We reserve the right to make changes without prior notice
57
M7
Res.vasca cond.
M7
Cond.tray heater
M7
Res.tina cond.
This screen only appears if the heater in the condensate tray in the unit has been enabled: it shows whether
the heater is enabled.
M8
Gest.lavaggio
M8
Washing mng.
M8
Gestion lavado
This screen only appears if a damper module is installed in the unit: it shows whether washing management
is enabled.
Circuito 1 M9
Prevent L.P.
Circuito 2
Prevent L.P.
Circuit 1 M9
Prevent L.P.
Circuit 2
Prevent L.P.
Circuito 1 M9
Prevent L.P.
Circuito 2
Prevent L.P.
This screen only appears if the low pressure prevention function is enabled: it shows whether the function for
the prevention of the low pressure alarm in circuit 1 and circuit 2 is enabled.
7.5 Unit ON/OFF menu
Access to the Unit ON/OFF menu from the home screen is gained by pressing the Prg button, after which
select the “Unit ON/OFF” item and press Enter to confirm. Screen "N0" appears on the display.
Stato unità N0
OFF DA TASTIERA
ENTER per
- ACCENDERE -
Unit status N0
OFF BY KEYBOARD
Press ENTER for
- SWITCH ON -
Estad unid. N0
OFF POR TECLADO
ENTER par
- ENCEDER -
Press the "Enter" button to change the status of the unit: if the unit is off, it turns on, and vice versa.
If the time slots are enabled, the unit only gets started if the current time slot is one of those enabled for unit
switch-on.
If the unit is switched on by a control system, the unit actually gets started
after receiving an OK signal via a serial line.
The digital ON/OFF input must be closed for actual unit start-up.
The unit will not get started if one of the systems above does not output the necessary OK signal.
7.6 Manufacturer menu
Access to the Manufacturer menu is for the Factory and Service technicians only.
WARNING!
The parameters in the Manufacturer menu must not be changed for any reason
whatsoever without written authorisation from the unit Manufacturer. Any improper or
unauthorised parameter changes may cause serious damage to the unit and its
components and may instantly void the warranty with which the machine is supplied.
The parameters in the Manufacturer menu can only be changed if the unit is switched
OFF (OFF on the keyboard or digital input, where enabled).
Access to the Manufacturer menu from the home screen is gained by pressing the Prg button, after which
select the “Manufacturer” item and press Enter to confirm. Screen "Z0" appears on the display.