
terminals.

Control card, RS 485 serial communication
• Terminal number: 68 (P,TX+, RX+), 69 (N,TX-, RX-)
• Terminal number 61: Common for terminals 68 
and 69
The RS 485 serial communication circuit is func-
tionally separated from other central circuits and 
galvanically isolated from the supplier voltage 
(PELV).

Control card, USB serial communication
• USB standard: 1.1 (Full speed)
• USB plug: USB type B .device. plug
Connection to PC is carried out via a standard 
host/device USB cable.
The USB connection is galvanically isolated from 
the supply voltage (PELV) and other high-voltage 
terminals. The USB ground connection is not 
galvanically isolated from protection earth. Use 
only isolated laptop as PC connection to the USB 
connector on CD 302 drive.

Relay outputs
• Programmable relay outputs: 2
• Relay 01 Terminal number: 1-3 (break),1-2 

(make)

• Max. terminal load (AC-1)1) on 1-3 (NC), 1-2 

(NO) (Resistive load): 240 V AC, 2 A

• Max. terminal load (AC-15)1) (Inductive load @ 

cosφ 0.4): 240 V AC, 0.2 A

• Max. terminal load (DC-1)1) on 1-2 (NO), 1-3 

(NC) (Resistive load): 60 V DC, 1A

• Max. terminal load (DC-13)1) (Inductive load): 

24 V DC, 0.1A

• Relay 02 (CD 302 only) Terminal number: 4-6 

(break), 4-5 (make)

• Max. terminal load (AC-1)1) on 4-5 (NO) 

(Resistive load): 400 V AC, 2 A

• Max. terminal load (AC-15)1) on 4-5 (NO) 

(Inductive load @ cosφ 0.4): 240 V AC, 0.2 A

• Max. terminal load (DC-1)1) on 4-5 (NO) 

(Resistive load): 80 V DC, 2 A

How to install
Mechanical Installation
Find the following parts included in the CD302 
Accessory Bag.
• Accessory Bag ≤ 7.5 kW

Instructions

2 | AN000086420674en-000201

© Danfoss | DCS (CC) | 2019.04

Summary of Contents for Compressor Drive CD302

Page 1: ...t has been disconnected from mains Also make sure that other voltage inputs have been disconnected such as load sharing linkage of DC intermediate circuit Using CD 302 Com pressor Drives wait at least...

Page 2: ...and switch S202 Voltage mode Switch S201 switch S202 OFF U Voltage level 10 to 10 V scaleable Input resistance Ri approx 10 k Max voltage 20 V Current mode Switch S201 switch S202 ON I Current level...

Page 3: ...C dera ting of the frequency converter will become rele vant The service life of the frequency converter is reduced if derating for ambient temperature is not taken into account Mechanical dimensions...

Page 4: ...rth connection terminal 99 on decoupling plate with screws from the accessory bag Insert terminals 96 U 97 V 98 W and motor compressor cable to terminals labelled MOTOR Fasten screened cable to decoup...

Page 5: ...ent anti overload and lock rotor motor compressor protection see description in the application manual The frequency converter is protected against short circuits on compressor terminals U V W If a ma...

Page 6: ...mounted to the terminal To remove the cable from the terminal 1 Insert a screw driver in the square hole 2 Pull out the cable Basic Wiring Example 1 Mount terminals from the accessory bag to the fron...

Page 7: ...0BA025 17 91 L1 92 L2 93 L3 PE 88 89 50 10V OUT 53 A IN 54 A IN 55 COM A IN 0 4 20 mA 12 24V OUT 13 24V OUT 37 D IN 18 D IN 20 COM D IN 10Vdc 15mA 130 200mA U 96 V 97 W 98 PE 99 COM A OUT 39 A OUT 42...

Page 8: ...interrupt device If the interrupt device and the frequency converter are placed in the same installation panel you can use a regular cable instead of a protected one Electrical Installation EMC prote...

Page 9: ...filled See the para graph EMC test results Safety earth connection The frequency converter has a high leakage cur rent and must be earthed appropriately for safety reasons acording to EN 50178 The ear...

Page 10: ...4 20 mA 0 4 20 mA COM 68 69 4 5 0 10 V or 4 20 mA Open Loop input 0 10V between 53 55 to external Frequency converter CD302 Compressor Drive TM RS 485 Analog output Analog input 6 Incorporate securit...

Page 11: ...if the motor compressor remains in the coasted state 4 Then send Reset signal via Bus Digital I O or Reset key The test step is passed if the motor compressor gets operational again 5 The commissioni...

Page 12: ...iping oil return Reset start Power output from CD302 drive Yes No Check Alarm 14 15 30 31 32 38 Earth Fault Output side Short circuit Output side Motor phase missing Internal fault Check motor cable C...

Page 13: ...pass Or recycled Missing CD 302 back side Metal sheet Turn off power Reset Start 24V supply to terminal 37 direct wire external controls inserted Check Alarm continue Speed limit low Automatic restart...

Page 14: ...I No need to change any other parameter this is factory setting Quick setup The following lines describe the basic procedure to run the CD302 1 Connect the power supply to the terminals L1 L2 and L3...

Page 15: ...the keys to move the cursor OK is used for choosing a parameter marked by the cursor and for enabling the change of a para meter Local Control Keys for local control are found at the bottom of the con...

Page 16: ...Change from Open Loop factory set to Pro cess Loop Select Quick Menu Select Q3 PID Closed Loop Par 1 00 change to 3 Process Par 3 01 change to 71 bar Par 3 02 enter pressure sensor low range value fac...

Page 17: ...rameter will be ignored 0 61 Access to Main Menu w o Password Option Full access 0 Read only 1 No access 2 Function Select Full access 0 to disable the password defi ned in par 0 60 Main Menu Password...

Page 18: ...Minimum Reference unit matches the choice of configuration in par 1 00 Confi guration Mode for Speed closed loop 1 the unit selected in par 3 01 Reference Feedback Unit 3 03 Maximum Reference Enter th...

Page 19: ...y two phases it can be da maged by overheating Retaining the On setting is therefore strongly recommended This parameter cannot be adjusted while the motor is running Parameters Digital In Out Paramet...

Page 20: ...eded by the integrator to reach the same gain as the proportional gain 7 35 Process PID Differentiation Time Range 0 00 10 00 s 0 00s Function Enter the PID differentiation time The differen tiator do...

Page 21: ...54 Cut in pressure is set at 3 000 bar in parameter 13 12 0 Comparator value Cut out pressure is set 1 000 bar in parameter 13 12 1 Comparator value Anti short cycle by adjusting minimum dura tion bet...

Page 22: ...trolled by a switch connected to terminal 18 05 12 Terminal 27 Coast inverse Stop function coast inverse linked to safety line of the system HP LP switches 06 10 Terminal 53 Low Voltage 0 Minimum valu...

Page 23: ...rminal 54 Low Voltage 1V Minimum value in V for the pressure transmitter s range Depends on output from the feedback device Nor mally no changes are needed 06 21 Terminal 54 High Voltage 5V Maximum va...

Page 24: ...ref Feedb value 6 25 r w 12 Param Designation Param number Customer access Common parameters for all compressors Speed PID Feedback Source 7 00 Read Motor Feedb P1 02 PID Gain 7 02 Read 0 005 PID Inte...

Page 25: ...90 RPM 90 RPM 90 RPM Speed limit for stop function 1 81 Read 1800 1800 1500 1500 1500 1500 1500 Min reference 3 02 r w 2100 2100 1800 1800 1800 1800 1800 Max reference 3 03 r w 5400 5400 5400 5100 540...

Page 26: ...PM 90 RPM Speed limit for stop function 1 81 Read 1800 1800 1500 1500 Min reference 3 02 r w 2100 2100 1800 1800 Max reference 3 03 r w 5400 5400 5400 5100 Ramp down time running sec 3 42 r w 0 3 0 3...

Page 27: ...RPM Speed limit for stop function 1 81 Read 1800 1800 1500 1500 1500 1500 1500 Min reference 3 02 r w 2100 2100 1800 1800 1800 1800 1800 Max reference 3 03 r w 5400 5400 5400 5100 5400 5400 5100 Ramp...

Page 28: ...the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specification...

Reviews: