Manual RS8GP102 © Danfoss 08-2013 

5

Preparing the system manager

1. Set its address on the front to 1 (there must always be a system 

manager with address 1 on a network (1=master)). If there are 

several networks and thus several system managers, they must 

have addresses 2 to 10.

2. Connect the controllers to the two data communications, LON 

and MODBUS. Switch on the controllers and set an address in 

each controller. Addresses may not be duplicated – not even 

with addresses on the Daikin-NET, the Comm. box’s 3 addresses 

or the addresses adjusted with an offset.

3. Apply power to the system manager

4. If a static IP address is used, this must be set

5. Enter the system manager's service PIN

Preparing the AK-PI 300

1. Set its address on the front (e.g. to 12)

(possible range = 11-999)

2. Apply the power

3. If a static IP address is used, this must be set

4. (You can activate the “Service PIN” function at this point. 

If you do, this means you do not have to start the scan function 

in the next point.)

Perform the first scan

1. Start the scan function in the system manager – wait for the 

results

(the controllers on the LON and MODBUS communication will 

now be located and visible in the network overview). 

2. Go to the next page of the network overview, which details the 

IP registrations.

Check that the AK-PI 300 unit is registered.

Interconnection

Define which AK-PI 300 unit the system manager should recognise 

(several units can be registered but the system manager with 

address 1 can only control two units.

1. There is a menu in the system manager in which settings must 

be entered. Go to the Setup menu/Protocol interface (the 

system manager must be version 1.20 or later).

2. Select the address of the AK-PI 300, which is to be connected to 

the system unit.

Perform scan number 2 and locate the Daikin units

Precondition: 

Daikin units must be connected to AK-PI 300 on the Modbus termi-

nals. (This output is adapted to the Daikin Modbus Protocol and 

can only be used for Daikin units.) 

1. Perform a new scan of the system manager. Wait for the results. 

(All controllers will now be located.)

Se manualen for systemmanageren for yderligere installation.

Daikin units

Summary of Contents for AK-PI 300

Page 1: ...Protocol interface AK PI 300 Manual...

Page 2: ...outdoor unit is connected via a Comm box Principle The link between the system manager and the AK PI 300 is via a TCP IP In this very simple connection the two units can be connected to each other vi...

Page 3: ...ress can be viewed in the IP list Up to two PI units can be connected to the system manager which is master i e has address 1 You set the network address on the front of the system units and on the fr...

Page 4: ...ted to a router or to a switch A dynamic or static IP address is used here 2 Setting a Router Dynamic There are no settings in the router Static A static address range must be set in the router b AK S...

Page 5: ...in the next point Perform the first scan 1 Start the scan function in the system manager wait for the results the controllers on the LON and MODBUS communication will now be located and visible in th...

Page 6: ...it is set with the 2 subsequent ones The units on an RTD network must not have an address that coincides with these 3 addresses Requirements and terms Principle Network addresses Here is a small summa...

Page 7: ...manager that AK PI 300 is connected to The status of the alarm transmission Date and time The quality of the Daikin communication signal The configuration display gives access to the following The con...

Page 8: ...ansformer module 230 V 115 V to 24 V AK PS 075 18 VA Supply 080Z0053 Type Function Application Language Code no AK PI 300 Protocol interface Intermediary link between system manager and units with Dai...

Reviews: