background image

2

5

(2) Mount the canvas ducts to the air outlet and inlet so that

the vibration of the air conditioner will not be transmitted to the

duct or ceiling. Apply a sound absorbing material (insulation

material) to the inner wall of the duct and vibration insulation

rubber to the hanging bolts (refer to 8. DUCT WORK).

(3) Open installation holes (if the ceiling already exists).

Open the installation holes on the ceiling. Lay the refrigerant pip-

ing, drain piping, power line, transmission wiring, and remote

 

con-

roller wiring for the piping and wiring connection port of the

 

unit.

In the case of the installation of a wireless remote

 

con-

troller, refer to the installation manual provided with

 the

wir

eless remote controller.

Refer to 

6. REFRIGERANT PIPING WORK

7. DRAIN

PIPING WORK

, and 

10. WIRING EXAMPLE AND HOW

TO SET THE REMOTE CONTROLLER

.

The ceiling framework may need reinforcement in order

to keep the ceiling horizontal and prevent the vibration of

the ceiling after the installation holes are opened. For

details, consult your construction or interior contractor.

(4) Install the hanging bolts. Make sure that the hanging bolts

are M10 in size.

Use hole

 i

n anchors if the hanging bolts already exist;

otherwise use embedded inserts and embedded founda-

tion bolts so that they will withstand the weight of the unit.

Adjust the distance to the ceiling surface in advance.

It may be easier to install accessories (sold separately)

before installing the indoor unit. Refer to the installation

manuals provided to the accessories as well.

Be sure to use the accessories and specified parts for

installation work.

(1) Temporally install the indoor unit.

Connect the hanging brackets to the hanging bolts. Be sure to

use and tighten the nut and washer (procured in the field) for each

hanging bracket from both upper and lower sides of the hanging

bracket. 

(Refer to Fig. 3)

 At that time, the fall of the washer for

the hanging bracket can be prevented if the washing fixing plate

(8) is used.

During the installation work, perform the curing of the air

outlet and protect the resin drain pan of the indoor unit

from the intrusion of foreign substances, such as welding

spatters.

Otherwise, water leakage may occur as a result of damage,

such as hole damage, to the resin drain pan.

(2) Make adjustments so that the unit will be in the right position.

(3) Check the level of the unit.

(4) Remove the washer fixing plates for the falling prevention of

the washers for the hanging brackets, tighten the nuts on the upper

side, and securely fix the unit.

B

C

D

700 738 1000

1000  1038  1300

Model

40 • 50 type
63 • 80 • 100 type 

(length: mm)

• Determine the H3

dimension by maintaining a
downward slope of at least
1/100 as specified in
“7. DRAIN PIPING WORK”.

Indoor unit

Note)   All the above parts are field supplied. 

Installation example

Ceiling slab

Anchor

Long nut or turn-buckle

Hanging bolt

Hanging bracket

Level

Bottom of product

Vinyl tube

Use the level and check that the unit is installed

horizontally.(4-directions)

In the case of using a vinyl tube in place of the level, put the

both edges of the vinyl tube in close contact with the bottom

of the product to make levelness adjustment.

If the unit is installed at a slant with the drain pipe side set

high, in particular, the float switch will not operate normally

and water leakage may result.

As for the refrigerant piping of the outdoor unit, refer to the 

installation manual provided to the outdoor unit

.

Perform heat insulation work on both gas piping and liquid 

piping, or otherwise water leakage may result.

Use the insulation material that withstands a temperature 

of 120°C.

Adjust the height of the unit.(3)

Make sure the unit is 

5. INDO

(2) 

OR UNIT INSTALLATI

 

ON

!

CAUTION

!

CAUTION

6. REFRIGERANT PIPING WORK

Washer 

(Procured in the field)

Part to be procured in the field

Washer fixing plate (

8

(accessory)

Insert

Tighten from above and below 
(Double nut)

[Fixing hanging brackets]

[Fixing method of washers]

Fig. 3

Nut on the upper side

Summary of Contents for VRV FXMQ100ARV16

Page 1: ... shocks or fire Install the air conditioner on a foundation strong enough to withstand the weight of the unit A foundation of insufficient strength may result in the equipment falling down and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing ac...

Page 2: ...ut exerting any pressure on other parts especially the refrigerant piping drain piping flanges and other resin parts Be sure to check the type of R410A refrigerant to be used before installing the unit Using an incorrect refrigerant will prevent normal operation of the unit The accessories needed for installation must be retained in your custody until the installation work is completed Do not disc...

Page 3: ...eliver instruction manual if any for the field supplies to the customer Hold the hanging brackets in the case of moving the indoor and outdoor units at the time of and after opening the packages Do not impose undue force on other parts such as the refrigerant piping drain piping or flanges in particular Add heat insulation material to the indoor unit if the tem perature above the ceiling is likely...

Page 4: ...icing purposes of the el compo box and drain pump prepare one of the following service spaces 1 2 Inspection hatch 1 2 450 450 for the el compo box and a minimum space of 300 mm for the lower part of the product Refer to Fig 2 2 Inspection hatch 1 450 450 for the el compo box and inspection hatch 2 for the lower part of the prod uct see axial direction view A 1 Refer to Fig 2 3 3 Inspection hatch ...

Page 5: ...the washer for the hanging bracket can be prevented if the washing fixing plate 8 is used During the installation work perform the curing of the air outlet and protect the resin drain pan of the indoor unit from the intrusion of foreign substances such as welding spatters Otherwise water leakage may occur as a result of damage such as hole damage to the resin drain pan 2 Make adjustments so that t...

Page 6: ...e free of oil The drain pan and the resin part may be deteriorated if oil is attached If no torque wrenches are available refer to Table 3 as a standard When the flare nut is tightened with the spanner the tightening torque should increase suddenly Tighten the flare nut further for the corresponding angle shown in Table 3 Table 3 Torque wrench Spanner Piping union Flare nut Fig 4 Pipe size Tighten...

Page 7: ...r of 25 mm Make sure that the piping is short enough with a down ward slope of at least 1 100 and that there is no air bank formed No drain trap is required The drain piping will be clogged with water and water leak age may result if the water is accumulated in the drain piping Conduct drain up piping work if the gradient is insufficient Attach a support bracket at 1 to 1 5 m intervals for the pre...

Page 8: ...oling operation according to 11 FIELD SETTING and 12 TEST OPERATION Make sure that the water is not spilled onto the electric parts of the drain pump and others Ceiling slab 1 1 5 m 300 mm max 700 mm max Support bracket Drain up piping field supply Adjustable 467 mm max Metal clamp 1 accessory Drain hose 2 accessory Drain hose 2 accessory Horizontal or upward slope If there is an air bank noise ma...

Page 9: ...ng and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfunction A circuit breaker capable of shutting down power supply to the entire system must be installed Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instruction...

Page 10: ... connections are done fill in any gaps in the through holes with putty or insulation procured locally to prevent small animals and insects from entering the unit from outside If any do get in they could cause short circuits in the el compo box 5 Mount the provided wire fixing bracket 10 with the wire fixing screw 11 Fix each wire with the provided clamp 7 Precaution s for Power Supply Wiring Conne...

Page 11: ...rt a screwdriver into the clearance between the grooves of the lower casing and the upper casing to remove the upper casing 2 grooves The remote controller PCB is attached to the upper casing Note There is no need to set the indoor unit address when using group control It is automatically set when the power is turned on Lower part of remote controller Upper part of remote controller Insert the scr...

Page 12: ...mpossible by remote controllers Input OFF ON turns ON unit Input OFF enables control by remote con troller Input ON OFF turns OFF unit F2 T1 T2 FORCED OFF Input A SETTING MODE NO SECOND CODE NO FIELD SET MODE FIRST CODE NO 2 Filter Sign Settings The remote controller is provided with an LCD that tells the time of air filter cleaning If the air conditioner is used in places with excessive dust chan...

Page 13: ...ndoor unit indoor control PCB transmission error C6 Lit Improper combination of fan driver PCB of indoor unit or setting failure in control PCB type Test operation of outdoor unit has not U3 Lit been finished Contents Remote Controller Display is Lit up U4 is lit up UH is lit up No display The Power on the outdoor unit is off The outdoor unit has not been wired for power supply Incorrect wiring fo...

Page 14: ...nformation regarding safety Be sure to observe all precautions without fail WARNING Failure to follow these instructions properly may result in personal injury or loss of life CAUTION Failure to observe these instructions properly may result in property damage or personal injury which may be seri ous depending on the circumstances After reading keep this manual in a convenient place so that you ca...

Page 15: ...n order to prevent electric shock or fire 10 Air filter inside filter chamber Sold separately 11 Suction filter chamber Sold separately 12 Suction duct Field supply 13 Machine nameplate The nameplate is imprinted with the machine name and specifications 14 Suction grille Field supply 15 Air Filter Only a qualified person is allowed to perform mainte nance except daily maintenance Before touching a...

Page 16: ...e controller please clean the filter When the operating time exceeds the desig nated time this mark will be displayed If using the air conditioner under very dusty environment increase the frequency of air filter cleaning When you want to change the setting time until the mark is displayed consult with your dealer The default factory setting is 2500 hours There are the following time display patte...

Reviews: