Piping installation
Installer and user reference guide
77
R R8T7V1B
VRV IV heat pump for indoor installation
4P499898-1B – 2021.12
3
Put a wet cloth in front of the EPS to protect the drain pan.
4
Braze the liquid and gas piping.
NOTICE
Only for 8 HP.
Piping adapter
(Ø19.1→22.2 mm) (delivered as accessory in the compressor unit).
Use the piping adapter to connect the field piping (Ø22.2 mm) to the gas piping
connection of the heat exchanger unit (Ø19.1 mm).
5
Remove the wet cloth.
6
Put back the 2 insulation pieces, peel off the insulation tapes and adhere them
to the insulation pieces.
7
Reattach the cover.
1
2
4
3
5
6
7