52
RS8GX102 © Danfoss 10-2013
AK-LM 350
Configuration - continued
DI alarms
• Name
• Select sensor
• Alarm function
Start or stop of the alarm function.
• Alarm delay
• Alarm text
• Use relay output
Specify if a relay is to be used for this alarm
function.
• ON time total
Here the user can see how long the function
has been in alarm mode. All ON times are
summed up. It is possible to reset or change
the read-out.
• Cyclus total
Here the user can see how many times the
alarm has occurred. It is possible to reset or
change the read-out.
We have not used this function in our
example. The image is included for guidance
only.
The name of the function may be xx and
further down in the display the alarm texts
may be entered.
Digital alarms
We have not used this function in our
example. The image is included for guidance
only.
The name of the function may be xx and
further down in the display the alarm texts
may be entered.
3 -
Voltage inputs
The general volt inlet can be used to monitor
external voltage signals.
For each volt inlet setup /readout:
•
Name
Actual value
= read-out of the measurement
in %
• Use relay output
Define whether a relay must be used for this volt-
age function.
•
Actual state
= read-out of outlet status
•
Min. readout
State read-out values at minimum voltage
signal
•
Max. readout
State read-out values at maximum voltage
signal
•
Cutout
Cut-out value for outlet (scaled value)
•
Cutin
Cut-in value for outlet (scaled value)
•
Cutout delay
Time delay for cut-out
•
Cut in delay
Time delay for cut-in
•
High alarm limit
High alarm limit
•
High alarm delay
Time delay for high alarm
•
High alarm text
Set alarm text for high alarm
•
Low alarm limit
Low alarm limit
•
Low alarm delay
Time delay for low alarm
•
Low alarm text
Indicate alarm text for low alarm
Voltage controls