background image

Manual RS8GP102 © Danfoss 08-2013 

AK-PI 

300

Introduction

Function

The AK-PI 300 is an intermediary link allowing Daikin type 

controllers to be operated via a System Manager, e.g. AK-SM 720 

or similar. 

The actual operation of the controllers is carried out with an AK-ST 

500.

Daikin units include data communication, where communication 

is controlled by a Daikin Comm. box or a Daikin RTD-network.

The three units: “Outdoor unit”, “Booster unit” and “Indoor unit” 

can be connected to the Comm. box and “Indoor unit” to RTD-

network.

Application

The AK-PI 300 is used on systems where the system unit is an  

AK-SM 720 and where there is/are one or more Daikin type units.

AK-PI 300 links communication to Daikin so that the system  

manager can present all the controllers on the system.

Daikin units are presented on an equal footing together with  

LON RS 485 controllers and MODBUS controllers.

All controllers can be viewed and operated from the system  

manager’s network overview.

The network list on the right shows two RTD-networks, and an 

outdoor unit. The outdoor unit is connected via a Comm. box.

Principle

The link between the system manager and the AK-PI 300 is via a 

TCP/IP. 

In this very simple connection the two units can be connected to 

each other via a crossed cable.

This is where the IP addresses are set to static addresses.

On larger systems or where there is also outgoing IP 

communication from the system, the connection must be made 

via a router.

Here the IP addresses can be dynamic, but if there is 

communication to the system from outside, they must be static.

If you are not sure whether you should select static or dynamic, abide 

by the following recommendation:

Dynamic is the easiest. Here the router itself allocates an address 

for the system manager and another for the PI unit. But you 

should only select this solution if the system is closed without a 

connection for an external operation interface.

With static you must obtain a couple of addresses yourself at the 

local IT department and you must also set the addresses yourself 

in the two units. This solution must always be used when the 

system is operated by an external service company, e.g. for log 

collection, alarm management or service. 

Contents

Introduction ....................................................................................................... 2
Installation .......................................................................................................... 4
Requirements and terms ............................................................................... 6
Ordering .............................................................................................................. 8
Data ....................................................................................................................... 8

Summary of Contents for AK-PI 300

Page 1: ...Protocol interface AK PI 300 Manual...

Page 2: ...outdoor unit is connected via a Comm box Principle The link between the system manager and the AK PI 300 is via a TCP IP In this very simple connection the two units can be connected to each other vi...

Page 3: ...ress can be viewed in the IP list Up to two PI units can be connected to the system manager which is master i e has address 1 You set the network address on the front of the system units and on the fr...

Page 4: ...ted to a router or to a switch A dynamic or static IP address is used here 2 Setting a Router Dynamic There are no settings in the router Static A static address range must be set in the router b AK S...

Page 5: ...in the next point Perform the first scan 1 Start the scan function in the system manager wait for the results the controllers on the LON and MODBUS communication will now be located and visible in th...

Page 6: ...it is set with the 2 subsequent ones The units on an RTD network must not have an address that coincides with these 3 addresses Requirements and terms Principle Network addresses Here is a small summa...

Page 7: ...manager that AK PI 300 is connected to The status of the alarm transmission Date and time The quality of the Daikin communication signal The configuration display gives access to the following The con...

Page 8: ...ansformer module 230 V 115 V to 24 V AK PS 075 18 VA Supply 080Z0053 Type Function Application Language Code no AK PI 300 Protocol interface Intermediary link between system manager and units with Dai...

Reviews: