6 Installation

Installer reference guide

22

RZAG71~Y1

Sky Air Alpha-series

4P486046-1A – 2017.08

6

When the display is not blinking anymore, press the BS3 button
again to activate vacuum mode.

To deactivate vacuum mode:

After charging or vacuuming the unit, please deactivate the vacuum
mode by changing the setting back to '

0

'.

Make  sure  to  reattach  the  electronic  component  box  cover  and  to
install the front cover after the job is finished.

NOTICE

Make  sure  that  all  outside  panels,  except  for  the  service
cover  on  the  electrical  component  box,  are  closed  while
working.

Close the lid of the electrical component box firmly before
turning on the power.

6.6.10

To completely recharge refrigerant

WARNING

▪ Only  use  R32  as  refrigerant.  Other  substances  may

cause explosions and accidents.

▪ R32  contains  fluorinated  greenhouse  gases.  Its  global

warming  potential  (GWP)  value  is  675.  Do  NOT  vent
these gases into the atmosphere.

▪ When  charging  refrigerant,  always  use  protective

gloves and safety glasses.

CAUTION

To  avoid  compressor  breakdown,  do  NOT  charge  more
than the specified amount of refrigerant.

Prerequisite: 

Before  completely  recharging  refrigerant,  make  sure

the  system  is  pumped  down,  the  outdoor  unit's 

external

  refrigerant

piping  is  checked  (leak  test,  vacuum  drying)  and  vacuum  drying  on
the outdoor unit's 

internal

 refrigerant piping is performed.

1

If not already done (for vacuum drying of the unit), activate the
vacuum  mode  (see 

"6.6.9  To  activate/deactivate  the  vacuum

mode field setting" on page 21

)

2

Connect the refrigerant cylinder to the service port of the liquid
stop valve.

3

Open the liquid stop valve.

4

Charge the complete refrigerant amount.

5

Deactivate the vacuum mode (see 

"6.6.9 To activate/deactivate

the vacuum mode field setting" on page 21

).

6

Open the gas stop valve.

6.6.11

To fix the fluorinated greenhouse gases
label

1

Fill in the label as follows:

b

Contains fluorinated greenhouse gases

2

1

1

1

2

2

kg

tCO

2

eq

GWP × kg

1000

=
=

+

kg

=

kg

=

GWP: XXX

RXXX

a

f

c

d
e

a

If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of 

a

.

b

Factory refrigerant charge: see unit name plate

c

Additional refrigerant amount charged

d

Total refrigerant charge

e

Greenhouse gas emissions

 of the total refrigerant charge

expressed as tonnes CO

2

-equivalent

f

GWP = Global warming potential

NOTICE

In  Europe,  the 

greenhouse  gas  emissions

  of  the  total

refrigerant  charge  in  the  system  (expressed  as  tonnes
CO

2

-equivalent)  is  used  to  determine  the  maintenance

intervals. Follow the applicable legislation.

Formula  to  calculate  the  greenhouse  gas  emissions:

GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000

2

Fix  the  label  on  the  inside  of  the  outdoor  unit.  There  is  a
dedicated place for it on the wiring diagram label.

6.7

Connecting the electrical wiring

6.7.1

About connecting the electrical wiring

Typical workflow

Connecting  the  electrical  wiring  typically  consists  of  the  following
stages:

1

Making  sure  the  power  supply  system  complies  with  the
electrical specifications of the units.

2

Connecting the electrical wiring to the outdoor unit.

3

Connecting the electrical wiring to the indoor units.

4

Connecting the main power supply.

6.7.2

About electrical compliance

RZAG71~140M7V1B

Equipment  complying  with  EN/IEC  61000‑3‑12  (European/
International  Technical  Standard  setting  the  limits  for  harmonic
currents  produced  by  equipment  connected  to  public  low-voltage
systems with input current >16 A and ≤75 A per phase.).

RZAG71~140M7Y1B

Equipment 

complying 

with 

EN/IEC 

61000‑3‑2 

(European/

International  Technical  Standard  setting  the  limits  for  harmonic
currents  produced  by  equipment  connected  to  public  low-voltage
systems with input current ≤16 A per phase.).

6.7.3

Precautions when connecting the
electrical wiring

INFORMATION

Also  read  the  precautions  and  requirements  in  the
following chapters:

▪ General safety precautions

▪ Preparation

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

CAUTION

For  use  of  units  in  applications  with  temperature  alarm
settings  it  is  recommended  to  foresee  a  delay  of  10
minutes  for  signalling  the  alarm  in  case  the  alarm
temperature  is  exceeded.  The  unit  may  stop  for  several
minutes during normal operation for "defrosting the unit", or
when in "thermostat stop" operation.

WARNING

Do  not  interchange  the  supply  conductors  L  and  the
neutral conductor N.

Summary of Contents for SkyAir RZAG100M7V1B

Page 1: ...staller reference guide Sky Air Alpha series English Installer reference guide Sky Air Alpha series RZAG71M7V1B RZAG100M7V1B RZAG125M7V1B RZAG140M7V1B RZAG71M7Y1B RZAG100M7Y1B RZAG125M7Y1B RZAG140M7Y1...

Page 2: ...2 Precautions when checking the refrigerant piping 18 6 5 3 Checking refrigerant piping Setup 18 6 5 4 To check for leaks 18 6 5 5 To perform vacuum drying 18 6 6 Charging refrigerant 19 6 6 1 About c...

Page 3: ...T touch the refrigerant piping water piping or internal parts during and immediately after operation It could be too hot or too cold Give it time to return to normal temperature If you must touch it w...

