Si71-812
Troubleshooting
Troubleshooting
81
2.24
Damper Motor
Error Detection
Method
Check damper motor and limit switch when damper motor does not operate.
Error Generating
Conditions
Possible Causes
Troubleshooting
Check resistance and voltage — DAMPER MOTOR
NO
YES
YES
Is
measured
value 0
Ω
when limit switch
turns on, and
infinity when
it turns
off?
Damper motor is
normal.
Place tester probes
at connectors of limit
switch, and check
continuity while
moving switch by
hand.
Limit switch is faulty.
Damper motor is faulty.
(HF017)
NO
Is
measured
value of EJ type
approx. 17 k
Ω
?
Place tester probes
on connectors of
damper motor and
check resistance.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(HL038)