Field Setting
Si71-812
86
Field Setting
5. When “Filter cleaning time setting” or “Night-purge operation setting” is changed, explain set
contents to the customer.
6. See below for details on the settings for cold areas.
In case of Independent operation
– : operate at the set fan strength
L : operate at the weak fan strength
S : Stop
Defrost operation
z
In heating operation, freezing of the outdoor unit's coil increases.
Heating capability decreases and the system goes into defrost operation.
z
The remote controller will read “
”until the hot air starts blowing.
z
It returns to the heating operation again after 6 to 8 minutes (10 at the longest)
z
During defrost operation, the fans of the unit continues driving (factory setting).
The purpose of this is to maintain the amount of ventilation and humidifying.
z
The change of air discharge grill's location should be examined when the cold draft from air discharge
grill is feared.
z
Though the fan can be stopped by the setting of remote controller
Do not stop the fan in the place where no ventilation by stopping the fan may cause the influence of
diffusion of air which it is dirty and moisture into another room, or the inflow from outside the room.
(outflow such as viruses from the sickroom, or smell leakage from the rest room, etc.)
7. See below for details on the external input terminal function.
∗
SECOND CODE NO. “04” does not function when in air conditioner linked mode.
Air conditioner Fan
HRV fan
01
02
04
06
Heating thermo off
Operation
–
–
L
L
Defrost
Stop
–
S
S
S
Oil return
Stop
–
S
S
S
Air conditioner fan
01
02
04
06
Heating thermo off
Operation
–
–
L
L
Defrost
Stop
–
–
Stop
Stop
Oil return
Stop
–
–
Stop
Stop
SECOND CODE
NO.
Input contact
Fan
operation
Operation
lamp
01
a
Operation
On
Fresh-up operation
02
a
Operation
On
Malfunction code “60” is displayed
06
a
Operation
On
Fan strength up
(Low to high, high to ultra-high)
Summary of Contents for VKM50GAV1
Page 9: ...Introduction Si71 812 viii...
Page 43: ...Operation Si71 812 34 Operation...
Page 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance...
Page 91: ...Troubleshooting Si71 812 82 Troubleshooting...
Page 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1...
Page 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1...
Page 103: ...Piping Diagram Si71 812 94 Appendix...
Page 105: ...Si71 812 ii Index...