Choosing an Installation Site

• Before choosing the installation site, obtain user approval.

1. 

Indoor unit

CAUTION

• When moving the unit during or after unpacking, make sure to lift it by holding its lifting lugs.  Do not exert any pressure on 

other parts, especially the refrigerant piping, drain piping and flange parts. 
Wear protective gear (such as gloves) when installing the unit.

• If you think the humidity inside the ceiling might exceed 86°F (30°C) and RH80%, reinforce the insulation on the unit body. 

Use glass wool or polyethylene foam as insulation so that the thickness is more than 0.4in (10mm) and fits inside the ceiling 
opening.

• Optimum air distribution is ensured.
• The air passage is not blocked.
• Condensate can drain properly.
• The ceiling is strong enough to bear the weight of the indoor unit.
• A false ceiling does not seem to be at an incline.
• Sufficient clearance for maintenance and servicing is ensured.
• Piping between the indoor and outdoor units is within the allowable limits.  

(Refer to the installation manual for the outdoor unit.)

• The indoor unit, outdoor unit, power supply wiring and transmission wiring is at 

least 3.3ft (1m) away from televisions and radios. This prevents image interfer

-

ence and noise in electrical appliances. (Noise may be generated depending 
on the conditions under which the electric wave is generated, even if a 3.3ft 
(1m) allowance is maintained.)

 

Use suspension bolts to install the unit. Check whether or not the 
ceiling is strong enough to support the weight of the unit. If there is 
a risk that the ceiling is not strong enough, reinforce the ceiling 
before installing the unit.

(Installation pitch is marked on the carton box for installation. Refer to it to check 
for points requiring reinforcing.) Select the *H dimension such that a downward 
slope of at least 1/100 is ensured as indicated in “

Drain Piping Work

”.

• The installation pitch is listed on the packing material, and should be checked 

when deciding whether to reinforce the location or not.

Control box

Maintenance

space

12 (300)

or more

13/16 (20) or more

100 (2500)  or more

*H= 9-1/2 (240) or more

7-7/8  (200)

Ceiling

Floor surface

(unit : in (mm))

If there is  no ceiling

 

Select the signal receiver mounting location according to the 
following conditions:

• Install the signal receiver, which has a built-in temperature sensor, near the 

intake vent where there is convection of air and it can get an accurate reading 
of the room’s temperature. If the intake vent is in another room or the unit 
cannot be installed near the intake vent for any other reason, install it 5ft 
(1.5m) above the floor on a wall where there is convection.

• In order to get an accurate reading of the room’s temperature, install the signal 

receiver in a location where it is not exposed directly to cold or hot air from the 
air discharge grille or to direct sunlight.

• Since the receiver has a built-in light receptor to receive signals from the 

wireless remote controller, do not mount it in a location where the signal may 
be blocked by a curtain, etc.

Air outlet grille: 
Wooden or plastic grille is recommended 
because condensation may occur 
depending on humidity conditions.

CAUTION

If the signal receiver is not installed in a location where there is convection of air, it may be unable to get an accurate reading 
of the room’s temperature.

01_EN_3P297301-3C.indd   3

10/26/2012   11:27:23 AM

Summary of Contents for SUPER MULTI NX CDXS18LVJU

Page 1: ...ANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalación English Français Español MODELS FDXS09LVJU FDXS12LVJU CDXS15LVJU CDXS18LVJU CDXS24LVJU Manuel dinstallation 00_CV_3P297301 3C indd 1 10 26 2012 11 23 56 AM ...

Page 2: ...bags so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk of explosion resulting in serious injury or death Do not ground units to telephone wires or lightning rods because lightning strikes could cause a severe shock hazard resulting in severe injury or d...

Page 3: ...ault circuit interrupter breaker may result in electrically shocks or personal injury CAUTION Establish drain piping according to the instructions of this manual Inadequate piping may cause water damage Note for installing the outdoor unit For heat pump model only In regions of the country where the outside temperature is at or below the freezing point the drain may freeze If so it is recommended ...

Page 4: ...ough reinforce the ceiling before installing the unit Installation pitch is marked on the carton box for installation Refer to it to check for points requiring reinforcing Select the H dimension such that a downward slope of at least 1 100 is ensured as indicated in Drain Piping Work The installation pitch is listed on the packing material and should be checked when deciding whether to reinforce t...

Page 5: ... to reinforce the ceiling frame to prevent shaking Consult an architect or carpenter for details Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor sunken insert sunken anchor for existing ceilings and a sunken insert sunken anchor or other part to be procured in the field to reinforce the ceiling to bearing the weight of the unit Refer to Fig 19 11 16 500 17 3 4 45...

Page 6: ...cessory accessory For bottom intake type 4 Attach the hanger right insulation to the right hanger Stored in outlet vent See the below figure for the sticking base line Hanger right insulation accessory Slit Sticking base line Hanger bracket right Arrow view 5 Attach the air filter accessory in the manner shown in the diagram In case of bottom side In case of back side Filter Push Push Main unit At...

Page 7: ... with water In using a plastic tube instead of a level adjust the top surface of the unit to the surface of the water at both ends of the plastic tube and adjust the unit horizontally One thing to watch out for in particular is if it is installed so that the slope is not in the direction of the drain piping as this might cause leaking Tighten the upper nut Mounting the receiver Mount the receiver ...

Page 8: ...o prevent damage to the flare nuts and escaping gas Flare nut tightening torque Gas side Liquid side 3 8 inch 9 5mm 1 2 inch 12 7mm 5 8 inch 15 9mm 1 4 inch 6 4mm 24 1 29 4ft lbf 32 7 39 9N m 36 5 44 5ft lbf 49 5 60 3N m 45 6 55 6ft lbf 61 8 75 4N m 10 4 12 7ft lbf 14 2 17 2N m CAUTION Overtightening may damage the flare and cause leaks 3 After the work is finished make sure to check that there is...

Page 9: ...ness 13 32 inch 10mm Min 1 3 16 inch 30mm or more 1 9 16 inch 40mm or more 1 15 16 inch 50mm or more 1 3 16 inch 30mm or more Thickness 0 031 inch 0 8mm C1220T O Thickness 0 039 inch 1 0mm C1220T O Thickness 0 031 inch 0 8mm C1220T O Also when subject to high humidity heat insulation of the refrigerant piping the unit piping and branch piping must be further reinforced Reinforce the insulation whe...

Page 10: ... the indoor unit through the drain pipes and corrode the heat exchanger Do not twist or bend the drain hose so that excessive force is not applied to it This type of treatment may cause leaking After piping work is finished check drainage flows smoothly Gradually insert approximately 1L of water into the drain pan to check drainage in the manner described below Gradually pour approximately 1L of w...

Page 11: ...laths of the net or fence shape or metal plating into wooden buildings Wiring See the installation manual supplied with the outdoor unit HOW TO CONNECT WIRINGS Wire only after removing the control box cover as shown in the Fig Remote controller wiring Control box cover Wiring Diagram rear Conduit mounting plate accessory Conduit field supply Lock nut field supply Screw accessory Power supply wiring ...

Page 12: ...e control box cover Next pull the wires into the unit through the conduit and thread them through the insulation tube accessory then connect to the power wiring terminal block 4P Secure the wires covered by the insulation tube with the clamp accessory Be sure to put the part of the sheathed vinyl into the control box Terminal block 4P Conduit Power supply wiring Ground wire Indoor PC board ASSY Cl...

Page 13: ... out the test operation in accordance with the Operation Manual to ensure that all functions and parts are working properly The air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air cond...

Page 14: ...Two dimensional bar code is a code for manufacturing 3P297301 3C M11B121B 1210 HT 00_CV_3P297301 3C indd 2 10 26 2012 11 23 57 AM ...