Page 4: ...operated and stored must be larger than the minimum floor area defined in table below A m2 This applies to Indoor units without refrigerant leakage sensor in case of indoor units with refrigerant lea...

Page 5: ...eakage If refrigerant gas leaks ventilate the area immediately Possible risks Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency Toxic gas may be produced if refrigera...

Page 6: ...gory III condition MUST be installed in the fixed wiring WARNING ONLY use copper wires Make sure the field wiring complies with the applicable legislation All field wiring must be performed in accorda...

Page 7: ...er Description General safety precautions Safety instructions that you must read before installing About the documentation What documentation exists for the installer About the box How to unpack the u...

Page 8: ...connecting multiple indoor units to the outdoor unit you need one or more refrigerant branch kits The outdoor indoor combination determines which and how many refrigerant branch kits to use Layout Mo...

Page 9: ...urroundings Choose a location where the hot cold air discharged from the unit or the operation noise will NOT disturb anyone Heat exchanger fins are sharp and injury is possible Choose an installation...

Page 10: ...imum inclination of 15 or vertically Make the length of the branch pipes to the indoor units as short as possible Try to keep length of the branch pipes to the indoor units equal Definitions L1 L7 H1...

Page 11: ...difference The piping lengths and height differences must comply with the following requirements Requirement Limit 71 100 125 140 1 Minimum total one way piping length Pair Limit L1 Twin Limit L1 L3...

Page 12: ...wires stranded conductor wires extension cords or connections from a star system They can cause overheating electrical shock or fire Do NOT install a phase advancing capacitor because this unit is eq...

Page 13: ...installation structure Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise Fix the unit securely by means of foundation bolts in a...

Page 14: ...ng 6 3 6 To prevent the outdoor unit from falling over In case the unit is installed in places where strong wind can tilt the unit take following measure 1 Prepare 2 cables as indicated in the followi...

Page 15: ...Torque wrench b Spanner c Piping union d Flare nut Piping size mm Tightening torque N m Flare dimensions A mm Flare shape mm 9 5 33 39 12 8 13 2 R 0 4 0 8 45 2 90 2 A 15 9 63 75 19 3 19 7 6 4 4 Pipe...

Page 16: ...frigerant leak a b a Spanner b Torque wrench When it is expected that the operating pressure will be low e g when cooling will be performed while the outside air temperature is low sufficiently seal t...

Page 17: ...he system a NOTICE Do not block the air vents This could affect air circulation inside the unit WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Sma...

Page 18: ...bble test solution from your wholesaler Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping gets cold and o...

Page 19: ...nit s internal refrigerant piping it is necessary to activate the vacuum mode see 6 6 9 To activate deactivate the vacuum mode field setting on page 21 which will open required valves in the refrigera...

Page 20: ...Height difference between the highest indoor unit and the outdoor unit H2 Height difference between the highest and the lowest indoor unit Refrigerant branch kit 6 6 5 To determine the additional refr...

Page 21: ...uble twin 6 6 7 Charging refrigerant Setup See 6 5 3 Checking refrigerant piping Setup on page 18 6 6 8 To charge additional refrigerant WARNING Only use R32 as refrigerant Other substances may cause...

Page 22: ...d stick it on top of a b Factory refrigerant charge see unit name plate c Additional refrigerant amount charged d Total refrigerant charge e Greenhouse gas emissions of the total refrigerant charge ex...

Page 23: ...ed crimp style ring terminals 6 7 5 Specifications of standard wiring components Component V1 Y1 71 100 140 71 100 125 140 Power supply cable MCA a 18 8 A 28 5 A 12 3 A 15 9 A 15 7 A 15 4 A Voltage ra...

Page 24: ...frame Choose one of the 3 possibilities a b a b a b 2 3 1 a Power supply cable b Interconnection cable Connecting to the frame When cables are routed from the unit a protection sleeve for the conduit...

Page 25: ...at up the compressor oil to avoid oil shortage and compressor breakdown during startup NOTICE NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor migh...

Page 26: ...ice cover to prevent electric shocks 3 Turn ON power for at least 6 hours before starting operation to protect the compressor 4 On the user interface set the unit to cooling operation mode 2 Start the...

Page 27: ...the unit 9 Maintenance and service NOTICE Maintenance must be done by an authorised installer or service agent We recommend to do maintenance at least once a year However applicable legislation might...

Page 28: ...for reuse recycling and recovery 11 1 Overview Disposal Typical workflow Disposing of the system typically consists of the following stages 1 Pumping down the system 2 Bringing the system to a specia...

Page 29: ...nits 1 1 2 1 A E a b c d e eB eD HB HD HU mm a b c d e eB eD A B C D E HB HU HD B 100 A B C 100 100 100 B E 100 1000 500 A B C E 150 150 150 1000 500 D 500 D E 1000 500 500 500 B D 100 B D E HB HD HB...

Page 30: ...pper unit high enough above the lower unit to prevent ice buildup at the upper unit s bottom plate B1 B2 B1 If there is no danger of drainage dripping and freezing between the upper and lower units B2...

Page 31: ...tive devices S1PH S1PLand Q1E 3 Refer to the combination table and the option manual for how to connect the wiring to X6A X28A and X77A 4 Colours BLK black RED red BLU blue WHT white GRN green 4 Legen...

Page 32: ...icable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual Instruction manual specified for a cert...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ...4P486046 1A 2017 08 Copyright 2017 Daikin...

Reviews: