We reserve the right to make changes without prior notice
62
Limiti sonda CO2 Cf
Limite min 0000ppm
Limite max 2000ppm
CO2 air quality Cf
probe limits
Min limit 0000ppm
Max limit 2000ppm
Limit. Sonda CO2 Cf
Limite min 0000ppm
Limite max 2000ppm
This screen is used to set the operating range of the air quality probe.
The third line is used to set the min. CO
2
threshold measured by the probe, expressed in parts per million.
The fourth line is used to set the max. CO
2
threshold measured by the probe, expressed in parts per million.
Sonda Cg
cond./sbrin.1 S
Tipo 4-20 mA
En.cond/defr.1 Cg
probe Y
Type 4-20 mA
Sonda Cg
cond./deses.1 S
Tipo 4-20 mA
This screen is used to enable the pressure probe in refrigerant circuit 1, and to set its type.
The second line is used to enable the pressure probe.
The fourth line is used to set the probe type.
Sonda Ch
cond./sbrin.1
Min 00.0bar
Max 45.0bar
Cond/defr.1 probe Ch
limits
Min 00.0bar
Max 45.0bar
Limit. sonda Ch
cond./deses.1
Min 00.0bar
Max 45.0bar
This screen is used to set the operating range of the pressure probe in refrigerant circuit 1.
The third line is used to set the min. pressure threshold measured by the probe.
The fourth line is used to set the max. pressure threshold measured by the probe.
Sonda Ci
cond./sbrin.2 S
Tipo 4-20 mA
En.cond/defr.2 Ci
probe Y
Type 4-20 mA
Sonda Ci
cond./deses.2 S
Tipo 4-20 mA
This screen is used to enable the pressure probe in refrigerant circuit 2, where fitted, and to set its type.
The second line is used to enable the pressure probe.
The fourth line is used to set the probe type.
Sonda Cj
cond./sbrin.2
Min 00.0bar
Max 45.0bar
Cond/defr.2 probe Cj
limits
Min 00.0bar
Max 45.0bar
Limit. sonda Cj
cond./deses.2
Min 00.0bar
Max 45.0bar
This screen is used to set the operating range of the pressure probe in refrigerant circuit 2.
The third line is used to set the min. pressure threshold measured by the probe.
The fourth line is used to set the max. pressure threshold measured by the probe.
Abilita Ck
recupero calore N
----
Enable heat Ck
recovery N
----
Habilit Ck
recuper. calor N
----
This screen is used to enable heat recovery in units featuring this function.
The second line is used to enable heat recovery.
The third line is used to set the heat recovery type. The only type features in these units is cross-flow heat
recovery.
Serranda by-pass Cq
Tipo ANALOGICO
Posizione
SERRANDA AGGIUNTIVA
By-pass damper Cq
type ANALOG
Position
ADDITIONAL DAMPER
Obturad. by-pass Cq
Tipo ANALOGICO
Posiciòn
COMP. ADICIONAL
This screen is used to enable the bypass damper in units featuring this damper, and to select the control type
and whether to manage the damper as an additional damper or as a damper on the heat recovery unit.