AK-PI 

300 

Manual RS8GP102 © Danfoss 08-2013 

3

Number of Daikin units

One Comm. box and three RTD units can be connected to a single 

AK-PI 300. 

If there are more, use 2 (x) AK-PI 300 units. 

Up to two AK-PI-300 units can be connected to a single system 

manager, i.e. up to 2 Comm. boxes and 6 RTD units. 

If there are two AK-PI 300 units, the connection to the system 

manager is led via a router or a switch.

(Up to 32 outdoor units, 30 booster units and 64 indoor units can 

be connected to a single Comm. box. Up to 16 indoor units can be 

connected to a single RTD unit.)

Addresses

In principle there are three types of addresses:

IP addresses

Both the system manager and the AK-PI 300 must have an IP 

address set.

The address can be either dynamic or static – the desired value is 

selected with a setting. If static is chosen, an address must also be 

set.

If the system can be accessed externally, the setting in the 

system manager AK-SM 720 must always be set to static so that 

the external connection always recognises the address and can 

communicate with the unit.

(The IP address is set in a menu).

Network addresses

There must always be one and only one master system manager 

on a network. This is defined with the address setting = 1. This 

system manager controls the communication to all the other 

controllers on the network. The PI unit is perceived as a controller 

on the network and its address can be viewed in the IP list. (Up to 

two PI units can be connected to the system manager, which is 

master - i.e. has address =1)

(You set the network address on the front of the system units and 

on the front of the PI units.) 

Set the system manager to address 1.

If there are several system managers (slave network), set these to 

addresses 2 to 10.

Each PI unit is set with a separate address. Select 12 or higher, e.g. 

21.

Interconnection

When setting the system manager, a menu must also be set in 

which the relevant AK-PI 300 chooses the network. The system 

manager then knows the way to the different Daikin units. The 

system manager must be version 1.20 or later.

Controller addresses

All controllers on the same network must have different addresses. 

In other words, all controllers that are connected to a system 

manager on either:

• the LON communication

• the MODBUS communication

• the DANBUSS communication or

• Daikin

 

communication.

Start with the addresses on Daikin RTD-NET.  

Then for DANBUSS, if needed (via AK-PI 200).

A Daikin Comm. box registers 3 addresses. 

After this, add the addresses on the Daikin Comm. box connec-

tions. (These address numbers can be offset. See next page.)

 

The addresses on the LON and MOD buses can be set higher.

No more than 200 controllers can be connected to a system 

manager.

Daikin Outdoor:  

Address options 1 to 32

Daikin Booster:  

Address options 1 to 30

Daikin Indoor:  

Address options 1 to 64

DANBUSS communication:  

Address options 1 to 120

LON-communication:  

Address options 1 to 999

MOD-bus communication:  

Address options 1 to 247

Max. number of controllers:  

200 pcs.

Summary of Contents for AK-PI 300

Page 1: ...Protocol interface AK PI 300 Manual...

Page 2: ...outdoor unit is connected via a Comm box Principle The link between the system manager and the AK PI 300 is via a TCP IP In this very simple connection the two units can be connected to each other vi...

Page 3: ...ress can be viewed in the IP list Up to two PI units can be connected to the system manager which is master i e has address 1 You set the network address on the front of the system units and on the fr...

Page 4: ...ted to a router or to a switch A dynamic or static IP address is used here 2 Setting a Router Dynamic There are no settings in the router Static A static address range must be set in the router b AK S...

Page 5: ...in the next point Perform the first scan 1 Start the scan function in the system manager wait for the results the controllers on the LON and MODBUS communication will now be located and visible in th...

Page 6: ...it is set with the 2 subsequent ones The units on an RTD network must not have an address that coincides with these 3 addresses Requirements and terms Principle Network addresses Here is a small summa...

Page 7: ...manager that AK PI 300 is connected to The status of the alarm transmission Date and time The quality of the Daikin communication signal The configuration display gives access to the following The con...

Page 8: ...ansformer module 230 V 115 V to 24 V AK PS 075 18 VA Supply 080Z0053 Type Function Application Language Code no AK PI 300 Protocol interface Intermediary link between system manager and units with Dai...

Reviews: