16 Configuration

Installation and operation manual

18

FXMQ-A

VRV system air conditioner

3P701545-1 – 2022.07

▪ T1/T2 input setting

Setting: External static pressure

INFORMATION

▪ The fan speed of the indoor unit is preset to ensure the

standard external static pressure.

▪ To set a higher or lower external static pressure, reset

the initial setting with the user interface.

Settings for external static pressure can be achieved in 2 ways:

▪ Using the airflow automatic adjustment function

▪ Using the user interface

To set external static pressure by airflow automatic adjustment
function

NOTICE

▪ Do  NOT  adjust  the  dampers  during  the  fan  only

operation for airflow automatic adjustment.

▪ For the external static pressure higher than 100 Pa, do

NOT use airflow automatic adjustment function.

▪ If the ventilation paths have been changed, perform the

airflow automatic adjustment again.

▪ Test  run  MUST  be  done  with  a  dry  coil,  run  the  unit  for  2  hours

with fan only to dry the coil.

▪ Check  if  the  power  supply  wiring,  duct,  air  filter  are  properly

attached. If the closing damper is installed in the unit, make sure it
is open.

▪ If there is more than one air inlet and outlet, adjust the dampers so

that the airflow rate of each air inlet and outlet is conform with the
designed airflow rate.

1

Operate  the  unit  in 

fan  only  mode

  prior  to  using  the  airflow

automatic adjustment function.

2

Stop 

the air conditioning unit.

3

Set the value

 number “—“ to 03 for 

M

 11(21) and 

SW

 7.

4

Start 

the air conditioning unit.

Result: 

The  operation  lamp  lights  up  and  the  unit  starts  the  fan

operation for airflow automatic adjustment.

5

After  airflow  automatic  adjustment  is  finished  (air  conditioning
unit will stop) check if the value number “—“ is set to 02. If there
is no change, perform the setting again.

Setting content:

Then

(1)

M

SW

Airflow adjustment is OFF

11(21)

7

01

Completion of automatic airflow adjustment

02

Start of automatic airflow adjustment

03

To set external static pressure by the user interface

Check the indoor unit setting: the value number “—“ must be set to
01 for 

M

 11(21) and 

SW

 7.

1

Change  the  value  number  “—“  according  to  the  external  static
pressure of the duct to be connected as in table below.

M

SW

External static pressure (Pa)

(1)

13(23)

6

01

50

02

75

03

100

04

115

05

130

06

150

07

160

08

175

09

190

10

200

11

210

12

220

13

230

14

240

15

250

Setting: Air volume when thermostat control is OFF

This  setting  must  correspond  with  the  needs  of  the  user.  It
determines  the  fan  speed  of  the  indoor  unit  during  thermostat  OFF
condition.

1

If you have set the fan to operate, set the air volume speed:

If you want…

Then

(1)

M

SW

During thermostat
OFF at cooling
operation

LL

(2)

12 (22)

6

01

Setup volume

(2)

02

OFF

(a)

03

Monitoring 1

(2)

04

Monitoring 2

(2)

05

During thermostat
OFF at heating
operation

LL

(2)

12 (22)

3

01

Setup volume

(2)

02

OFF

(a)

03

Monitoring 1

(2)

04

Monitoring 2

(2)

05

(a)

Only use in combination with optional remote sensor or when
setting 

M

 10 (20), 

SW 

2, —

 

03 is used.

Setting: Time to clean air filter

This setting must correspond with the air contamination in the room.
It determines the interval at which 

"Time to clean filter"

 notification

is displayed on the user interface.

If you want an interval of…

(air contamination)

Then

(1)

M

SW

±2500 h (light)

10 (20)

0

01

±1250 h (heavy)

02

Notification ON

3

01

Notification OFF

02

(1)

Field settings are defined as follows:

M

: Mode number – 

First number

: for group of units – 

Number between brackets

: for individual unit

SW

: Setting number

• —: Value number

: Default

(2)

Fan speed:

LL

: Low fan speed (set during thermostat OFF)

L

: Low fan speed (set by the user interface)

Setup volume

: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user

interface.

Monitoring 1, 2

: The fan is OFF, but runs for a short time every 6 minutes to detect the room temperature by 

LL

 (Monitoring 1) or by 

L

(Monitoring 2).

Summary of Contents for VRV system FXMQ200AXVMB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXMQ200AXVMB FXMQ250AXVMB...

Page 2: ...laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokladu...

Page 3: ...accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60...

Page 4: ...Configuration 17 16 1 Field setting 17 17 Technical data 20 17 1 Wiring diagram 20 17 1 1 Unified wiring diagram legend 20 1 About the documentation 1 1 About this document INFORMATION Make sure that...

Page 5: ...iring All components procured on site and all electrical construction MUST comply with the applicable legislation WARNING If the power supply has a missing or wrong N phase equipment might break down...

Page 6: ...the symbol this chemical symbol means that the battery contains a heavy metal above a certain concentration Possible chemical symbols are Pb lead 0 004 Waste batteries MUST be treated at a specialise...

Page 7: ...unit may fall and result in injury CAUTION Before accessing terminal devices make sure to interrupt all power supply DANGER RISK OF ELECTROCUTION To clean the air conditioner or air filter be sure to...

Page 8: ...for future system extensions is available in technical engineering data and should be consulted Contact your installer to receive more information and professional advice 4 1 System layout INFORMATIO...

Page 9: ...he indoor unit fan will stop operation and the following icon will appear on the home screen 6 3 To operate the system INFORMATION For setting of the operation mode or other settings see the reference...

Page 10: ...unit is indicated both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 Contact your installer f...

Page 11: ...tion site 12 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 70 dBA INFORMATION Equipment meets the requirement for commercial and light industr...

Page 12: ...using a nut and washer from the upper and lower sides of the hanger bracket e 1526 e 1028 a b b d c a Nut field supply b Washer accessories c Hanger bracket d Double nut field supply e Suspension bolt...

Page 13: ...s 7 Wind aluminium tape around the flanges and duct connections Make sure there are no air leaks at any other connection 8 Insulate the ducts to prevent condensation from forming Use glass wool or pol...

Page 14: ...he electrical wiring Remove the service cover Disconnect the power supply Disconnect the user interface Reattach the service cover When installation of the system is already completed 1 Start cooling...

Page 15: ...er accessory d Attached piping e Sealing on the attached piping f Indoor unit NOTICE Join the attached piping accessory and the field refrigerant piping field supply by brazing before fixing the attac...

Page 16: ...F2 match with the symbols on the outdoor unit Bundle the transmission cable with the user interface cable and fix them with a tie wrap on the wiring fixture 4 Power supply cable Route the cable throug...

Page 17: ...supply panel The voltage MUST correspond to the voltage on the nameplate of the unit Earth wiring Be sure that the earth wires have been connected properly and that the earth terminals are tightened...

Page 18: ...11 21 7 01 Completion of automatic airflow adjustment 02 Start of automatic airflow adjustment 03 To set external static pressure by the user interface Check the indoor unit setting the value number m...

Page 19: ...fference between cooling setpoint and heating setpoint in automatic mode availability depends on the system type Differential is cooling setpoint minus heating setpoint If you want to set Then 1 Examp...

Page 20: ...connector D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Connector frame ground H Harness H P LED V L Pilot lamp light emitting...

Page 21: ...n and operation manual 21 FXMQ A VRV system air conditioner 3P701545 1 2022 07 Symbol Meaning X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C Fer...

Page 22: ......

Page 23: ......

Page 24: ...3P701545 1 2022 07 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: