PIM-00004
△
1
[Operation Manual]
22/61
DAIKIN INDUSTRIES, LTD.
Connecting the I/O signal cable
(1) Connect the main power supply cable to the controller through the controller's wiring hole. Use a cable
clamp suitable for the wiring hole, which should provide IP54 or higher protection rating. (Wiring hole
diameter: 22 mm)
(2) Check the specifications of individual signal lines (see p. 24), and connect the cable to the I/O signal
terminal block.
<When the unit controller small cover is removed>
<Enlarged view of I/O signal terminal block>
DANGER
Do not connect the I/O signal cable to the power supply terminal block.
When unsheathing the cable, be careful not to damage the conductors.
Be careful that the cable conductors do not protrude from the terminal block.
CAUTION
After checking the specifications of individual signal lines (see p. 24), connect the cable to the I/O signal
terminal block.
The cable inserted into the cable clamp should be a multi-core cable as those recommended below.
If two or more cables are inserted into the clamp, the cable clamp does not conform to the specified
protection rating because of a gap between the cables and the cable clamp.
Terminate the shielded cable securely, and connect it to the shielded cable connection terminal.
If noise cannot be eliminated by connecting the shielded cable to the ground terminal, the user's
equipment should be directly grounded. (Disconnect the ground cable of this unit.)
I/O signal terminal block
Wiring hole
Shielded cable ground terminal
Connect a
ground c able to
the s peci fied
posi tion.
Ground