AK-SM 350 Version 1.7x
Manual RS8EF402 © Danfoss 02-2009
7
Type
Measuring points
Description
Language
Code no.
AK-SM 350
16
With inputs for PT 1000 ohm,
PTC 1000 ohm , NTC 5000 ohm
English, German, French,
Dutch, Italian
080Z8500
English (UK), Spanish,
Portuguese, English (US)
080Z8502
English, Danish,
Swedish, Finnish
080Z8503
m2+
16
With inputs for PT 1000 ohm,
PTC 1000 ohm
080Z8005
Cable for PC
(see also AK-ST 500 literature)
RJ 45 - Com port
080Z0262
Printer cable 3 m (parallel)
080Z8401
Modem cable
080Z0261
Ordering
Power supply
230 V +10/-15%, 50/60 Hz, 5 VA
Connection
PT 1000 ohm at 0°C or
PTC 1000 ohm at 25°C or
Digital On/Off signal or
Standard 4-20 mA signal
Measuring range
-60 to +50°C
Measuring accuracy at PT 1000
+/-0.5 K in the range -35 to +25°C
+/-1 K in the range below -35°C
+/-1 K in the range above 25°C
Data communication
RS485 - TP (TP stands for Third
Party)
Enclosure
IP 20
Ambient
environ-
ment
0 to 50°C, during operation
-20 to +70°C, during transport
20-80% RH, Non-condensed
No shock loads/vibrations
Approvals
EN 60730-1 and EN 60730-2-9
EN 50081-1 and EN 50082-1
Weight
1.6 Kg
m2+ (accessories)