Tempo tra On T1
stesso comp. 0300s
Tempo tra On
diversi comp. 0030s
Time between ON T1
same comp. 0300s
Time between ON
differ.comp. 0030s
Tempo ent/On T1
mismo comp. 0300s
Tiemp ent/On
distin.comp. 0030s
This screen is used to set the compressor times.
The second line in the screen is used to set the min. time elapsing between two consecutive start-ups of a
compressor.
The fourth line in the screen is used to set the min. time elapsing between two consecutive start-ups of two
different compressors.
Ritardo allarme T2
bassa pressione
0003s
Low press alarm T2
Delay
0003s
Retardo alarma T2
Baja presión
0003s
This screen is used to set the delay in the activation of the low pressure alarm.
The third line in the screen is used to set the delay in the low pressure alarm.
Ritardo allarme T3
Flussostato
Partenza 030s
Regime 005s
Flowswitch alarm T3
delay
Start 030s
Running 005s
Retardo alarma T3
flujostato
Arranque 030s
Régim. 005s
This screen is used to set the delay in the activation of the air flow alarm.
The third line in the screen is used to set the delay in the air flow alarm upon unit start-up.
The fourth line in the screen is used to set the delay in the air flow alarm at operating speed.
Ritardo Off T4
ventil.princ. 240s
Ritardo partenza
compressore 060s
Main fan T4
delay off 240s
Delay compressor
running 060s
Retardo Off T4
ventil.princ. 240s
Retardo arranque
compresor 060s
This screen is used to set the delay in the switch-off of air treatment fans immediately after the unit switch-off,
and the delay in the start-up of the first compressor after the start-up of the main fan.
The second line in the screen is used to set the delay in the switch-off of the air treatment fans after the unit is
switched off.
The fourth line in the screen is used to set the delay in the start-up of the first compressor in the unit after the
main fan gets started.
Off forzato T5
compressore durante
inizio/fine
sbrinamento 000s
Compressor T5
forced OFF on
start / end
defrost 000s
Off forzado T5
Compresor durante
inicio/fin
desescarche 000s
This screen is used to set the compressor stop time upon cycle reversal during the defrost cycle. If this time is
set to 0, cycle reversal to defrost mode will take place with one compressor ON in the circuit; if the time setpoint
is greater than zero, the compressors in the circuit will be switched off before cycle reversal to defrost mode.
The fourth line in the screen is used to set the compressor stop time upon cycle reversal during the defrost
cycle.
Ritardo allarme T6
filtro 030s
Filter alarm T6
delay time 030s
Retardo alarma T6
filtro 030s
This screen is used to set the delay in the activation of the filters dirty alarm, which is calculated from the time
when the alarm signal is received by the controller.
The second line in the screen is used to set the delay in activation of the filters dirty alarm.