background image

6 Installation

Installer reference guide

16

RZAG71~Y1

Sky Air Alpha-series

4P486046-1A – 2017.08

a

b

c

d

e

f

f

a

Refrigerant piping

b

Part to be brazed

c

Taping

d

Manual valve

e

Pressure-reducing valve

f

Nitrogen

▪ Do NOT use anti-oxidants when brazing pipe joints.

Residue can clog pipes and break equipment.

▪ Do  NOT  use  flux  when  brazing  copper-to-copper  refrigerant

piping.  Use  phosphor  copper  brazing  filler  alloy  (BCuP),  which
does not require flux.
Flux  has  an  extremely  harmful  influence  on  refrigerant  piping
systems. For instance, if chlorine based flux is used, it will cause
pipe  corrosion  or,  in  particular,  if  the  flux  contains  fluorine,  it  will
deteriorate the refrigerant oil.

6.4.7

Using the stop valve and service port

To handle the stop valve

Take the following guidelines into account:

▪ The stop valves are factory closed.

▪ The following illustration shows each part required in handling the

valve.

c
d

a

b

a

Service port and service port cap

b

Valve stem

c

Field piping connection

d

Stem cap

▪ Keep both stop valves open during operation.

▪ Do  NOT  apply  excessive  force  to  the  valve  stem.  Doing  so  may

break the valve body.

▪ Always  make  sure  to  secure  the  stop  valve  with  a  spanner,  then

loosen or tighten the flare nut with a torque wrench. Do NOT place
the  spanner  on  the  stem  cap,  as  this  could  cause  a  refrigerant
leak.

a

b

a

Spanner

b

Torque wrench

▪ When  it  is  expected  that  the  operating  pressure  will  be  low  (e.g.

when  cooling  will  be  performed  while  the  outside  air  temperature
is  low),  sufficiently  seal  the  flare  nut  in  the  stop  valve  on  the  gas
line with silicon sealant to prevent freezing.

Silicon sealant, make sure there is no gap.

To open/close the stop valve

1

Remove the stop valve cover.

2

Insert  a  hexagon  wrench  (liquid  side:  4  mm,  gas  side:  6  mm)
into the valve stem and turn the valve stem:

Counterclockwise to open.
Clockwise to close.

3

When the stop valve cannot be turned any further, stop turning.
The valve is now opened/closed.

To handle the stem cap

▪ The  stem  cap  is  sealed  where  indicated  with  the  arrow.  Do  NOT

damage it.

▪ After handling the stop valve, tighten the stem cap, and check for

refrigerant leaks.

Item

Tightening torque (N∙m)

Stem cap, liquid side

13.5~16.5

Stem cap, gas side

22.5~27.5

To handle the service cap

▪ Always  use  a  charge  hose  equipped  with  a  valve  depressor  pin,

since the service port is a Schrader type valve.

▪ After  handling  the  service  port,  tighten  the  service  port  cap,  and

check for refrigerant leaks.

Item

Tightening torque (N∙m)

Service port cap

11.5~13.9

6.4.8

To connect the refrigerant piping to the
outdoor unit

Piping length.

 Keep field piping as short as possible.

Piping  protection.

  Protect  the  field  piping  against  physical

damage.

1

Do the following:

▪ Remove the service cover (a) with screw (b).
▪ Remove the piping intake plate (c) with screw (d).

c

a

b

d

2

Choose a piping route (a, b, c or d).

Summary of Contents for SkyAir RZAG100M7V1B

Page 1: ...staller reference guide Sky Air Alpha series English Installer reference guide Sky Air Alpha series RZAG71M7V1B RZAG100M7V1B RZAG125M7V1B RZAG140M7V1B RZAG71M7Y1B RZAG100M7Y1B RZAG125M7Y1B RZAG140M7Y1...

Page 2: ...2 Precautions when checking the refrigerant piping 18 6 5 3 Checking refrigerant piping Setup 18 6 5 4 To check for leaks 18 6 5 5 To perform vacuum drying 18 6 6 Charging refrigerant 19 6 6 1 About c...

Page 3: ...T touch the refrigerant piping water piping or internal parts during and immediately after operation It could be too hot or too cold Give it time to return to normal temperature If you must touch it w...

Page 4: ...operated and stored must be larger than the minimum floor area defined in table below A m2 This applies to Indoor units without refrigerant leakage sensor in case of indoor units with refrigerant lea...

Page 5: ...eakage If refrigerant gas leaks ventilate the area immediately Possible risks Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency Toxic gas may be produced if refrigera...

Page 6: ...gory III condition MUST be installed in the fixed wiring WARNING ONLY use copper wires Make sure the field wiring complies with the applicable legislation All field wiring must be performed in accorda...

Page 7: ...er Description General safety precautions Safety instructions that you must read before installing About the documentation What documentation exists for the installer About the box How to unpack the u...

