background image

4

English

Choosing an Installation Site

2. 

Wireless remote controller

• Turn on all the fluorescent lamps in the room, if any, and find the site where remote controller signals are properly 

received by the indoor unit (within 13ft (4m)).

3. 

Outdoor unit

• For outdoor unit installation, see the installation manual supplied with the outdoor unit.

Preparations before Installation

 

Relation of the unit to the suspension bolt positions. 

• Install the inspection opening on the control box side where 

maintenance and inspection of the control box are easy.  Install 
the inspection opening also in the lower part of the unit.

 

Make sure the range of the unit’s external static pres-
sure is not exceeded.

(See the technical documentation for the range of the external 
static pressure setting.)

 

Open the installation hole. (Pre-set ceilings)

• Once the installation hole is opened in the ceiling where the unit 

is to be installed, pass refrigerant piping, drain piping, transmis

-

sion wiring, and remote controller wiring (unneeded if using a 
wireless remote controller) to the unit’s piping and wiring holes. 
See “

Refrigerant Piping Work

”, “

Drain Piping Work

”, and 

Wiring

”.

• After opening the ceiling hole, make sure ceiling is level if 

needed. It might be necessary to reinforce the ceiling frame to 
prevent shaking. Consult an architect or carpenter for details.

 

Install the suspension bolts.

(Use W3/8 to M10 suspension bolts.)

• Use a hole-in-anchor, sunken insert, sunken anchor for existing 

ceilings, and a sunken insert, sunken anchor or other part to be 
procured in the field to reinforce the ceiling to bearing the weight 
of the unit. (Refer to Fig.)

19-11/16 (500)

17-3/4 (450)

(Inspection opening 
size)

Air outlet

Suspension
bolt pitch

(unit : in (mm))

Air inlet

Control 
box

(Suspension bolt pitch)

Ceiling

24-7/16 (620)

24-7/16 (620)

A

Arrow view 

Inspection door

(Ceiling opening)

<SERVICE SPACE

>

A

B

FDXS09/12

CDXS15/18

A

27-9/16 (700)

B

29-1/8 (740)

37 (940)

35-7/16 (900)

CDXS24

44-7/8 (1140)

43-5/16 (1000)

Note: All the above parts are field supplied.

Suspension bolt

Long nut or turn-buckle

Anchor bolt

Indoor unit

Ceiling slab

 

Mount chamber cover and air filter (acces

-

sory).

For bottom intake, replace the chamber cover and the 
protection net in the procedure listed in Fig.

(1) Remove the protection net. (6 locations) 

Remove the chamber cover. (7 locations)

(2) Reattach the removed chamber cover in the 

orientation shown in Fig. (7 locations) 
Reattach the removed protection net in the 
orientation shown in Fig. (6 locations) 
Refer to Fig. for the direction of the protection net.

Air inlet

Air inlet

(1)

Chamber 
cover

(2)

Air outlet

Air outlet

Chamber 
cover

Protection net

Protection net

01_EN_3P297301-3C.indd   4

10/26/2012   11:27:23 AM

Summary of Contents for SUPER MULTI NX CDXS18LVJU

Page 1: ...ANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalación English Français Español MODELS FDXS09LVJU FDXS12LVJU CDXS15LVJU CDXS18LVJU CDXS24LVJU Manuel dinstallation 00_CV_3P297301 3C indd 1 10 26 2012 11 23 56 AM ...

Page 2: ...bags so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk of explosion resulting in serious injury or death Do not ground units to telephone wires or lightning rods because lightning strikes could cause a severe shock hazard resulting in severe injury or d...

Page 3: ...ault circuit interrupter breaker may result in electrically shocks or personal injury CAUTION Establish drain piping according to the instructions of this manual Inadequate piping may cause water damage Note for installing the outdoor unit For heat pump model only In regions of the country where the outside temperature is at or below the freezing point the drain may freeze If so it is recommended ...

Page 4: ...ough reinforce the ceiling before installing the unit Installation pitch is marked on the carton box for installation Refer to it to check for points requiring reinforcing Select the H dimension such that a downward slope of at least 1 100 is ensured as indicated in Drain Piping Work The installation pitch is listed on the packing material and should be checked when deciding whether to reinforce t...

Page 5: ... to reinforce the ceiling frame to prevent shaking Consult an architect or carpenter for details Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor sunken insert sunken anchor for existing ceilings and a sunken insert sunken anchor or other part to be procured in the field to reinforce the ceiling to bearing the weight of the unit Refer to Fig 19 11 16 500 17 3 4 45...

Page 6: ...cessory accessory For bottom intake type 4 Attach the hanger right insulation to the right hanger Stored in outlet vent See the below figure for the sticking base line Hanger right insulation accessory Slit Sticking base line Hanger bracket right Arrow view 5 Attach the air filter accessory in the manner shown in the diagram In case of bottom side In case of back side Filter Push Push Main unit At...

Page 7: ... with water In using a plastic tube instead of a level adjust the top surface of the unit to the surface of the water at both ends of the plastic tube and adjust the unit horizontally One thing to watch out for in particular is if it is installed so that the slope is not in the direction of the drain piping as this might cause leaking Tighten the upper nut Mounting the receiver Mount the receiver ...

Page 8: ...o prevent damage to the flare nuts and escaping gas Flare nut tightening torque Gas side Liquid side 3 8 inch 9 5mm 1 2 inch 12 7mm 5 8 inch 15 9mm 1 4 inch 6 4mm 24 1 29 4ft lbf 32 7 39 9N m 36 5 44 5ft lbf 49 5 60 3N m 45 6 55 6ft lbf 61 8 75 4N m 10 4 12 7ft lbf 14 2 17 2N m CAUTION Overtightening may damage the flare and cause leaks 3 After the work is finished make sure to check that there is...

Page 9: ...ness 13 32 inch 10mm Min 1 3 16 inch 30mm or more 1 9 16 inch 40mm or more 1 15 16 inch 50mm or more 1 3 16 inch 30mm or more Thickness 0 031 inch 0 8mm C1220T O Thickness 0 039 inch 1 0mm C1220T O Thickness 0 031 inch 0 8mm C1220T O Also when subject to high humidity heat insulation of the refrigerant piping the unit piping and branch piping must be further reinforced Reinforce the insulation whe...

Page 10: ... the indoor unit through the drain pipes and corrode the heat exchanger Do not twist or bend the drain hose so that excessive force is not applied to it This type of treatment may cause leaking After piping work is finished check drainage flows smoothly Gradually insert approximately 1L of water into the drain pan to check drainage in the manner described below Gradually pour approximately 1L of w...

Page 11: ...laths of the net or fence shape or metal plating into wooden buildings Wiring See the installation manual supplied with the outdoor unit HOW TO CONNECT WIRINGS Wire only after removing the control box cover as shown in the Fig Remote controller wiring Control box cover Wiring Diagram rear Conduit mounting plate accessory Conduit field supply Lock nut field supply Screw accessory Power supply wiring ...

Page 12: ...e control box cover Next pull the wires into the unit through the conduit and thread them through the insulation tube accessory then connect to the power wiring terminal block 4P Secure the wires covered by the insulation tube with the clamp accessory Be sure to put the part of the sheathed vinyl into the control box Terminal block 4P Conduit Power supply wiring Ground wire Indoor PC board ASSY Cl...

Page 13: ... out the test operation in accordance with the Operation Manual to ensure that all functions and parts are working properly The air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air cond...

Page 14: ...Two dimensional bar code is a code for manufacturing 3P297301 3C M11B121B 1210 HT 00_CV_3P297301 3C indd 2 10 26 2012 11 23 57 AM ...

Reviews: