12 Unit installation

Installation and operation manual

13

FXMQ-A
VRV system air conditioner
3P701545-1 – 2022.07

CAUTION

▪ Make sure the installation of the duct does NOT exceed

the setting range of the external static pressure for the
unit. Refer to the technical datasheet of your model for
the setting range.

▪ Make  sure  to  install  the  canvas  duct  so  vibrations  are

NOT  transmitted  to  the  duct  or  ceiling.  Use  a  sound-
absorbing material (insulation material) for the lining of
the  duct  and  apply  vibration  insulation  rubber  to  the
hanging bolts.

▪ When  welding,  make  sure  NOT  to  spatter  onto  the

drain pan or the air filter.

▪ If the metal duct passes through a metal lath, wire lath

or  metal  plate  of  the  wooden  structure,  separate  the
duct and wall electrically.

▪ Install the outlet grille in a position where the airflow will

not come into direct contact with people.

▪ Do NOT use booster fans in the duct. Use the function

to  adjust  the  fan  rate  setting  automatically  (see

"16 Configuration"

 [

4

 17]).

The ducting is to be field supplied.

a

c

e

f

d

d

b

c

4

a

Air inlet

b

Air outlet

c

Screws for duct flanges

d

Air outlet flange

e

Air inlet flange

f

Transportation case cover

1

Remove the air outlet flange from the transportation case cover.

2

Move and attach the air outlet flange to the air outlet side.

3

Fix  the  air  outlet  flange  with  the  34  screws  for  duct  flanges
(accessory).

4

Fix  the  air  inlet  flange  using  the  remaining  15  screws  for  duct
flanges (accessory).

5

Connect  the  canvas  duct  to  the  inside  of  the  flange  on  both
sides.

6

Connect the duct to the canvas duct on both sides.

7

Wind aluminium tape around the flanges and duct connections.
Make sure there are no air leaks at any other connection.

8

Insulate  the  ducts  to  prevent  condensation  from  forming.  Use
glass wool or polyethylene foam 25 mm thick.

a

b

c

b

a

f

f

e

e

d

d

a

Screws for duct flanges (accessory)

b

Flange (located on the unit)

c

Main unit

d

Insulation (field supply)

e

Canvas duct (field supply)

f

Aluminium tape (field supply)

Filter. 

Be sure to attach an air filter inside the air passage on the

air inlet side. Use an air filter with dust collecting efficiency ≥50%
(gravimetric method).

12.2.3

Guidelines when installing the drain
piping

Make  sure  condensation  water  can  be  evacuated  properly.  This
involves:

▪ General guidelines

▪ Connecting the drain piping to the indoor unit

▪ Checking for water leaks

General guidelines

Pipe length.

 Keep drain piping as short as possible.

Pipe size.

 Keep the pipe size equal to or greater than that of the

connecting  pipe  (vinyl  pipe  of  25  mm  nominal  diameter  and
32 mm outer diameter).

Slope.

 Make sure the drain piping slopes down (at least 1/100) to

prevent air from being trapped in the piping. Use hanging bars as
shown.

1~1.5 m

a

a

Hanging bar
Allowed
Not allowed

Condensation.

  Take  measures  against  condensation.  Insulate

the complete drain piping in the building.

Combining  drain  pipes.

  It  is  possible  to  combine  drain  pipes.

Use  drain  pipes  and  T-joints  with  the  correct  gauge  for  the
operating capacity of the units.

≥100

a

a

a

T-joint

To connect the drain piping to the indoor unit

NOTICE

Incorrect  connection  of  the  drain  hose  might  cause  leaks,
and damage the installation space and surroundings.

a b

a

Drain pipe connection

b

Refrigerant pipes

Drain piping connection

1

Pull out the drain plug.

2

Install the adapter for the drain hose (field supply).

Summary of Contents for VRV system FXMQ200AXVMB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXMQ200AXVMB FXMQ250AXVMB...

Page 2: ...laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokladu...

Page 3: ...accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60...

Page 4: ...Configuration 17 16 1 Field setting 17 17 Technical data 20 17 1 Wiring diagram 20 17 1 1 Unified wiring diagram legend 20 1 About the documentation 1 1 About this document INFORMATION Make sure that...

Page 5: ...iring All components procured on site and all electrical construction MUST comply with the applicable legislation WARNING If the power supply has a missing or wrong N phase equipment might break down...

Page 6: ...the symbol this chemical symbol means that the battery contains a heavy metal above a certain concentration Possible chemical symbols are Pb lead 0 004 Waste batteries MUST be treated at a specialise...

Page 7: ...unit may fall and result in injury CAUTION Before accessing terminal devices make sure to interrupt all power supply DANGER RISK OF ELECTROCUTION To clean the air conditioner or air filter be sure to...

Page 8: ...for future system extensions is available in technical engineering data and should be consulted Contact your installer to receive more information and professional advice 4 1 System layout INFORMATIO...

Page 9: ...he indoor unit fan will stop operation and the following icon will appear on the home screen 6 3 To operate the system INFORMATION For setting of the operation mode or other settings see the reference...

Page 10: ...unit is indicated both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 Contact your installer f...

Page 11: ...tion site 12 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 70 dBA INFORMATION Equipment meets the requirement for commercial and light industr...

Page 12: ...using a nut and washer from the upper and lower sides of the hanger bracket e 1526 e 1028 a b b d c a Nut field supply b Washer accessories c Hanger bracket d Double nut field supply e Suspension bolt...

Page 13: ...s 7 Wind aluminium tape around the flanges and duct connections Make sure there are no air leaks at any other connection 8 Insulate the ducts to prevent condensation from forming Use glass wool or pol...

Page 14: ...he electrical wiring Remove the service cover Disconnect the power supply Disconnect the user interface Reattach the service cover When installation of the system is already completed 1 Start cooling...

Page 15: ...er accessory d Attached piping e Sealing on the attached piping f Indoor unit NOTICE Join the attached piping accessory and the field refrigerant piping field supply by brazing before fixing the attac...

Page 16: ...F2 match with the symbols on the outdoor unit Bundle the transmission cable with the user interface cable and fix them with a tie wrap on the wiring fixture 4 Power supply cable Route the cable throug...

Page 17: ...supply panel The voltage MUST correspond to the voltage on the nameplate of the unit Earth wiring Be sure that the earth wires have been connected properly and that the earth terminals are tightened...

Page 18: ...11 21 7 01 Completion of automatic airflow adjustment 02 Start of automatic airflow adjustment 03 To set external static pressure by the user interface Check the indoor unit setting the value number m...

Page 19: ...fference between cooling setpoint and heating setpoint in automatic mode availability depends on the system type Differential is cooling setpoint minus heating setpoint If you want to set Then 1 Examp...

Page 20: ...connector D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Connector frame ground H Harness H P LED V L Pilot lamp light emitting...

Page 21: ...n and operation manual 21 FXMQ A VRV system air conditioner 3P701545 1 2022 07 Symbol Meaning X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C Fer...

Page 22: ......

Page 23: ......

Page 24: ...3P701545 1 2022 07 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: