About the units and options
Installer and user reference guide
59
R R8T7V1B
VRV IV heat pump for indoor installation
4P499898-1B – 2021.12
Filter for debris (delivered as accessory)
▪
When.
Installation is optional. It is recommended in places where a lot of debris
or dirt (example: leafs) can go into the suction ducting.
▪
Where.
Install the filter in one of the following places:
-
Suction opening of the heat exchanger unit
-
Suction ducting (easier for maintenance)
▪
How.
See the installation instructions attached to the filter.
▪
Pressure drop over the filter:
-
5 HP: 30 Pa at 60 m³/min
-
8 HP: 75 Pa at 100 m³/min