AK-LM 350
RS8GX102 © Danfoss 10-2013
49
Set plant type
1. Go to Configuration menu
2. Select plant type
Press the line Select plant type.
3. Set plant type
Configuration - continued
3-
Select plant type
Select how many measurements of each type that will be
used by the controller here.
One measurement can be used by several functions,
so that, later, when setting the individual function, you
select the measurement that will be used.
Number of temperature sensors:
Number of pressure readings:
Number of voltage inputs:
Number of digital inputs (DIs):
Number of energy readings:
Number of thermostats
Number of pressostats
Number of voltage signals
Number of digital inputs
COP calculation. (The controller will subsequently
display what readings are required.)
Alarm relays
Define whether a relay which is enabled for alarms with
high priority is to be used.
Define whether a relay which is enabled for alarms with
all priorities is to be used.
If an alarm relay is defined, it will activate an alarm
that must be reset externally.
Select quick setup
You can reset all settings and return to factory settings
here.
In the example, we have decided to
use the following number of input
signals for the COP calculation:
• 8 temperature sensors
• 5 pressure transmitters
• 2 voltage inputs
• 2 digital inputs
Set COP calculation to YES