Si71-812
Troubleshooting
Troubleshooting
77
2.21
Main Unit PC Board Assembly
Error Detection
Method
Check microcomputer operation monitor.
Error Generating
Conditions
When main unit PC board assembly does not operate.
When communication circuit errors.
Possible Causes
Fuse (excess current)
Power transformer
Noise
Main unit PC board
Troubleshooting
Main unit PC board (A1P)
NO
NO
NO
YES
Does equipment
reset properly.
Is it flashing?
After checking
other possible
causes, replace
PC board assembly.
Is monitor indicator
Off?
YES
YES
Monitor indicator remains
On.
With remote controller
disconnected, check
microcomputer operation
monitor.
Turn off power, then
restart.
Noise may be causing erroneous
operation. If power reset does not
solve the problem, replace main unit
PC board.
There may be a malfunction in main
unit PC board fuse, main unit PC board
or power transformer.
Check fuse and transformer. If they are
normal, replace PC board.
Replace main unit PC board.
(HF013)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
HAP
(HL031)
(Microcomputor Operation Monitor)
Summary of Contents for VKM50GAV1
Page 9: ...Introduction Si71 812 viii...
Page 43: ...Operation Si71 812 34 Operation...
Page 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance...
Page 91: ...Troubleshooting Si71 812 82 Troubleshooting...
Page 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1...
Page 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1...
Page 103: ...Piping Diagram Si71 812 94 Appendix...
Page 105: ...Si71 812 ii Index...