English
9
11. WIRING EXAMPLE
11-1 HOW TO CONNECT WIRINGS
•
Wire only after removing the control box lid as shown in
the picture below, referring to view A or B depending on the
type of unit.
CAUTION
•
Be sure to attach power supply wiring and earth wire to the
control box with the clamp.
•
When doing the wiring, make sure the wiring is neat and
does not cause the control box lid to stick up, then close the
cover firmly. When attaching the control box lid, make sure
you do not pinch any wires.
•
Outside the air conditioners, separate the weak wiring (remote
controller and transmission wiring) and strong wiring (earth
wire and power supply wiring) at least 50 mm so that they do
not pass through the same place together. Proximity may
cause electrical interference, malfunctions, and breakage.
•
A main switch or other means for disconnection, having a
contact separation in all poles, must be incorporated in the
fixed wiring in accordance with relevant local and national
legislation.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.
[ PRECAUTIONS ]
•
Refer to the “REMOTE CONTROLLER INSTALLATION
MANUAL” on how to install and lay the wiring for the remote
controller.
•
See also the “Wiring Diagram plate” attached to the control
box lid when laying electrical wiring.
•
Connect the remote controller and transmission wiring their
respective terminal blocks.
CAUTION
• Do not, under any circumstances, connect the power sup-
ply wiring to the remote controller or transmission wiring
terminal block. Doing so can destroy the entire system.
[ Connecting electrical wiring, remote controller wiring,
and transmission wiring ] (Refer to the following picture)
• Power supply and Earth wiring
Remove the control box lid.
Next, pull the wires into the unit through the wiring through
hole and connect to the terminal block (3P).
Be sure to put the part of the sheathed vinyl into the control
box.
• Remote controller and transmission wiring
Pull the wires into the unit through the wiring through hole
and connect to the terminal block (6P).
Be sure to put the part of the sheathed vinyl into the control
box.
(Rear)
Wiring Diagram
Control box lid
Power supply wiring
Earth wire
*Remote controller wiring
• Make sure to let a wire go through a wire penetration area.
• After wiring, seal the wire and wire penetration area to
prevent moisture and small creatures from the outside.
• Wrap the strong and weak electric lines with the sealing
material as shown in the figure below.
(Otherwise, moisture or small creatures such as insects from
the outside may cause short-circuit inside the control box.)
Attach securely so that there are no gaps.
Wiring through
hole
Sealing material
(accessory)
Wire
[How to adhere it]
Outside
unit
Inside
unit
Power supply
wiring
Earth wire
Indoor PCboard
(ASSY)
Clamps
(for preventing
slippage)
*Transmission wiring
*Remote controller wiring
* Do not connect power
supply wiring here.
That may cause malfunction
Control box
Control box
Transmission wiring / Remote contr. wiring
Indoor PCboard
(ASSY)
Terminal block (6P)
Terminal block (3P)
Remote controller wiring
Transmission wiring
Wiring through hole
Power supply wiring
Earth wire
Clamps
(for preventing
slippage)
OFF
WIRING
FORCED
REMOTE
CONTRL
TRANSMISSION
P
1
P
2
F
1
F
2
T
1
T
2
Wiring through
hole