![background image](http://html2.mh-extra.com/html/daikin/vrv-system-fxnq20a2veb/vrv-system-fxnq20a2veb_installation-manual_4705215007.webp)
English
5
NOTE: The unit must be installed within a fully enclosed
casing built by others. The casing shall include as minimum
a removable access panel, suction air grille and discharge
air grille. These removable items shall prevent any access
to the unit by its shape, position and by the use of fixings
that require the use of a tool for removal.
1) Positioning of holes for fastening to the wall
Unit of measurement = mm
■
Fixing method of the unit
Make sure that the floor is strong enough to bear the unit.
1) Level the indoor unit with the leveling screws
(accessory part). If the floor is too uneven to level
the unit, place the unit on a flat and level base.
2) If the unit is in danger of falling over, either fasten to
the wall using the holes provided, or fasten to the
floor with a field supplied floor fastener.
6. OUTDOOR UNIT INSTALLATION
Install as described in the installation manual supplied with the
outdoor unit.
7. REFRIGERANT PIPING WORK
For refrigerant piping of outdoor units, see the installation
manual attached to the outdoor unit.
Execute heat insulation work completely on both sides of
the gas piping and the liquid piping. Otherwise, a water
leakage can result sometimes.
Use insulation that can withstand temperatures of at least
120°C. Reinforce the insulation on the refrigerant piping
according to the installation environment. If the tempera-
ture in the wall reaches 30°C or the humidity RH80%, con-
densation may form on the surface of the insulation.
2) Wall mounted installation
Install the unit according to the figures below.
Unit of measurement = mm
A
618
500
740
940
1140
Suspension
bolt pitch
20+25+32 type
40+50 type
63 type
(Suspension bolt pitch)
Air outlet
A
B
Model
A
B
760
D
D
C
)
100
A
Width of air inlet grille
B
C
Air inlet direction
D
Air outlet direction
F
Height of the intake area
300
300
1000
Unit
20
Width of maintenance area
Model
20/25/35 40/50
63
660
1350
1550
860
1750
1060
3) Floor standing concealed installation
Install the unit according to the figures below.
Unit of measurement = mm
B
Model
20/25/35 40/50
63
660
1350
1550
860
1750
1060
Width of maintenance area
A
B
760
C
100
(
200
300
300
1000
Unit
20
A
Width of air inlet grille
C
Air inlet direction
D
Air outlet direction
(
Height of the intake area
D
D