Page 8: ...connecting multiple indoor units to the outdoor unit you need one or more refrigerant branch kits The outdoor indoor combination determines which and how many refrigerant branch kits to use Layout Mo...

Page 9: ...urroundings Choose a location where the hot cold air discharged from the unit or the operation noise will NOT disturb anyone Heat exchanger fins are sharp and injury is possible Choose an installation...

Page 10: ...imum inclination of 15 or vertically Make the length of the branch pipes to the indoor units as short as possible Try to keep length of the branch pipes to the indoor units equal Definitions L1 L7 H1...

Page 11: ...difference The piping lengths and height differences must comply with the following requirements Requirement Limit 71 100 125 140 1 Minimum total one way piping length Pair Limit L1 Twin Limit L1 L3...

Page 12: ...wires stranded conductor wires extension cords or connections from a star system They can cause overheating electrical shock or fire Do NOT install a phase advancing capacitor because this unit is eq...

Page 13: ...installation structure Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise Fix the unit securely by means of foundation bolts in a...

Page 14: ...ng 6 3 6 To prevent the outdoor unit from falling over In case the unit is installed in places where strong wind can tilt the unit take following measure 1 Prepare 2 cables as indicated in the followi...

Page 15: ...Torque wrench b Spanner c Piping union d Flare nut Piping size mm Tightening torque N m Flare dimensions A mm Flare shape mm 9 5 33 39 12 8 13 2 R 0 4 0 8 45 2 90 2 A 15 9 63 75 19 3 19 7 6 4 4 Pipe...

Page 16: ...frigerant leak a b a Spanner b Torque wrench When it is expected that the operating pressure will be low e g when cooling will be performed while the outside air temperature is low sufficiently seal t...

Page 17: ...he system a NOTICE Do not block the air vents This could affect air circulation inside the unit WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Sma...

Page 18: ...bble test solution from your wholesaler Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping gets cold and o...

Page 19: ...nit s internal refrigerant piping it is necessary to activate the vacuum mode see 6 6 9 To activate deactivate the vacuum mode field setting on page 21 which will open required valves in the refrigera...

Page 20: ...Height difference between the highest indoor unit and the outdoor unit H2 Height difference between the highest and the lowest indoor unit Refrigerant branch kit 6 6 5 To determine the additional refr...

Page 21: ...uble twin 6 6 7 Charging refrigerant Setup See 6 5 3 Checking refrigerant piping Setup on page 18 6 6 8 To charge additional refrigerant WARNING Only use R32 as refrigerant Other substances may cause...

Page 22: ...d stick it on top of a b Factory refrigerant charge see unit name plate c Additional refrigerant amount charged d Total refrigerant charge e Greenhouse gas emissions of the total refrigerant charge ex...

Page 23: ...ed crimp style ring terminals 6 7 5 Specifications of standard wiring components Component V1 Y1 71 100 140 71 100 125 140 Power supply cable MCA a 18 8 A 28 5 A 12 3 A 15 9 A 15 7 A 15 4 A Voltage ra...

Page 24: ...frame Choose one of the 3 possibilities a b a b a b 2 3 1 a Power supply cable b Interconnection cable Connecting to the frame When cables are routed from the unit a protection sleeve for the conduit...

Page 25: ...at up the compressor oil to avoid oil shortage and compressor breakdown during startup NOTICE NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor migh...

Page 26: ...ice cover to prevent electric shocks 3 Turn ON power for at least 6 hours before starting operation to protect the compressor 4 On the user interface set the unit to cooling operation mode 2 Start the...

Page 27: ...the unit 9 Maintenance and service NOTICE Maintenance must be done by an authorised installer or service agent We recommend to do maintenance at least once a year However applicable legislation might...

Page 28: ...for reuse recycling and recovery 11 1 Overview Disposal Typical workflow Disposing of the system typically consists of the following stages 1 Pumping down the system 2 Bringing the system to a specia...

Page 29: ...nits 1 1 2 1 A E a b c d e eB eD HB HD HU mm a b c d e eB eD A B C D E HB HU HD B 100 A B C 100 100 100 B E 100 1000 500 A B C E 150 150 150 1000 500 D 500 D E 1000 500 500 500 B D 100 B D E HB HD HB...

Page 30: ...pper unit high enough above the lower unit to prevent ice buildup at the upper unit s bottom plate B1 B2 B1 If there is no danger of drainage dripping and freezing between the upper and lower units B2...

Page 31: ...tive devices S1PH S1PLand Q1E 3 Refer to the combination table and the option manual for how to connect the wiring to X6A X28A and X77A 4 Colours BLK black RED red BLU blue WHT white GRN green 4 Legen...

Page 32: ...icable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual Instruction manual specified for a cert...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ...4P486046 1A 2017 08 Copyright 2017 Daikin...

Reviews: