Service Manual SM-Inverter_(i)
36
Troubleshooting
Check outdoor
installation
condition
Any abnormal?
Check outdoor fan
motor
Fan motor
running
smoothly
Change fan motor
Change outdoor
location. Clean
outdoor coil.
Check outdoor coil
thermistor resistance
Resistance
normal?
Change thermistor
Check refrigerant level, EXV,
stop valve and condenser
ambient temperature
Any abnormal?
Refer to the type
of abnormality and
conduct proper
service
Change outdoor
PCB
Yes
No
No
Yes
No
Yes
Yes
No
*Refer thermistor resistance table