Service Manual SM-Inverter_(i)
12
Zone
Control
Stop
Compressor is stopped when a certain limit reaches the stop zone for abnormality
correction.
Drop
Frequency will be dropped with a timer setting.
Keep
Frequency is maintained at lower/upper limit.
Up
Frequency will be increased with a timer setting.
Reset
Frequency lower/upper limit is canceled and returned to command rotation.
HIGH PRESSURE PROTECTION
-
To prevent high pressure in the system.
-
Compressor operating frequency is adjusted based on upper limit of coil temperature
-
The compressor frequency is adjusted based on coil temperature:
•
During cooling mode – outdoor coil temperature.
•
During heating mode – indoor coil temperature.
-
This protection is activated when the coil temperature > 64°C, the compressor stop and OD fan stop after
30s.
-
The unit can only be restarted after 3 minutes.