background image

English

3

Also review the “SAFETY PRECAUTIONS”.

b. Items to be checked at time of delivery

c. Points for explanation about operations

3. SELECTING INSTALLATION SITE 

CAUTION

When moving the unit during or after unpacking, make sure 
to lift it by holding its lifting lugs. Do not exert any pressure on 
other parts, especially the refrigerant piping, drain piping and 
flange parts.

If you think the humidity inside the wall might exceed 30°C 
and RH80%, reinforce the insulation on the unit body.
Use glass wool or polyethylene foam as insulation so that 
it is no thicker than 10mm and fits inside the wall opening.

(1) Select an installation site where the following conditions 

are fulfilled and that meets with your customer’s approval.

Where optimum air distribution can be ensured.

Where nothing blocks air passage.

Where condensate can be properly drained.

Where the wall/floor is strong enough to bear the indoor 

unit weight.

Where the floor is not noticeably on an incline.

Where there is no risk of flammable gas leakage.

Where sufficient clearance for maintenance and service 

can be ensured.

Where piping between indoor and outdoor units is possi-

ble within the allowable limit. (Refer to the installation 

manual for the outdoor unit.)

The equipment is not intended for use in a potentially 

explosive atmosphere.

[ PRECAUTION ]

Install the indoor and outdoor units, power supply wiring 
and connecting wires at least 1 m away from televisions or 
radios in order to prevent image interference or noise. 
(Depending on the radio waves, a distance of 1 m may not 
be sufficient enough to eliminate the noise.)

If installing the wireless kit in a room with electronic fluo-
rescent lighting (inverter or rapid start type), the remote 
controller’s transmission distance may be shortened. 
Indoor units should be installed as far away from fluores-
cent lighting as possible.

(2) Use suspension bolts for installation. Check whether 

the wall/floor is strong enough to support the weight of 
the unit or not. If there is a risk, reinforce the wall/floor 
before installing the unit.

To avoid contact with the fan, the following precaution action must be 
taken:

-

Install the unit with ducting and grill which can only be 
removed with the aid of tooling. It shall be installed so that 
it gives adequate protection against touching the fan. If a 
maintenance panel exists in the ducting, it shall only be 
possible to remove the panel by the aid of tooling to avoid 
contact with the fan. The protection shall be according to 
relevant European and local legislation. There are no 
restrictions concerning the installation height.

4. PREPARATIONS BEFORE INSTALLATION

(1) Make sure the range of the unit’s external static pres-

sure is not exceeded.

(See the technical documentation for the range of the 
external static pressure setting.)

(2) In case of front suction:

(1) Remove the protection net.

(2) Remove the chamber lid. (7 locations)
(3) Remove one leg on the opposite side of the el. compo 

(for instruction, see page 4, “Removing the legs”).

(4) Reattach the removed chamber lid in the orientation 

shown in picture 2 below. (7 locations)

(5) Attach the protection net to the front side.

(6) Reattach the leg if necessary.

(7) Attach the air filter (accessory) in the manner shown in 

the diagram.

 

Is something blocking the air 
outlet or inlet of either the 
indoor or outdoor units?

It may result in insufficient 
cooling.

Are refrigerant piping length 
and additional refrigerant 
charge noted down?

The refrigerant charge in the 
system is not clear.

Items to be checked

Check

Did you explain about operations while showing the 
operation manual to your customer?
Did you hand the operation manual and warranty over to 
your customer?
Did you explain about the way of maintaining and cleaning 
local procurements (air filter, grille (both air outlet and suc-
tion grille), etc.) to your customer?
Did you hand manuals of local procurements (in case 
equipped) over to your customer?

The items with 

WARNING and 

CAUTION marks in 

the operation manual are the items pertaining to 
possibilities for bodily injury and material damage in 
addition to the general usage of the product. Accordingly, it 
is necessary that you make a full explanation about the 
described contents and also ask your customers to read the 
operation manual.

(1)

(2)

Air inlet

Air discharge

Air inlet

Air discharge

Chamber lid

Protection net

Protection net

Chamber lid

Attach the 
filter to the 
main unit 
while pushing 
down on the 
bends.

In case of front side

In case of bottom side

Main unit

Force

Force

Filter

Summary of Contents for VRV SYSTEM FXNQ20A2VEB

Page 1: ...INSTALLATION MANUAL FXNQ20A2VEB FXNQ25A2VEB FXNQ32A2VEB FXNQ40A2VEB FXNQ50A2VEB FXNQ63A2VEB System Inverter Air Conditioners...

Page 2: ...A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o...

Page 3: ...after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply ci...

Page 4: ...by the hanger brackets Do not apply force to the refrigerant piping drain piping or flange parts Be sure to check the type of R410A refrigerant to be used before installing the unit Using an incorrect...

Page 5: ...with ducting and grill which can only be removed with the aid of tooling It shall be installed so that it gives adequate protection against touching the fan If a maintenance panel exists in the ducti...

Page 6: ...ust the unit to fit between the walls 3 Check the unit is horizontally level CAUTION Make sure the unit is installed level using a level or a plastic tube filled with water In using a plastic tube ins...

Page 7: ...to the outdoor unit Execute heat insulation work completely on both sides of the gas piping and the liquid piping Otherwise a water leakage can result sometimes Use insulation that can withstand tempe...

Page 8: ...id sealing pad 6 over the insulation for fitting 4 flare nut part CAUTION Be sure to insulate any field piping all the way to the piping connection inside the unit Any exposed piping may cause condens...

Page 9: ...ia in the sewage might enter the indoor unit through the drain piping and corrode the heat exchanger Do not twist or bend the drain hose 2 so that excessive force is not applied to it This type of tre...

Page 10: ...rth wires Gas pipes gas leaks can cause explosions and fire Water pipes they cannot be grounded if hard vinyl pipes are used Telephone earth wire and lightning rods the ground potential when struck by...

Page 11: ...ck Doing so can destroy the entire system Connecting electrical wiring remote controller wiring and transmission wiring Refer to the following picture Power supply and Earth wiring Remove the control...

Page 12: ...ntroller and working from the 2 positions pry off the upper part 2 loca tions Terminal block Tightening torque N m Remote controller transmission wiring terminal block 6P 0 79 0 97 Power supply wiring...

Page 13: ...E NO and SECOND CODE NO The Field Settings included with the remote controller lists the order of the settings and method of operation Lastly make sure the customer keeps the Field Settings manual alo...

Page 14: ...rouble An explanation of malfunction codes and the correspond ing trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of the following there is a possi bility tha...

Page 15: ...L PARTS X24A CONNECTOR WIRELESS REMOTE CONTROLLER X33A CONNECTOR ADAPTOR FOR WIRING X35A CONNECTOR POWER SUPPLY CONNECTOR X38A CONNECTOR MULTI TENANT WIRED REMOTE CONTROLLER R1T THERMISTOR AIR SS1 SEL...

Page 16: ...4P393318 1B 2015 03 Copyright 2014 Daikin...

Reviews: