13. Text for the high temperature alarm
This is where you can enter the alarm text that is to follow a high
temperature alarm from this reading. If you do not enter a text, a
factory-set text will appear.
Fx "Max temp Point _".
14. Text for the low temperature alarm
This is where you can enter the alarm text that is to follow a low
temperature alarm from this reading. If you do not enter a text, a
factory-set text will appear. Fx "Min temp Point _".
15. Priority of high temperature alarms
Set the priority
The setting determines the sort/action which must be carried out
when an alarm occurs.
• "High" is the top priority
• "Log only" is the lowest priority
• "Disabled" does not initiate any action
The relationships between the setting and action are as follows:
Setting
Log
Alarm relay
Network
AKM
destination
(priority)
Non
High
Low - High
High
X
X
X
X
1
Medium
X
X
X
2
Low
X
X
X
3
Log only
X
Disabled
16. Priority of low temperature alarms
Same setting as for high temperature.
17. Cancelling alarms during defrost
If a defrost signal is registered at a given point, an alarm will not
be triggered. When the signal disappears again, alarms will be
permitted.
Set the point, which follows the defrost signal.
18. Temperature reading offset
Corrections to the sensor signal can be made here.
The correction is used when the sensor wires are long.
19. Is there a configuration error?
The value on this line is normally = 0.
Any other value indicates that an error has occurred. The explana-
tions are as follows:
0: No error.
1: Incorrect address entered – it cannot be found in the network
list or it cannot be used for this point type.
2: Incorrect point entered – the number is outside those permitted
for this unit.
3: The unit does not support this point type.
4: The transmitter type is not supported.
5: The input signal specified is already in use as a signal for an-
other point, and this signal has been defined differently.
6: Incorrect setting for defrost signal. The point cannot be found or
has not been defined for the type "Defrost".
7: Internal system error. Try turning the unit off and on again.
8: The controller or software version is newer, which means the
monitoring unit does not recognise its data. See Appendix 1 for
instructions on how to generate a template that can be used in
the AK-SM 350.
9: The data is not presented correctly. Try selecting another setting
in the function "Template view".
10: The log capacity has been exceeded. Log data cannot be
stored for one year. Extend the interval time for one or more
readings.
11: Too many ‘Template views’ have been created.
12: The selected reference point for power meter reading is inva-
lid.