4 Installation

Installation manual

10

250D7Y1B

Sky Air Advance-series

4P573384-1 – 2019.04

NOTICE

To  perform  vacuum  drying  or  a  complete  recharge  of  the
outdoor  unit’s  internal  refrigerant  piping  it  is  necessary  to
activate the vacuum mode (see 

"To activate/deactivate the

vacuum  mode  field  setting" 

[

4

  12])  which  will  open

required  valves  in  the  refrigerant  circuit  so  the  vacuuming
process or recharge of refrigerant can be done properly.

▪ Before  vacuum  drying  or  recharging,  activate  field

setting "vacuum mode".

▪ After finishing vacuum drying or recharging, deactivate

field setting "vacuum mode".

WARNING

Some  sections  of  the  refrigerant  circuit  may  be  isolated
from  other  sections  caused  by  components  with  specific
functions  (e.g.  valves).  The  refrigerant  circuit  therefore
features  additional  service  ports  for  vacuuming,  pressure
relief or pressurizing the circuit.

In case it is required to perform 

brazing

 on the unit, ensure

that there is no pressure remaining inside the unit. Internal
pressures  need  to  be  released  with  ALL  the  service  ports
indicated  on  the  figures  below  opened.  The  location  is
depending on model type.

Location of service ports:

b

c

a

a

Internal service port

b

Stop valve with service port (liquid)

c

Stop valve with service port (gas)

Typical  workflow  –  Completely  recharging  refrigerant  typically
consists of the following stages:

1 Determining how much refrigerant to charge.

2 Charging refrigerant.

3 Filling in the fluorinated greenhouse gases label, and fixing it to

the inside of the outdoor unit.

4.4.2

About the refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

Refrigerant type: R32

Global warming potential (GWP) value: 675

WARNING: FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

WARNING

▪ Do NOT pierce or burn refrigerant cycle parts.

▪ Do NOT use cleaning materials or means to accelerate

the  defrosting  process  other  than  those  recommended
by the manufacturer.

▪ Be  aware  that  the  refrigerant  inside  the  system  is

odourless.

WARNING

The  refrigerant  inside  the  unit  is  mildly  flammable,  but
normally  does  NOT  leak.  If  the  refrigerant  leaks  in  the
room  and  comes  in  contact  with  fire  from  a  burner,  a
heater, or a cooker, this may result in fire, or the formation
of a harmful gas.

Turn  off  any  combustible  heating  devices,  ventilate  the
room,  and  contact  the  dealer  where  you  purchased  the
unit.

Do  NOT  use  the  unit  until  a  service  person  confirms  that
the  part  from  which  the  refrigerant  leaked  has  been
repaired.

4.4.3

Precautions when charging refrigerant

INFORMATION

Also  read  the  precautions  and  requirements  in  the
following chapters:

▪ General safety precautions

▪ Preparation

4.4.4

Definitions: L1~L7, H1, H2

Pair

(a)

H1

L1

Twin

(a)

H1

H2

L1

L2

L3

Triple

(a)

L2

L3

L4

H1

H2

L1

Double twin

(a)

H1

H2

L1

L2

L3

L4

L5

L6

L7

(a)

Assume that the longest line in the illustration corresponds
with the actual longest pipe, and the highest unit in the
illustration corresponds with the actual highest unit.

L1

Main piping

L2~L7

Branch piping

H1

Height difference between the highest indoor unit and the
outdoor unit

Summary of Contents for Sky Air Advance Series

Page 1: ...Installation manual Sky Air Advance series English Installation manual Sky Air Advance series RZA200D7Y1B RZA250D7Y1B...

Page 2: ...HD HU 200 1000 1000 500 HD HU A B C 200 1 300 1000 A B C E 200 1 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 250 1500 300 1500 B D E HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 50...

Page 3: ...6 17 Direktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir n...

Page 4: ...staava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS...

Page 5: ...sioning 14 5 2 To perform a test run 15 5 3 Error codes when performing a test run 16 6 Disposal 16 7 Technical data 17 7 1 Service space Outdoor unit 17 7 2 Piping diagram Outdoor unit 17 7 3 Wiring...

Page 6: ...ance or an operating electric heater 3 1 1 Installation site requirements of the outdoor unit Mind the spacing guidelines See the Technical data chapter and the figures on the inside of the front cove...

Page 7: ...ze between the heat exchanger and the casing of the unit This might decrease the operating efficiency INFORMATION We suggest to install the optional bottom plate heater EKBPH250D7 when the unit is ins...

Page 8: ...tation of the bends NOTICE Always protect the surrounding surfaces e g wiring insulation foam from heat when brazing 6 Do the following Insulate the liquid piping a and the gas piping b Wind heat insu...

Page 9: ...copper flare 4 3 3 To perform vacuum drying To remove all moisture from the system proceed as follows 1 Check that with the vacuum pump turned off the target vacuum is maintained for at least 1 hour 4...

Page 10: ...the refrigerant This product contains fluorinated greenhouse gases Do NOT vent gases into the atmosphere Refrigerant type R32 Global warming potential GWP value 675 WARNING FLAMMABLE MATERIAL The refr...

Page 11: ...70 R1 0 45 0 9 1 35 1 8 2 25 2 7 3 15 Standard liquid pipe size Length m 0 10 10 20 20 30 30 40 40 50 50 60 60 70 R2 0 2 0 4 0 6 0 8 1 1 2 1 4 Size up liquid pipe size Length m 0 5 5 10 10 15 15 20 20...

Page 12: ...refrigerant WARNING Only use R32 as refrigerant Other substances may cause explosions and accidents R32 contains fluorinated greenhouse gases Its global warming potential GWP value is 675 Do NOT vent...

Page 13: ...18 6 A 19 9 A Voltage range 380 415 V Phase 3N Frequency 50 Hz Wire sizes Must comply with applicable legislation Interconnection cables H05VV U4G2 5 Recommended field fuse 20 A Earth leakage circuit...

Page 14: ...ck the insulation resistance of the compressor NOTICE If after installation refrigerant accumulates in the compressor the insulation resistance over the poles can drop but if it is at least 1 M then t...

Page 15: ...e lit For any other action it needs to be lit first The backlight is lit for 30 seconds when you press a button 1 Perform introductory steps Action 1 Open the liquid stop valve and gas stop valve by r...

Page 16: ...ase of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires L4 The air inlet or air outlet is blocked U0...

Page 17: ...m distance between the unit and the edge of obstacle E in the direction of obstacle D HU Height of the unit HB HD Height of obstacles B and D 1 Seal the bottom of the installation frame to prevent dis...

Page 18: ...d Legend Optional Optional Part n Part n Description Description A1P Printed circuit board main A2P Printed circuit board noise filter A3P Printed circuit board inverter A4P Printed circuit board fan...

Page 19: ......

Page 20: ...4P573384 1 2019 04 Copyright 2019 Daikin 4P573384 1 0000000S...

Reviews: