background image

English

7

When you keep on tightening the flare nut with a spanner, there 
is a point where the tightening torque suddenly increases. From 
that position, further tighten the flare nut by the angle shown 
below:
Table 2

8. DRAIN PIPING WORK

CAUTION

Make sure all water is out before making the duct connection.

(1) Install the drain piping.

Make sure the drain works properly.

The diameter of the drain piping should be greater than or 
equal to the diameter of the connecting pipe (vinyl tube; pipe 
size: 20 mm; outer dimension: 26 mm). 
(not including the riser)

Keep the drain piping short and sloping downwards at a gra-
dient of at least 1/100 to prevent air pockets from forming.

(Refer to the following picture)

CAUTION

Water accumulating in the drain piping can cause the 
drain to clog.

To keep the drain piping from sagging, space hanging 
bracket every 1 to 1.5 m.

Use the drain hose (2) and the metal clamp (1). Insert the 
drain hose (2) fully into the drain socket and firmly tighten the 
metal clamp (1) with the upper part of the tape on the hose 

end. Tighten the metal clamp (1) until the screw head is less 
than 4 mm from the hose. 

(Refer to the following pictures)

The two areas below should be insulated because conden-
sation may form there causing water to leak.

Drain piping passing indoors

Drain socket

Referring the figure below, insulate the metal clamp (1) and 
drain hose (2) using the included large sealing pad (5).

(Refer to the right picture below)

 

PRECAUTIONS 

Drain piping connections

Do not connect the drain piping directly to sewage pipes that 
smell of ammonia. The ammonia in the sewage might enter 
the indoor unit through the drain piping and corrode the heat 
exchanger.

Do not twist or bend the drain hose (2), so that excessive 
force is not applied to it. 
(This type of treatment may cause leaking.)

If you are using central drain piping, follow the procedure 
outlined in the picture depicting drain piping on this page.

Select central drain piping of proper size according to the 
capacity of the connected unit.

CAUTION

The electric wiring work shall be performed by qualified elec-
tricians.

If workers not having the electrician qualification have per-
formed the electric wiring work, the steps 3 to 7 shall be per-
formed after the 

TEST RUN

.

(2) After piping work is finished, check drainage flows 

smoothly. Gradually insert approximately 1L of water 
into the drain pan to check drainage in the manner 
described below.

• Gradually pour approximately 1L of water from the 

outlet hole into the drain pan to check drainage.

• Check the drainage.

CAUTION

When filling the drainpan with water, be sure that the 
water is sliding down the drainpan wall (see picture 
below). Failure to observe this instruction may result in 
water leakage.

Pipe size

Further tightening angle

Recommended arm 
length of tool

φ 

6.4 (1/4”)

60 to 90 degrees

Approx. 150mm

φ 

9.5 (3/8”)

60 to 90 degrees

Approx. 200mm

φ 

12.7 (1/2”)

30 to 60 degrees

Approx. 250mm

φ 

15.9 (5/8”)

30 to 60 degrees

Approx. 300mm

Connect the drain pipe after 
removing the rubber cap and 
insulation tubing attached to 
the connection hole.

Refrigerant pipes

Drain pipe connection hole

Central drain piping
(with a slope of at least 1/100)

(accessory)

(accessory)

Metal clamp (1)

Large sealing 
pad (5)

≤4mm

(accessory)

(accessory)

Tape

Drain hose (2)

Metal clamp (1)

Portable pump

Bucket

Drain pan

Air outlet

Drain outlet

Refrigerant 

pipes

Summary of Contents for VRV SYSTEM FXNQ20A2VEB

Page 1: ...INSTALLATION MANUAL FXNQ20A2VEB FXNQ25A2VEB FXNQ32A2VEB FXNQ40A2VEB FXNQ50A2VEB FXNQ63A2VEB System Inverter Air Conditioners...

Page 2: ...A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o...

Page 3: ...after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply ci...

Page 4: ...by the hanger brackets Do not apply force to the refrigerant piping drain piping or flange parts Be sure to check the type of R410A refrigerant to be used before installing the unit Using an incorrect...

Page 5: ...with ducting and grill which can only be removed with the aid of tooling It shall be installed so that it gives adequate protection against touching the fan If a maintenance panel exists in the ducti...

Page 6: ...ust the unit to fit between the walls 3 Check the unit is horizontally level CAUTION Make sure the unit is installed level using a level or a plastic tube filled with water In using a plastic tube ins...

Page 7: ...to the outdoor unit Execute heat insulation work completely on both sides of the gas piping and the liquid piping Otherwise a water leakage can result sometimes Use insulation that can withstand tempe...

Page 8: ...id sealing pad 6 over the insulation for fitting 4 flare nut part CAUTION Be sure to insulate any field piping all the way to the piping connection inside the unit Any exposed piping may cause condens...

Page 9: ...ia in the sewage might enter the indoor unit through the drain piping and corrode the heat exchanger Do not twist or bend the drain hose 2 so that excessive force is not applied to it This type of tre...

Page 10: ...rth wires Gas pipes gas leaks can cause explosions and fire Water pipes they cannot be grounded if hard vinyl pipes are used Telephone earth wire and lightning rods the ground potential when struck by...

Page 11: ...ck Doing so can destroy the entire system Connecting electrical wiring remote controller wiring and transmission wiring Refer to the following picture Power supply and Earth wiring Remove the control...

Page 12: ...ntroller and working from the 2 positions pry off the upper part 2 loca tions Terminal block Tightening torque N m Remote controller transmission wiring terminal block 6P 0 79 0 97 Power supply wiring...

Page 13: ...E NO and SECOND CODE NO The Field Settings included with the remote controller lists the order of the settings and method of operation Lastly make sure the customer keeps the Field Settings manual alo...

Page 14: ...rouble An explanation of malfunction codes and the correspond ing trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of the following there is a possi bility tha...

Page 15: ...L PARTS X24A CONNECTOR WIRELESS REMOTE CONTROLLER X33A CONNECTOR ADAPTOR FOR WIRING X35A CONNECTOR POWER SUPPLY CONNECTOR X38A CONNECTOR MULTI TENANT WIRED REMOTE CONTROLLER R1T THERMISTOR AIR SS1 SEL...

Page 16: ...4P393318 1B 2015 03 Copyright 2014 Daikin...

Reviews: