![background image](http://html1.mh-extra.com/html/daikin/rzvf50/rzvf50_installation-manual_4704904037.webp)
2. Items to be checked at delivery
Items to be checked
Check column
Have you carried out field setting? (if necessary)
Are the control box lid, the air filter and the suction
grille attached?
Does the cool air discharge during the cooling
operation? Does the indoor unit makes
unpleasant sound of air discharge?
Have you explained how to operate the air
conditioner showing the operation manual to the
customer?
Have you explained the description of
cooling, program dry and automatic (cooling)
given in the operation manual to the
customer?
If you set the fan speed at thermostat OFF, did you
explain the set fan speed to the customer.
Have you handed the operation manual and the
installation manual to the customer?
Have you checked that there is no generation
of abnormal noise (i.e., noise resulting from
contamination or missing parts)?
Is the printed circuit board switch not on the
emergency (EMG.) side?
The switch is factory set to the normal (NORM.) side.
If an optional accessory is in use, did you check the
operation of the optional accessory and make field
settings as needed?
Is the remote controller icon displayed? Is the
remote controller connected to the master unit if the
system is in simultaneous multi operation?
Have you explained failure examples of
3. SELECTION OF INSTALLATION LOCATION?
Points of the operation explanation
In addition to the general usage, since the items in the
operation manual with the
&
WARNING and
&
CAUTION marks are likely to result in human bodily
injuries and property damages, it is necessary not only
to explain these items to the customer but also to have
the customer read them.
Furthermore, it is necessary to have the customer read
through the troubleshooting items while explaining the
above items.
3. SELECTION OF INSTALLATION LOCATION
Hold the hangers at 4 locations to move the indoor unit
when unpacking or after unpacked, and do not apply force
to the piping (refrigerant and drain) and air outlet flange.
If the temperature and humidity in the ceiling is likely to
exceed 30
°
C, RH80%, use the additional insulation stick to
the indoor unit.
Use the insulation such as glass wool or polyethylene
that has thickness of 10 mm or more. However, keep the
insulated outside dimension smaller than the ceiling
opening so that the unit may go through the opening at
installation.
(1) Select the installation location that meets the following
conditions and get approval of the customer.
• Where the cool and warm air spreads evenly in the
room.
• Where there are no obstacles in the air passage.
• Where drainage can be ensured.
• Where the ceiling's lower surface is not remarkably
inclined.
• Where there is sufficient strength to withstand the mass
of the indoor unit. (If the strength is insufficient, the in
door unit may vibrate and get in contact with the ceiling
and generate unpleasant chattering noise.)
• Where a space sufficient for installation and service can
be ensured.
• Where the piping length between the indoor and the out
door units is ensured within the allowable length. (Refer
to the installation manual attached to the outdoor unit.)
• Where there is no risk of flammable gas leak.
0
0
C')
Ceiling
�
(111121221212 21212 212 2 2 2112 2 2 2
<l;
(length: mm)
Floor surface -
7777,7,77"
Please secure
maintenance
space.
•The H1 dimension indicates the
height of the product.
• Determine the H2 dimension by
maintaining a downward slope of
at least 1/100 as specified in
"7. DRAIN PIPING WORK".
Fig.1
Min. 700 (service space)
[Required installation place]
The dimensions indicate
the minimum required
space of installation.
3
7
Summary of Contents for RZVF50
Page 1: ...1...
Page 2: ...2...
Page 3: ...3...
Page 4: ...4...
Page 5: ...5...
Page 6: ...6...
Page 7: ...7...
Page 8: ...8...
Page 9: ...9...
Page 10: ...10...
Page 11: ...11...
Page 12: ...12...
Page 13: ...13...
Page 14: ...14...
Page 15: ...15...
Page 16: ...16...
Page 17: ...17 17 19 20 20 22 23 27 27 28 31 31 32...
Page 18: ...18...
Page 19: ...19...
Page 20: ...20...
Page 21: ...21...
Page 22: ...22...
Page 23: ...23...
Page 24: ...24...
Page 25: ...255...
Page 26: ...26...
Page 27: ...27...
Page 28: ...28...
Page 29: ...299...
Page 30: ...30...
Page 31: ...31...
Page 32: ...32...
Page 33: ...DR18 1226C Daikin IM OM A 4 Size 3P542797 1 KA B 40P Dt 26 07 19 33...
Page 40: ...40...
Page 57: ...MEMO 57...