18
|
Configuration
Installer and user reference guide
106
R R8T7V1B
VRV IV heat pump for indoor installation
4P499898-1B – 2021.12
Value / Description
H6P
Shows the status of low noise operation.
OFF
Unit is currently not operating under low noise restrictions.
ON
Unit is currently operating under low noise restrictions.
Low noise operation reduces the sound generated by the unit compared
to nominal operating conditions.
Low noise operation can be set in mode 2. There are two methods to
activate low noise operation of the compressor unit and heat exchanger
unit.
▪
The first method is to enable an automatic low noise operation during
night time by field setting. The unit will operate at the selected low
noise level during the selected time frames.
▪
The second method is to enable low noise operation based on an
external input. For this operation an optional accessory is required.
H7P
Shows the status of power consumption limitation operation.
OFF
Unit is currently not operating under power consumption
limitations.
ON
Unit is currently operating under power consumption
limitation.
Power consumption limitation reduces the power consumption of the
unit compared to nominal operating conditions.
Power consumption limitation can be set in mode 2. There are two
methods to activate power consumption limitation of the compressor
unit.
▪
The first method is to enable a forced power consumption limitation
by field setting. The unit will always operate at the selected power
consumption limitation.
▪
The second method is to enable power consumption limitation based
on an external input. For this operation an optional accessory is
required.
7‑LEDs display – Mode 1 (H1P flashing)
(in case of 5 HP)
You can read out the following information: