11

If stranded wires are used, do not solder the front end of the

wires.

Connect proper wires securely and fix the wires so that exter-

nal force will not be imposed on the terminals.

Use an appropriate screwdriver to tighten the terminal

screws. The screw heads may be damaged if the screwdriver

is too small and the terminal screws will not be tightened

properly.

Do not tighten the terminal screws excessively, or otherwise

the screw heads may be damaged.

Refer to the table below for the required tightening torque

values of the terminal screws.

Tightening torque (N·m)

Terminal block for remote controller 
and transmission wires

0.80 - 0.96

Terminal block for power supply

1.18 - 1.44

Install  an earth leakage breaker.

The installation of an earth leakage breaker is imperative for the 

prevention of electric shocks and fire accidents.

No. 1 system 

When using  1 remote  controller for 1 indoor uni t 

No. 2 system 
For group  controller use with  2 remote  controllers

No. 3 system 
When inc luding  BS unit

1. If no earth leakage breaker is required, install a breaker or

load switch with a fuse for the wiring. If an earth leakage
breaker is required, make sure that the earth leakage
breaker is designed to protect the air conditioner from
ground faults, overloads, and short circuiting.

2. The remote controller wiring (P1 and P2) and transmission

wiring (F1 and F2) have no polarity.

• Set one of the remote controllers to main and the other to sub

in the case of remote control with two remote controllers.

Switching Main/Sub

(1) Insert a   screwdriver into the clearance between the

grooves of the lower casing and the upper casing to remove
the upper casing. (2 grooves) (The remote controller PCB is
attached to the upper casing.)

Note)

 

There is no need to set the indoor unit 
address when using group control. 
(It is automatically set when the power 
is turned on.)

Lower part of 
remote controller

Upper part of 
remote controller

Insert the screwdriver here and gently work 
off the upper part of remote controller.

(2) Set the main/sub switch on one of the remote controller

PCBs to sub. (Keep the switch of the other remote controller
PCB set to main.)

Only one remote 

controller needs to be 

changed if factory 

settings have 

remained untouched.

M

S

S

S

M

(Factory setting)

Remote controller 
PC board

10-

2

  

WIRING EXAMPLE

!

WARNING

PRECAUTIONS

P1 P2 F1 F2 T1 T2

P1 P2

P1 P2 F1 F2 T1 T2

P1 P2

L N

P1 P2 F1 F2 T1 T2

P1 P2

F1 F2 F1F2

OUT/D

IN/D

L

LLL NN

NN

Indoor

unit A

Indoor

 unit B

Indoor

 unit C

Power

supply

230V

50 Hz

Most downstream

 indoor unit

Control

 box

L N

L N

P1 P2 F1 F2 T1 T2

P1 P2

P1 P2 F1 F2 T1T2

P1 P2

P1 P2

P1 P2 F1 F2 T1 T2

F1 F2 F1F2

IN/D

OUT/D

Outdoor unit

Power

supply

230V

50 Hz

Indoor

unit A

Indoor

 unit B

Most downstream

 indoor unit

Control

 box

(Option)

For use with 2 remote 

controllers

L N

N

L

L N

L N

In case of 
group control

Remote controller

Remote controller

P1 P2 F1 F2 T1 T2

P1 P2

F1 F2 F1F2

OUT/D

IN/D

F1 F2 F1 F2

OUT/D

IN/D

Control

 box

Control

 box

Outdoor

 unit

BS

unit

Power

supply

230V

50 Hz

Indoor

unit A

L

LLL NN

NN

L N

10-

3

 CONTROL BY 2 REMOTE CONTROLLERS

(C

ontrolling 1 unit by 2 remote controllers)

Remote controller 

(Option)

Remote controller 

(Option)

Remote controller 

(Option)

Remote controller(Option)

Remote controller 

(Option)

Summary of Contents for VRV FXMQ100ARV16

Page 1: ... shocks or fire Install the air conditioner on a foundation strong enough to withstand the weight of the unit A foundation of insufficient strength may result in the equipment falling down and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing ac...

Page 2: ...ut exerting any pressure on other parts especially the refrigerant piping drain piping flanges and other resin parts Be sure to check the type of R410A refrigerant to be used before installing the unit Using an incorrect refrigerant will prevent normal operation of the unit The accessories needed for installation must be retained in your custody until the installation work is completed Do not disc...

Page 3: ...eliver instruction manual if any for the field supplies to the customer Hold the hanging brackets in the case of moving the indoor and outdoor units at the time of and after opening the packages Do not impose undue force on other parts such as the refrigerant piping drain piping or flanges in particular Add heat insulation material to the indoor unit if the tem perature above the ceiling is likely...

Page 4: ...icing purposes of the el compo box and drain pump prepare one of the following service spaces 1 2 Inspection hatch 1 2 450 450 for the el compo box and a minimum space of 300 mm for the lower part of the product Refer to Fig 2 2 Inspection hatch 1 450 450 for the el compo box and inspection hatch 2 for the lower part of the prod uct see axial direction view A 1 Refer to Fig 2 3 3 Inspection hatch ...

Page 5: ...the washer for the hanging bracket can be prevented if the washing fixing plate 8 is used During the installation work perform the curing of the air outlet and protect the resin drain pan of the indoor unit from the intrusion of foreign substances such as welding spatters Otherwise water leakage may occur as a result of damage such as hole damage to the resin drain pan 2 Make adjustments so that t...

Page 6: ...e free of oil The drain pan and the resin part may be deteriorated if oil is attached If no torque wrenches are available refer to Table 3 as a standard When the flare nut is tightened with the spanner the tightening torque should increase suddenly Tighten the flare nut further for the corresponding angle shown in Table 3 Table 3 Torque wrench Spanner Piping union Flare nut Fig 4 Pipe size Tighten...

Page 7: ...r of 25 mm Make sure that the piping is short enough with a down ward slope of at least 1 100 and that there is no air bank formed No drain trap is required The drain piping will be clogged with water and water leak age may result if the water is accumulated in the drain piping Conduct drain up piping work if the gradient is insufficient Attach a support bracket at 1 to 1 5 m intervals for the pre...

Page 8: ...oling operation according to 11 FIELD SETTING and 12 TEST OPERATION Make sure that the water is not spilled onto the electric parts of the drain pump and others Ceiling slab 1 1 5 m 300 mm max 700 mm max Support bracket Drain up piping field supply Adjustable 467 mm max Metal clamp 1 accessory Drain hose 2 accessory Drain hose 2 accessory Horizontal or upward slope If there is an air bank noise ma...

Page 9: ...ng and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfunction A circuit breaker capable of shutting down power supply to the entire system must be installed Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instruction...

Page 10: ... connections are done fill in any gaps in the through holes with putty or insulation procured locally to prevent small animals and insects from entering the unit from outside If any do get in they could cause short circuits in the el compo box 5 Mount the provided wire fixing bracket 10 with the wire fixing screw 11 Fix each wire with the provided clamp 7 Precaution s for Power Supply Wiring Conne...

Page 11: ...rt a screwdriver into the clearance between the grooves of the lower casing and the upper casing to remove the upper casing 2 grooves The remote controller PCB is attached to the upper casing Note There is no need to set the indoor unit address when using group control It is automatically set when the power is turned on Lower part of remote controller Upper part of remote controller Insert the scr...

Page 12: ...mpossible by remote controllers Input OFF ON turns ON unit Input OFF enables control by remote con troller Input ON OFF turns OFF unit F2 T1 T2 FORCED OFF Input A SETTING MODE NO SECOND CODE NO FIELD SET MODE FIRST CODE NO 2 Filter Sign Settings The remote controller is provided with an LCD that tells the time of air filter cleaning If the air conditioner is used in places with excessive dust chan...

Page 13: ...ndoor unit indoor control PCB transmission error C6 Lit Improper combination of fan driver PCB of indoor unit or setting failure in control PCB type Test operation of outdoor unit has not U3 Lit been finished Contents Remote Controller Display is Lit up U4 is lit up UH is lit up No display The Power on the outdoor unit is off The outdoor unit has not been wired for power supply Incorrect wiring fo...

Page 14: ...nformation regarding safety Be sure to observe all precautions without fail WARNING Failure to follow these instructions properly may result in personal injury or loss of life CAUTION Failure to observe these instructions properly may result in property damage or personal injury which may be seri ous depending on the circumstances After reading keep this manual in a convenient place so that you ca...

Page 15: ...n order to prevent electric shock or fire 10 Air filter inside filter chamber Sold separately 11 Suction filter chamber Sold separately 12 Suction duct Field supply 13 Machine nameplate The nameplate is imprinted with the machine name and specifications 14 Suction grille Field supply 15 Air Filter Only a qualified person is allowed to perform mainte nance except daily maintenance Before touching a...

Page 16: ...e controller please clean the filter When the operating time exceeds the desig nated time this mark will be displayed If using the air conditioner under very dusty environment increase the frequency of air filter cleaning When you want to change the setting time until the mark is displayed consult with your dealer The default factory setting is 2500 hours There are the following time display patte...

Reviews: