AK-LM 350
RS8GX102 © Danfoss 10-2013
55
5. Configuration of Analog
inputs signals
Configuration - continued
We set up the analog inputs for the sensors, pressure transmit-
ters and voltage signals.
5 - Analog inputs
The possible signals are the
following:
Temperature sensors
:
S1 - S40
Setting:
• Pt1000
• PTC 1000
Pressure transmitters::
P1 - P20
Setting:
• AKS 32, -1 – 6 Bar
• AKS 32R, -1 – 6 Bar
• AKS 32, - 1 – 9 Bar
• AKS 32R, -1 – 9 Bar
• AKS 32, - 1 – 12 Bar
• AKS 32R, -1 – 12 Bar
• AKS 32, - 1 – 20 Bar
• AKS 32R, -1 – 20 Bar
• AKS 32, - 1 – 34 Bar
• AKS 32R, -1 – 34 Bar
• AKS 32, - 1 – 50 Bar
• AKS 32R, -1 – 50 Bar
• AKS 2050, -1 – 59 Bar
• AKS 2050, -1 – 99 Bar
• AKS 2050, -1 – 159 Bar
• User defined (only ratio-
metric. The min. and max.
values of the pressure
interval must be set).
Voltage signals:
Voltage input 1 - 20
Setting:
• 0 - 5
• 1 - 5
• 0 - 10
• 2 - 10
Analoge signals
Inlet
Module Point
Type
Ss MT
AI1
1
1
Pt 1000
Sd MT
AI2
1
2
Pt 1000
Comp. capacity MT
AI3
1
3
0-10 V
Stw2
AI4
1
4
Pt 1000
Shr2
AI5
1
5
Pt 1000
Pgc MT
AI6
1
6
AKS 2050-159
Prec MT
AI7
1
7
AKS 2050-159
AI8
1
8
AI9
1
9
Po MT
AI10
1
10
AKS 2050-59
Pc MT
AI11
1
11
AKS 2050-159
Sc3
AI1
2
1
Pt 1000
Shp
AI2
2
2
Pt 1000
AI3
2
3
Po LT
AI4
2
4
AKS 2050-59
Ss LT
AI5
2
5
Pt 1000
Sd LT
AI6
2
6
Pt 1000
Comp. capacity LT
AI7
2
7
0-10 V
AI8
2
8