Control Functions
Control Functions
47
Nighttime Free Cooling
Operating Condition
Nighttime Free Cooling
Operation <Flow Chart>
Air-conditioner Operation
<STOP>
Yes
Yes
Yes
Yes
Yes
Nighttime Free
Cooling Operation
<ON>
From air-conditioner stop time
Lapsed time
>
Setup time
Indoor temp.
>
Preset temp.+2˚C
Indoor temp.
>
Outdoor temp.
Yes
Yes
No
No
No
No
No
Yes
Yes
Yes
No
No
No
Fan operation & Temperature monitor
<5Min>
Fan operation
<ON (H)or(U-H)tap>
Lapsed time setup
<2hr, 4hr, 6hr, 8hr>
No
Air-conditioner Operation
<RUN>
Temp. monitor operation time
Lapsed time
>
60hr
Indoor temp.
≤
Outdoor temp.
Indoor temp.
≤
Preset temp.
Fan operation Lapsed time
Lapsed time
>
60Min
Standard mode
Fan operation
<STOP>
Standby mode
<60 Min>
( Fan ON time is included )