17
|
Electrical installation
Installer and user reference guide
93
R R8T7V1B
VRV IV heat pump for indoor installation
4P499898-1B – 2021.12
Model
Minimum circuit
ampacity
Recommended fuses
RKXYQ5
13.5 A
16 A
RKXYQ8
17.4 A
20 A
▪
Phase and frequency: 3N~ 50 Hz
▪
Voltage: 380-415 V
Transmission wiring
Transmission line section:
Transmission wiring
Sh shielded cable (2 wires)
Vinyl cords
0.75~1.25 mm²
(using shielded cable for the
transmission wiring is mandatory for
5 HP, and optional for 8 HP)
Maximum wiring length
(= distance between compressor unit
and furthest indoor unit)
300 m
Total wiring length
(= distance between compressor unit
and all indoor units, and between
compressor unit and heat exchanger
unit)
600 m
If the total transmission wiring exceeds these limits, it may result in communication
error.
17.2 To connect the electrical wiring on the compressor unit
NOTICE
▪
Follow the wiring diagram (delivered with the unit, located on the switch box
cover).
▪
Make sure the electrical wiring does NOT obstruct proper reattachment of the
service cover.
1
Remove the service covers of the compressor unit and the switch box. See
"15.2.2 To open the compressor unit"
2
Connect the transmission wiring as follows: