background image

6

English

CAUTION

Follow the points at below.

Use a pipe cutter and flare suitable for the type of refrigerant.

Apply ester oil or ether oil to the flare section when using a 
flare connection.

Only use the flare nuts included with the unit. Using different 
flare nuts may cause the refrigerant to leak.

To prevent dust, moisture or other foreign matter from infil-
trating the piping, either pinch the end or cover it with tape.

Do not allow anything other than the designated refrigerant 
to get mixed into the refrigerant circuit, such as air, etc. If any 
refrigerant gas leaks while working on the unit, ventilate the 
room thoroughly right away.

(1) Connect the piping.

The outdoor unit is charged with refrigerant.

Be sure to use both a spanner and torque wrench together, 
as shown in the drawing, when connecting or disconnecting 
pipes to/from the unit. 

(Refer to the left picture below)

Refer to Table 1 for the dimensions of flare nut spaces.

Apply ester oil or ether oil to flare section (both inside and 
out) when using flare nut connections and then turn 3 or 4 
times by hand. 

(Refer to the right picture above)

Refer to Table 1 for tightening torque.

Table 1

CAUTION

Overtightening may damage the flare and cause leaks.

Be careful for oil not to adhere to any portions other 

than a flare part. If oil adheres to resin parts etc., there 

is a possibility of damaging by deterioration.

Refer to Table 2 if no torque wrench is available.
Using a wrench to tighten flare nuts causes the tightening 
torque to suddenly grow much tighter after a certain point.
From there, tighten the nut further by the appropriate angle 
listed in Table 2.

(2) After the work is finished, make sure to check that 

there is no gas leak.

(3) After checking for gas leaks, be sure to insulate the 

pipe connections referring to the following picture.

Insulate using the insulation for fitting (3) (4) included with 
the liquid and gas pipes. Besides, make sure the insula-
tion for fitting (3) (4) on the liquid and gas piping has its 
seams facing up.
(Tighten both edges with clamp (9).)

For the gas piping, wrap the mid. sealing pad (6) over the 
insulation for fitting (4) (flare nut part).

CAUTION

Be sure to insulate any field piping all the way to the piping 

connection inside the unit. Any exposed piping may cause 

condensation or burns if touched.

When brazing the refrigerant piping, perform nitrogen 
replacement first, or perform the brazing (CAUTION 2) while 
feeding nitrogen into the refrigerant piping (CAUTION 1), and 
finally connect the indoor unit using the flare connections. 

(Refer to the picture below)

CAUTION

1. When brazing a pipe while feeding nitrogen inside the 

pipe, make sure to set the nitrogen pressure to 0.02 MPa 
(0.2 kg/cm

2

) using the pressure reducing valve. (This 

pressure is such that breeze is blown to your cheek.)

2. Do not use a flux when brazing the refrigerant pipe joints. 

Use phosphor copper brazer (BCuP-2: JIS Z 3264/B-
Cu93P-710/795: ISO 3677) which does not require flux. 
(Using a flux containing chlorine may cause the piping to 
corrode. Using a welding flux containing fluorine may 
cause the refrigerant lubricant to deteriorate, and affect 
adversely the refrigerant piping system.)

Not recommendable but in case of emergency

You must use a torque wrench but if you are obliged to install the 
unit without a torque wrench, you may follow the installation 
method mentioned below.

After the work is finished, make sure to check that there is 
no gas leak.

Pipe 

size

Tightening torque

Flare dimen-

sion A (mm)

Flare shape

 φ

 6.4

15 – 17 N·m

8.7 – 9.1

 φ

 9.5

33 – 39 N·m

12.8 – 13.2

φ

 12.7

50 – 60 N·m

16.2 – 16.6

 

φ

 15.9

63 – 75 N·m

19.3 – 19.7

Flare nut

Piping union

Ester oil or ether oil

Spanner

Torque wrench

A

45

0

2

0

R0.4-0.8

90

0

2

0

 

Main unit

Wrap over the top of the 
flare nut connection.

(accessory)

(accessory)

Insulation for fitting (3)
(accessory)

Liquid pipe

Main unit

Attach to base

Piping insulation material 
(main unit)

Piping insulation material
(Field supply)

Turn seams up

Flare nut connection

Clamp (9) (accessory)

Piping insulation material
(Field supply)

Clamp (9)
(accessory)

Liquid Piping Insulation Procedure

Gas Piping Insulation Procedure

Insulation for fitting (4)

Mid. sealing pad (6)

Turn seams up

Flare nut connection

Attach to base

Piping insulation 
material (main unit)

Gas pipe

Nitrogen

Nitrogen

Hands 
valve

Pressure-reducing valve

Taping

Part to be brazed

Refrigerant piping

Summary of Contents for VRV SYSTEM FXNQ20A2VEB

Page 1: ...INSTALLATION MANUAL FXNQ20A2VEB FXNQ25A2VEB FXNQ32A2VEB FXNQ40A2VEB FXNQ50A2VEB FXNQ63A2VEB System Inverter Air Conditioners...

Page 2: ...A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o...

Page 3: ...after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply ci...

Page 4: ...by the hanger brackets Do not apply force to the refrigerant piping drain piping or flange parts Be sure to check the type of R410A refrigerant to be used before installing the unit Using an incorrect...

Page 5: ...with ducting and grill which can only be removed with the aid of tooling It shall be installed so that it gives adequate protection against touching the fan If a maintenance panel exists in the ducti...

Page 6: ...ust the unit to fit between the walls 3 Check the unit is horizontally level CAUTION Make sure the unit is installed level using a level or a plastic tube filled with water In using a plastic tube ins...

Page 7: ...to the outdoor unit Execute heat insulation work completely on both sides of the gas piping and the liquid piping Otherwise a water leakage can result sometimes Use insulation that can withstand tempe...

Page 8: ...id sealing pad 6 over the insulation for fitting 4 flare nut part CAUTION Be sure to insulate any field piping all the way to the piping connection inside the unit Any exposed piping may cause condens...

Page 9: ...ia in the sewage might enter the indoor unit through the drain piping and corrode the heat exchanger Do not twist or bend the drain hose 2 so that excessive force is not applied to it This type of tre...

Page 10: ...rth wires Gas pipes gas leaks can cause explosions and fire Water pipes they cannot be grounded if hard vinyl pipes are used Telephone earth wire and lightning rods the ground potential when struck by...

Page 11: ...ck Doing so can destroy the entire system Connecting electrical wiring remote controller wiring and transmission wiring Refer to the following picture Power supply and Earth wiring Remove the control...

Page 12: ...ntroller and working from the 2 positions pry off the upper part 2 loca tions Terminal block Tightening torque N m Remote controller transmission wiring terminal block 6P 0 79 0 97 Power supply wiring...

Page 13: ...E NO and SECOND CODE NO The Field Settings included with the remote controller lists the order of the settings and method of operation Lastly make sure the customer keeps the Field Settings manual alo...

Page 14: ...rouble An explanation of malfunction codes and the correspond ing trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of the following there is a possi bility tha...

Page 15: ...L PARTS X24A CONNECTOR WIRELESS REMOTE CONTROLLER X33A CONNECTOR ADAPTOR FOR WIRING X35A CONNECTOR POWER SUPPLY CONNECTOR X38A CONNECTOR MULTI TENANT WIRED REMOTE CONTROLLER R1T THERMISTOR AIR SS1 SEL...

Page 16: ...4P393318 1B 2015 03 Copyright 2014 Daikin...

Reviews: