background image

2. Items to be checked at delivery

Items to be checked 

Check column 

Have you carried out field setting? (if necessary) 

Are the control box lid, the air filter and the suction 
grille attached? 

Does the cool air discharge during the cooling 

operation? Does the indoor unit makes 
unpleasant sound of air discharge? 

Have you explained how to operate the air 

conditioner showing the operation manual to the 
customer? 

Have you explained the description of 

cooling, program dry and automatic (cooling) 

given in the operation manual to the 
customer? 

If you set the fan speed at thermostat OFF, did you 

explain the set fan speed to the customer. 

Have you handed the operation manual and the 

installation manual to the customer? 

Have you checked that there is no generation 

of abnormal noise (i.e., noise resulting from 
contamination or missing parts)? 

Is the printed circuit board switch not on the 

emergency (EMG.) side? 
The switch is factory set to the normal (NORM.) side. 

If an optional accessory is in use, did you check the 

operation of the optional accessory and make field 
settings as needed? 

Is the remote controller icon displayed? Is the 

remote controller connected to the master unit if the 
system is in simultaneous multi operation? 

Have you explained failure examples of 

3. SELECTION OF INSTALLATION LOCATION? 

Points of the operation explanation 

In addition to the general usage, since the items in the 

operation manual with the 

WARNING and 

CAUTION marks are likely to result in human bodily 

injuries and property damages, it is necessary not only 

to explain these items to the customer but also to have 

the customer read them. 

Furthermore, it is necessary to have the customer read 

through the troubleshooting items while explaining the 

above items. 

3. SELECTION OF INSTALLATION LOCATION

Hold the hangers at 4 locations to move the indoor unit 

when unpacking or after unpacked, and do not apply force 

to the piping (refrigerant and drain) and air outlet flange. 

If the temperature and humidity in the ceiling is likely to 

exceed 30

°

C, RH80%, use the additional insulation stick to 

the indoor unit. 

Use the insulation such as glass wool or polyethylene 

that has thickness of 10 mm or more. However, keep the 

insulated outside dimension smaller than the ceiling 

opening so that the unit may go through the opening at 

installation. 

(1) Select the installation location that meets the following

conditions and get approval of the customer.

• Where the cool and warm air spreads evenly in the

room.

• Where there are no obstacles in the air passage.

• Where drainage can be ensured.

• Where the ceiling's lower surface is not remarkably

inclined.

• Where there is sufficient strength to withstand the mass

of the indoor unit. (If the strength is insufficient, the in­

door unit may vibrate and get in contact with the ceiling

and generate unpleasant chattering noise.)

• Where a space sufficient for installation and service can

be ensured.

• Where the piping length between the indoor and the out­

door units is ensured within the allowable length. (Refer

to the installation manual attached to the outdoor unit.)

• Where there is no risk of flammable gas leak.

C') 

Ceiling 

� 

(111121221212 21212 212 2 2 2112 2 2 2 

<l; 

(length:  mm) 

Floor surface  -

7777,7,77" 

Please secure 

maintenance 

space. 

•The H1 dimension indicates the 

height of the product.

• Determine the H2 dimension by

maintaining a downward slope of
at least 1/100 as specified in
"7. DRAIN PIPING WORK".

Fig.1 

Min. 700 (service space) 

[Required installation place] 

The dimensions indicate 

the minimum required 
space of installation. 

 

3

7

Summary of Contents for RZVF50

Page 1: ...1...

Page 2: ...2...

Page 3: ...3...

Page 4: ...4...

Page 5: ...5...

Page 6: ...6...

Page 7: ...7...

Page 8: ...8...

Page 9: ...9...

Page 10: ...10...

Page 11: ...11...

Page 12: ...12...

Page 13: ...13...

Page 14: ...14...

Page 15: ...15...

Page 16: ...16...

Page 17: ...17 17 19 20 20 22 23 27 27 28 31 31 32...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...24...

Page 25: ...255...

Page 26: ...26...

Page 27: ...27...

Page 28: ...28...

Page 29: ...299...

Page 30: ...30...

Page 31: ...31...

Page 32: ...32...

Page 33: ...DR18 1226C Daikin IM OM A 4 Size 3P542797 1 KA B 40P Dt 26 07 19 33...

Page 34: ...Operation Manual Ask the user to keep this manual in a handy place for future reference WARNING Do not use means to accelerate the defrosting process or to clean other than those recommended by the ma...

Page 35: ...itioner in places such as the following 1 Where there is mist of oil oil spray or vapour for example a kitchen Resin parts may deteriorate and fall out or water may leak 2 Where corrosive gas such as...

Page 36: ...quired for multi slave units in simultaneous multi operation There are 2 kinds of remote controller wired type and wireless type Install the remote controller to the place where the customer has given...

Page 37: ...mer read through the troubleshooting items while explaining the above items 3 SELECTION OF INSTALLATION LOCATION Hold the hangers at 4 locations to move the indoor unit when unpacking or after unpacke...

Page 38: ...uct Refer Fig 2 2 2 Inspection hatch 1 450 x 450 on the control box side and inspection hatch 2 on the bottom of the product Fig 2 3 arrow A 1 3 Inspection hatch 3 on the bottom of the product and on...

Page 39: ...al components before installing the indoor unit 5 INSTALLATION OF INDOOR UNIT Depending on the optional parts it may be easier to attach them beforeinstalling the indoor unit Refer to also the install...

Page 40: ...40...

Page 41: ...ing NOTE 2 After all the brazing works are finished carry out flare connection with the indoor unit Refer to Fig 8 Pressure reducing valve Refrigerant piping Fig 9 NOTE a Taping Nitrogen 1 The proper...

Page 42: ...maged with the clamp end or bend the tip of the metal clamp 1 inward as shown Refer to Fig 12 In case of sticking vinyl tape Vinyl tape Stick vinyl tape without tearing the sealing l material r _ 5 _...

Page 43: ...ing must be carried out by a qualified electrician If a qualified person is not present after the electric wir ing work is finished check the drainage according to the method specified in When the ele...

Page 44: ...circuit Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or a fire Make sure to install an earth leakage breaker Failure to do so may c...

Page 45: ...ctric shocks or a fire 1 Remove the control box lid Fig 20 2 Connect the wiring into the control box through the wiring intake beside the control box Low voltage wiring inlet Remote controller wiring...

Page 46: ...r and indoor units must be matched 2 1 Connect the remote controller only to the master unit 2 2 The remote controller needs to be wired only to the master unit it does not need to be connected to the...

Page 47: ...factory The method of setting procedure and operation is shown in the installation manual attached to the remote controller Note Though setting of ModeNo is carried out as a group if you intend to ca...

Page 48: ...ring to the table below according to the external static pressure of the duct to be connected Table External static Mode No FIRST SECOND pressure CODE No CODE No 50Pa 05 60Pa 06 70Pa 07 80Pa 08 90Pa 0...

Page 49: ...the master unit The indoor unit does not operate properly when two or more remote controllers are attached to the unit in the simultaneous operation system mode 3 7 Earth leakage circuit breaker Eart...

Page 50: ...e the malfunction code NOTE _ DI 1 When the ON OFF button is kept pressed for 5 seconds or longer during the inspection mode the above trouble his tory indication disappears In this case after the mal...

Page 51: ...ct the adapter or Outdoor air thermistor Abnormal stop is applied the capacity is not set to the system malfunction depending on the model or data retention IC Outdoor unit condition The refrigerant m...

Page 52: ...he customer 12 DECLARED RATINGS Rated Values Please do not refer the Capacity Input Power Current Electricity Consumption mentioned on Outdoor unit rating label when this Outdoor is connected with Inv...

Page 53: ...caution to be given when connecting pipes IFi I I ur t e srace wit rutty or t ermal insulation field surrlY w ere t e rires t roug as s own elow If small animals li e insects enter into He outdoor un...

Page 54: ...tch to protectthe compressor I Caution I Never short circuit the high pressure switch duringpump down operation It is not allowed to let the refrigerant out into the air The refrigerant should be reco...

Page 55: ...itioner air conditioner Rework the flare For R32 see table on next page Use the supplied flare nut I Existing pi ping wort tor new air conditioner PRECAUTIONS ON REFRIGERANT PIPING Clean pipe if exist...

Page 56: ...LARE PROCESSING I Fi 9 I n oor t U ni t 7l Liq atop valve I I Fi 9 2 n oor i1 n 7 aa s pipe Liq stop valve I I Fi 9 3 n oor u ni Liq stop valve I I Ref recovery port Flare connection area of existed p...

Page 57: ...MEMO 57...

Page 58: ...DAIKIN SPLIT SYSTEM MODELS Ceiling mounted Duct type FDMF50BRV16 FDMF71BRV16 FDMF90BRV16 FDMF100BRV16 FDMF125BRV16 FDMF140BRV16 OPERATION MANUAL Air Conditioner 58...

Page 59: ...nd user maintenance shall only be done by persons described in manual The appliance is not intended for use by unattended young children or persons who are incompetent to operate air conditioners It m...

Page 60: ...oil vapor Oil vapor may cause crack damage to the air conditioner electric shocks or a fire Do not use flammable materials e g hairspray or insecticide near the air conditioner Do not clean the air c...

Page 61: ...result in electric shocks or fire Do not place water containers flower vases etc on the indoor unit as this may result in electric shocks or a fire Do not put flammable containers such as spray cans...

Page 62: ...r and call your local dealer for assistance After prolonged use check the unit stand and its mounts for damage If left in a damaged condition the unit may fall and cause injury Do not sit or place obj...

Page 63: ...ess remote controller kit If your installation has a customized control system ask your local dealer for the operation that corresponds to your system Names and functions of parts 2 7 3 D 6 d2b 13 10...

Page 64: ...and increased running noises If abnormal noises occur in use stop the operation of the air conditioner consult your local dealer Regarding drainage of drain piping Is the drain piping carried out prop...

Page 65: ...let of the air conditioner It may decrease the effect or stop the operation Set the airflow of the air discharge grille horizontally not to obstruct the wind Otherwise the wind will not come out and a...

Page 66: ...an air filter as a standard accessory Do not attach objects other than the genuine air filter e g kitchen paper to the air inlet Otherwise the performance of the air conditioner will be degraded and...

Page 67: ...inside of the air conditioner may become contaminated after several seasons of use potentially causing performance degradation and water leakage Ask your local dealer for details on cleaning the insi...

Page 68: ...operation from long resting time Dust absorbed by the unit blows out 7 THE INDOOR UNITS GIVE OFF ODORS During operation The unit absorbs the smell of rooms furniture cigarettes etc and then emits the...

Page 69: ...cooling Check if the heat source of the room is exces sive when cooling 4 Operation was performed or stopped al though the ON OFF button was not pressed Are you sure that the ON OFF timer operation is...

Page 70: ...DAIKIN AIRCONDITIONING IND A PVT LTD 12th Floor Building No 9 Tower A DLF Cyber City DLF Phase Ill Gurgaon 122002 Haryana India Tel 91 0124 4555444 Fax 91 0124 4555333 3P725250 2 70...

Reviews: