Manual RS8GP102 © Danfoss 08-2013 

AK-PI 

300

Installation

Preparing addresses on the Daikin-network

Note down which addresses the units have,

e.g.:

Outdoor = 6

Booster = 1

Indoor = 2

These must be adapted in order to prevent these addresses from 

conflicting with each other and other controller addresses on the 

network overview. 

Duplication of addresses is not permitted.

Set a value for the Comm. box connections that will increase the 

address value so as to prevent duplication.

E.g. 100, 200 and 300, as shown in the image on the right.  

The values constitute factory default settings.

In the network overview they will subsequently be shown as 

offset by either:

100 for outdoor (displayed as 106) 

200 for booster (displayed as 201)

300 for indoor (displayed as 302).

Preparing TCP/IP connection

The AK-PI 300 must have a connection to the system manager – 

both physically and with a software setting. This can take place in 

one of the following ways:

1. Connection

a) Direct connection (only used if there is not an external 

connection via a router).

The cable between the two units must be a crossed cable.

(A static IP address is always used here.)

b) Cables from the units are connected to a router or to a switch.

(A dynamic or static IP address is used here.)

2. Setting

a) Router

- Dynamic: There are no settings in the router

- Static: A static address range must be set in the router

b) AK-SM 720

- Select static if the connection between the system unit and 

the AK-PI 300 is with a crossed cable or there is an external 

connection to the system. Then set the IP address (an IP 

address must be obtained from the local IT manager).

- Select dynamic if it is a closed system and the two units are 

connected to a router or a switch. 

c) In the AK-PI 300 the IP address is set either to static or to 

dynamic.

- Select static if the connection between the system unit and 

the AK-PI 300 is with a crossed cable. Then set the IP address 

(an IP address must be obtained from the local IT manager).

- Select dynamic if it is a closed system and the two units are 

connected to a router or a switch. 

3. If a router or switch is connected, it must be turned on.

1a)

1b)

Crossed cable

RTD = 9600

Note

•  The address of Comm. box will take up 3 addresses, the set address and the  

two subsequent ones.

• RTD can only run at 9600 baud.

•  Omit indoor units on Comm. box: If an indoor unit is connected to both an  

RTD and outdoor unit, the scanning of indoor units on the Comm. box can  

be deselected. Otherwise, they will appear twice in the system.

Only via Comm. box 

Only via Comm. box 
Only via Comm. box 

Summary of Contents for AK-PI 300

Page 1: ...Protocol interface AK PI 300 Manual...

Page 2: ...outdoor unit is connected via a Comm box Principle The link between the system manager and the AK PI 300 is via a TCP IP In this very simple connection the two units can be connected to each other vi...

Page 3: ...ress can be viewed in the IP list Up to two PI units can be connected to the system manager which is master i e has address 1 You set the network address on the front of the system units and on the fr...

Page 4: ...ted to a router or to a switch A dynamic or static IP address is used here 2 Setting a Router Dynamic There are no settings in the router Static A static address range must be set in the router b AK S...

Page 5: ...in the next point Perform the first scan 1 Start the scan function in the system manager wait for the results the controllers on the LON and MODBUS communication will now be located and visible in th...

Page 6: ...it is set with the 2 subsequent ones The units on an RTD network must not have an address that coincides with these 3 addresses Requirements and terms Principle Network addresses Here is a small summa...

Page 7: ...manager that AK PI 300 is connected to The status of the alarm transmission Date and time The quality of the Daikin communication signal The configuration display gives access to the following The con...

Page 8: ...ansformer module 230 V 115 V to 24 V AK PS 075 18 VA Supply 080Z0053 Type Function Application Language Code no AK PI 300 Protocol interface Intermediary link between system manager and units with Dai...

Reviews: