10 | © Danfoss | 2019.04

VI.IR.W2.9Z 

AMEi 6

ENGLISH

Safety Notes

To avoid personal injury and damage 

to devices, it is absolutely essential for 

these instructions and safety notes to 

be read carefully and reviewed prior to 

assembly and use.
Do not dismantle actuator with the safety spring 

function! There is risk of injury and death in the 

event of improper handling!
The actuator is heavy. Handle with care to avoid 

injury or product damage.

Disposal

This product should be dismantled 

and its components sorted, if possible, 

in various groups before recycling or 

disposal.

Always follow the local disposal regulations.

Wiring

Do not touch anything on the PCB!  

Do not remove the service cover 

before the power supply is fully 

switched off.

Wiring length

Recommended cross-sectional 

area of the wiring

0-50 m

0,75 mm

2

> 50 m

1,5 mm

2

Electrical connection 

iSET actuator mounting to pressure 

actuator 

Stand-By mode for manual operation 

and differential pressure setting 

Set-point range see rating plate on the pressure 

actuator*

1.  Start-up of system *

2. Set flow rate on a motorized valve over 

which the differential pressure is controlled, 

to about 50 % *

3. Adjustment

• Observe pressure indica tors *

Enter the Stand-By mode for manual 

operation

•  Pushing the button 

 on the actuator 

increases the set-point (squeezing the 

spring)

•  Pushing the button 

 redu ces the  

set-point (stretching the spring)

End switch setting for  MIN/MAX set Δp 

Slider 

 can be set to limit min. ∆p 

Slider 

 can be set to limit max. ∆p

Fix the sliders 

 with 2 srews 

Slider 

 may be sealed 

see instruction for relevant combination

pressure actuator/ valve

DIP switch setting 

S1

S1/DIP 1

Input signal type selector: 

OFF: Input signal Y is set to voltage (V) 

ON: Input signal Y is set to current (mA) 
S1/DIP 2

Output signal type selector: 

OFF: Output signal X is set to voltage (V) 

ON: Output signal X is set to current (mA)
S1/DIP 3

Direct or inverse acting selector 

(Fig. 2)

: 

OFF: Actuator is direct acting to input 

signal 

ON: Not to be used for iSET
S1/DIP 4 

Normal or sequential mode selector:

OFF: Actuator is working in range 0(2)-10 V 

or 0(4)-20 mA 

ON: Actuator is working in sequential 

range; 0-5 V or (0-10 mA) or (5-10 V) or (10-

20 mA) 

Signal range selector S1/DIP 6 sets the 

sequential range.
S1/DIP 5 

0-10 V/2-10 V – Input/output

OFF: 0-10 V; input signal is in the range 

from 0-10 V (voltage input) or from 0-20 

mA (current input) 

ON: 2 –10 V; input signal is in the range 

from 2-10 V (voltage input) or from 4-20 mA 

(current input) 

Signal range selector S1/DIP 1 & DIP 2 sets 

Y and X signal. 
S1/DIP 6 

Sequential range selector:

OFF: 0-5 V or (0-10 mA) 

ON: 5-10 V or (10-20 mA) 

[S1/DIP 4 = ON!]
S1/DIP 7 

OFF: iSET

ON: iNET **
S1/DIP 8 

Not used 

** See AMEi 6 iNET data sheet

S2

S2/DIP 1 

OFF: analog MCV 

control signal

 

ON: 3-point MCV

 1

 control signal

S2/DIP 2 

OFF: analog MCV 

control signal

ON: 3-point MCV

 2

 control signal

S2/DIP 3 

Not used 
S2/DIP 4* 

OFF: Analog signal (V/mA)

Actuator operates in analog mode

ON: MOD BUS 

Actuator operates in digital mode

*In analog mode S2/DIP 4 = OFF,  DIP 

switches S1/DIP 1-7 work as active 

functions.

In digital mode S2/DIP 4 = ON , DIP 

switches S1/DIP 1-7 work as a digital 

addresses.

In digital mode Modbus RS485 could be 

used either for the monitoring  purposes or 

for the AMEi 6 actuator positioning.

3

Fig. 2

Calibration 

Calibration to the desired pressure actuator 

stroke (min-max spring setting). 

Before calibration drive the actuator out of end 

positions (minimal gap between sliders 

,

 

and pin on the end switch 

 has to be ensured).

To start calibration procedure, press and hold 

RESET button for 5 seconds until the green light 

starts flashing. End positions of the actuator are 

automatically adopted based on pre-set end 

switch positions sliders 

,

. Actuator goes 

to the stationary mode and starts responding 

to the control signal. Depends on min-max Δp 

setting (position of sliders 

 and 

), calibration 

may take up to ~1 h (in case of max available  Δp 

range-stroke is set).

Calibration procedure need to be repeated every 

time when min/max spring setting is changed 

(position of sliders 

 and 

 is changed).

LED signalisation 

Dimensions 

Summary of Contents for AMEi 6 iSET

Page 1: ...te AMEi 6 iSET www heating danfoss cn Pagina 13 中文 智能电动驱动器 AMEi 6 iSET www heating danfoss pl 第 14 页 POLSKI Inteligentny siłownik elektryczny AMEi 6 iSET www danfoss pl Strona 15 РУССКИЙ Интеллектуальный редукторный электропривод AMEi 6 iSET www heating danfoss ru Страница 16 Intelligent electrical actuator AMEi 6 iSET Operating Guide This document is included in the scope of delivery The latest d...

Page 2: ...2 Danfoss 2019 04 VI IR W2 9Z AMEi 6 PH2 6 mm 36mm 5 95 RH no condensing MAINTENANCE FREE AMEi 6 iSET Application principle ...

Page 3: ... elettrica 电源 Zasilanie Напряжение питания Y 0 2 10 V Input Eingang Entreé Ingresso 输入 Wejście Вход 0 4 20 mA X 0 2 10 V Output Ausgang Sortie Uscita 输出 Wyjście Выход 0 4 20 mA A D Modbus B D GND Ground Masse Masse Terra 接地 Masa Заземление 4 1 GND Y Y2 X A B GND AMEi 6 iSET 24V 230V AMV 3P POI module SN SP 4 1 3 5 Y X GND AMV 3P POI module SN SP 4 1 3 5 Y X GND MODBUS 3P control signal 3P POI modu...

Page 4: ...4 Danfoss 2019 04 VI IR W2 9Z AMEi 6 min 65 1 36 mm 1 6 mm Click 150 mm 3x ...

Page 5: ...ession maintenue pendant 10 s movimento AUTOMATICO premuto per 10s 自动控 制 按压 10秒 AUTO ruch przyciskaj 10s АВТОМАТИЧЕСКОЕ перемещение нажимать 10 с pressed for 1s 1 s lang gedruckt pression maintenue pendant 1 s premuto per 1s 按压 1秒 przyciskaj 1s нажимать 1 с 1s RESET STAND BY ON OFF RESET RESET RESET Press any key to stop AUTO move Drucken Sie eine beliebige Taste um die AUTO Bewegung zu stoppen Ap...

Page 6: ...6 Danfoss 2019 04 VI IR W2 9Z AMEi 6 GREEN LED GREEN LED 5s RESET RESET S1 S2 ...

Page 7: ...nym położeniu granicznym Нормальный режим Редукторный электропривод останавливается в крайнем верхнем положении Actuator has reached the bottom end position stretched spring Stellantrieb hat die untere Endlage erreicht Feder ausgefahren L actionneur a atteint la position de fin de course inférieure ressort allongé L attuatore ha raggiunto la posizione finale inferiore molla allungata 驱动器已达到 下端 弹簧拉...

Page 8: ...te COMPRIMI MOLLA 10 sec L attuatore sta comprimendo la molla 手动模式 按下 拉伸弹簧 按钮 10 秒 驱动器正在拉伸弹簧 Tryb pracy ręcznej Przycisk ŚCIŚNIĘCIE SPRĘŻYNY 10 s Siłownik ściska sprężynę Ручной режим Кнопка SQUEEZE SPRING Сжатие пружины 10 с Редукторный электропривод сжимает пружину Actuator is stretching the spring Stellantrieb fahrt die Feder auseinander L actionneur allonge le ressort L attuatore sta allungand...

Page 9: ...Tipo indicazione 指示类型 Typ wskazania Вид индикации Modbus communication status Modbus Kommunikationsstatus Statut de la communication Modbus Stato della comunicazione Modbus Modbus 通信状态 Stan komunikacji Состояние связи Modbus No power supply Keine Spannungsversorgung Absence d alimentation Alimentazione elettrica assente 无电源 Brak zasilania elektrycznego Отсутствие питания Dark Aus Éteinte Scuro 不亮 ...

Page 10: ...put signal ON Not to be used for iSET S1 DIP 4 Normal or sequential mode selector OFF Actuator is working in range 0 2 10 V or 0 4 20 mA ON Actuator is working in sequential range 0 5 V or 0 10 mA or 5 10 V or 10 20 mA Signal range selector S1 DIP 6 sets the sequential range S1 DIP 5 0 10 V 2 10 V Input output OFF 0 10 V input signal is in the range from 0 10 V voltage input or from 0 20 mA curren...

Page 11: ... 4 Wahlschalter für den Betriebsmodus Normal oder Sequentiell AUS Der Stellantrieb arbeitet im Bereich von 0 2 bis 10 V oder 0 4 bis 20 mA EIN Der Stellantrieb arbeitet im sequentiellen Bereich 0 5 V oder 0 10 mA oder 5 10 V oder 10 20 mA Der Signalbereichswahlschalter S1 DIP 6 stellt den sequentiellen Bereich ein S1 DIP 5 0 10 V 2 10 V Ein Ausgang AUS 0 10 V Eingangssignal liegt im Bereich von 0 ...

Page 12: ...age de 0 2 à 10 V ou de 0 4 à 20 mA MARCHE L actionneur fonctionne sur une plage séquentielle 0 5 V ou 0 10 mA ou 5 10 V ou 10 20 mA Le sélecteur de plage de signal S1 DIP 6 détermine la plage séquentielle S1 DIP 5 0 10 V 2 10 V Entrée sortie ARRÊT 0 10 V le signal d entrée se situe dans une plage de 0 à 10 V tension d entrée ou de 0 à 20 mA courant d entrée MARCHE 2 10 V le signal d entrée se sit...

Page 13: ...Selettore di modalità normale o sequenziale OFF L attuatore lavora nell intervallo 0 2 10 V o 0 4 20 mA ON L attuatore lavora in un intervallo sequenziale 0 5 V o 0 10 mA o 5 10 V o 10 20 mA Il selettore dell intervallo del segnale S1 DIP 6 imposta l intervallo sequenziale S1 DIP 5 0 10 V 2 10 V Ingresso uscita OFF 0 10 V il segnale in ingresso rientra nell intervallo 0 10 V ingresso tensione o 0 ...

Page 14: ... 0 5 V 或 0 10 mA 或 5 10 V 或 10 20 mA 信号范围选择开关 S1 DIP 6 设定分段模式 S1 DIP 5 0 10 V 2 10 V 输入 输出 关 0 10 V 输入信号范围为 0 10 V 电压 输入 或者 0 20 mA 电流输入 开 2 10 V 输入信号范围为 2 10 V 电压 输入 或者 4 20 mA 电流输入 信号范围选择开关 S1 DIP 1 与 DIP 2 设定 Y 与 X 信号 S1 DIP 6 分段模式选择开关 关 0 5 V 或 0 10 mA 开 5 10 V 或 10 20 mA S1 DIP 4 开 S1 DIP 7 关 iSET 开 iNET S1 DIP 8 未使用 请见 AMEi 6 iNET 数据表 S2 S2 DIP 1 关 模拟 MCV 1 控制信号 开 3 点 MCV 1 控制信号 S2 DIP 2 关 模...

Page 15: ...ia siłownika Rys 2 WYŁ Siłownik działa w kierunku zgodnym z sygnałem wejściowym WŁ Nie stosować w przypadku iSET S1 DIP 4 Wybór pracy w trybie normalnym lub sekwencyjnym WYŁ siłownik pracuje w zakresie 0 2 10 V lub 0 4 20 mA WŁ Siłownik pracuje w zakresie sekwencyjnym 0 5 V lub 0 10 mA lub 5 10 V lub 10 20 mA Wybór zakresu sygnału S1 DIP 6 ustawia zakres sekwencyjny S1 DIP 5 0 10 V 2 10 V wejście ...

Page 16: ...едукторный электропривод работает по принципу прямого действия ОN вкл не используется для iSET S1 DIP 4 Переключатель нормального или последовательного режима работы ОFF выкл редукторный электропривод работает в диапазоне 0 2 10 В или 0 4 20 мА ОN вкл редукторный электропривод работает в последовательном диапазоне 0 5 В или 0 10мА или 5 10 В или 10 20 мА Переключатель диапазонов сигналов S1 DIP 6 ...

Reviews: