Refrigerant Piping Work

See the installation manual supplied with the outdoor unit.

1. 

Flaring the pipe end

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing down

-

ward so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

A

A

(Cut exactly at right angles.)

Remove burrs

Flare’s inner surface 

must be flaw-free.

The pipe end must 

be evenly flared in a 

perfect circle.

Make sure that the 

flare nut is fitted.

Check

0-0.02in (0-0.5mm)

0.04-0.06in (1.0-1.5mm) 0.06-0.08in (1.5-2.0mm)

Set exactly at the position shown below.

Clutch-type

Flare tool for R410A

Clutch-type (Rigid-type) Wing-nut type (Imperial-type)

Conventional flare tool

Flaring

Die

WARNING

• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a drier to this R410A unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system. 

Incomplete flaring may cause refrigerant gas leakage.

2. 

Refrigerant piping

1) To prevent gas leakage, apply refrigeration machine oil to the inner 

surface of the flare. (Use refrigeration oil for R410A)

2) Align the centers of both flares and tighten the flare nuts 3 or 4 turns 

by hand. Then tighten them fully with the torque wrenches.

• Use torque wrenches when tightening the flare nuts to prevent 

damage to the flare nuts and escaping gas.

Flare nut tightening torque

Gas side

Liquid side

3/8 inch 

(9.5mm)

1/2 inch 

(12.7mm)

5/8 inch 

(15.9mm)

1/4 inch 

(6.4mm)

24.1-29.4ft•lbf 

(32.7-39.9N•m)

36.5-44.5ft•lbf 

(49.5-60.3N•m)

45.6-55.6ft•lbf 

(61.8-75.4N•m)

10.4-12.7ft•lbf 

(14.2-17.2N•m)

CAUTION

• 

Overtightening may damage the flare and cause leaks.

3) 

After the work is finished, make sure to 

check that there is no gas leak.

Torque wrench

Piping union

Flare nut

Spanner

Do not apply refrigeration 
oil to the outer surface.

Flare nut

Apply refrigeration 
oil to the inner 

surface of the flare.

Do not apply refrigeration oil to 

the flare nut to avoid tightening 
with excessive torque.

4) After checking for gas leaks, be sure to insulate the pipe connections.

• Insulate using the insulation for fitting included with the liquid and gas pipes. Besides, make sure the insulation for fitting 

on the liquid and gas piping has its seams facing up. 
(Tighten both edges with clamp.)

• For the gas piping, wrap the medium sealing pad over the insulation for fitting (flare nut part).

Gas pipe

Liquid pipe

Piping insulation 
material (main unit)

Attach to base

Flare nut connection

Turn seams up

Insulation for fitting 

(accessory)

Clamp 

Piping insulation material
(Field supplied)

Gas Piping Insulation Procedure

(accessory)

Main unit

Clamp (accessory)

Flare nut connection

Turn seams up

Piping insulation material
(Field supplied)

Piping insulation 
material (main unit)

Attach to base

Main unit

Insulation for fitting 

(accessory)

Liquid Piping Insulation Procedure

Small sealing pad 

Measure the length of the gas 
pipe as you will have to cover 
it with the sealing tape.

(accessory)

Wrap the sealing 

tape around the 

gas pipe.

Main unit

01_EN_3P297301-3C.indd   7

10/26/2012   11:27:25 AM

Summary of Contents for SUPER MULTI NX CDXS18LVJU

Page 1: ...ANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalación English Français Español MODELS FDXS09LVJU FDXS12LVJU CDXS15LVJU CDXS18LVJU CDXS24LVJU Manuel dinstallation 00_CV_3P297301 3C indd 1 10 26 2012 11 23 56 AM ...

Page 2: ...bags so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk of explosion resulting in serious injury or death Do not ground units to telephone wires or lightning rods because lightning strikes could cause a severe shock hazard resulting in severe injury or d...

Page 3: ...ault circuit interrupter breaker may result in electrically shocks or personal injury CAUTION Establish drain piping according to the instructions of this manual Inadequate piping may cause water damage Note for installing the outdoor unit For heat pump model only In regions of the country where the outside temperature is at or below the freezing point the drain may freeze If so it is recommended ...

Page 4: ...ough reinforce the ceiling before installing the unit Installation pitch is marked on the carton box for installation Refer to it to check for points requiring reinforcing Select the H dimension such that a downward slope of at least 1 100 is ensured as indicated in Drain Piping Work The installation pitch is listed on the packing material and should be checked when deciding whether to reinforce t...

Page 5: ... to reinforce the ceiling frame to prevent shaking Consult an architect or carpenter for details Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor sunken insert sunken anchor for existing ceilings and a sunken insert sunken anchor or other part to be procured in the field to reinforce the ceiling to bearing the weight of the unit Refer to Fig 19 11 16 500 17 3 4 45...

Page 6: ...cessory accessory For bottom intake type 4 Attach the hanger right insulation to the right hanger Stored in outlet vent See the below figure for the sticking base line Hanger right insulation accessory Slit Sticking base line Hanger bracket right Arrow view 5 Attach the air filter accessory in the manner shown in the diagram In case of bottom side In case of back side Filter Push Push Main unit At...

Page 7: ... with water In using a plastic tube instead of a level adjust the top surface of the unit to the surface of the water at both ends of the plastic tube and adjust the unit horizontally One thing to watch out for in particular is if it is installed so that the slope is not in the direction of the drain piping as this might cause leaking Tighten the upper nut Mounting the receiver Mount the receiver ...

Page 8: ...o prevent damage to the flare nuts and escaping gas Flare nut tightening torque Gas side Liquid side 3 8 inch 9 5mm 1 2 inch 12 7mm 5 8 inch 15 9mm 1 4 inch 6 4mm 24 1 29 4ft lbf 32 7 39 9N m 36 5 44 5ft lbf 49 5 60 3N m 45 6 55 6ft lbf 61 8 75 4N m 10 4 12 7ft lbf 14 2 17 2N m CAUTION Overtightening may damage the flare and cause leaks 3 After the work is finished make sure to check that there is...

Page 9: ...ness 13 32 inch 10mm Min 1 3 16 inch 30mm or more 1 9 16 inch 40mm or more 1 15 16 inch 50mm or more 1 3 16 inch 30mm or more Thickness 0 031 inch 0 8mm C1220T O Thickness 0 039 inch 1 0mm C1220T O Thickness 0 031 inch 0 8mm C1220T O Also when subject to high humidity heat insulation of the refrigerant piping the unit piping and branch piping must be further reinforced Reinforce the insulation whe...

Page 10: ... the indoor unit through the drain pipes and corrode the heat exchanger Do not twist or bend the drain hose so that excessive force is not applied to it This type of treatment may cause leaking After piping work is finished check drainage flows smoothly Gradually insert approximately 1L of water into the drain pan to check drainage in the manner described below Gradually pour approximately 1L of w...

Page 11: ...laths of the net or fence shape or metal plating into wooden buildings Wiring See the installation manual supplied with the outdoor unit HOW TO CONNECT WIRINGS Wire only after removing the control box cover as shown in the Fig Remote controller wiring Control box cover Wiring Diagram rear Conduit mounting plate accessory Conduit field supply Lock nut field supply Screw accessory Power supply wiring ...

Page 12: ...e control box cover Next pull the wires into the unit through the conduit and thread them through the insulation tube accessory then connect to the power wiring terminal block 4P Secure the wires covered by the insulation tube with the clamp accessory Be sure to put the part of the sheathed vinyl into the control box Terminal block 4P Conduit Power supply wiring Ground wire Indoor PC board ASSY Cl...

Page 13: ... out the test operation in accordance with the Operation Manual to ensure that all functions and parts are working properly The air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air cond...

Page 14: ...Two dimensional bar code is a code for manufacturing 3P297301 3C M11B121B 1210 HT 00_CV_3P297301 3C indd 2 10 26 2012 11 23 57 AM ...

Reviews: