background image

(1) Determine the route to carry the unit into the room.

(2) Do not unpack the unit until it is carried to the

installation location.

Where unpacking is unavoidable, use a sling of soft

material or protective plates together with a rope when

lifting, to avoid damage or scratches to the indoor unit.

• Have the customer actually operate the air conditioner while

looking at the operation manual.

Instruct the customer how to operate the air conditioner

(particularly cleaning of the air filters, operation procedures,

and temperature adjustment).

• Have the customer actually operate the air conditioner while

looking at the operation manual.

Instruct the customer how to operate the air conditioner

(particularly cleaning of the air filters, operation procedures,

and temperature adjustment).

• Do not use the air conditioner in a salty atmosphere such as

coastal areas, vehicles, vessels or where voltage fluctuation

is frequent such as factories.

• Take off static electricity from the body when carrying out

wiring and the control box lid is removed.

The electric parts may be damaged.

2-1  ACCESSORIES

Check if the following accessories are attached to the 

indoor unit. 

Table 1 

Name 

Insulation 

for fitting 

Sealing pad 

Quantity 

1 each 

1 each 

d

� 

0

�  � 

M4x8 

► 

Shape 

Thin for 

liquid pipe (3) 

1 pc. Large 

9 Pc. Clamp (7)  2 Pc. 

(Dark grey) (5) 

Wire sealing  2 Pc. 

Metal 

material (9) 

Wire fixing 

clamp (1) 

� 

screw 

65/ 

� 

(11) 

� 

Drain 

Thick for 

2 pc.  Middle 

4 Pc. Washer 

2 Pc. 

Hose(2) 

gas pipe (4)  (Dark grey) (6)  fixing plate (8)  Wire fixing 

bracket (10) 

2-2  OPTIONAL ACCESSORIES

• A remote controller is required for the indoor unit.

(No remote controllers are required for multi slave units

in simultaneous multi operation.)

• There are 2 kinds of remote controller; wired type and

wireless type.

Install the remote controller to the place where the customer

has given consent.

Refer to the catalog for the applicable model.

(Refer to the installation manual attached to the remote

controller for how to install.}

CARRY OUT THE WORK GIVING CAUTION 

TO THE FOLLOWING ITEMS AND AFTER THE 

WORK IS COMPLETED CHECK THESE AGAIN. 

1. Items to be checked after the installation work is

completed

Items to be checked 

In case of defective 

Check column 

Are the indoor and outdoor 

Drop • vibration • 

units rigidly fixed? 

noise 

Are the installation works of  Does not operate • 

the outdoor and indoor units 

completed? 

burnout 

Have you carried out a leakage 

test with the test pressure 

Does not cool. 

specified in the outdoor unit 

installation manual? 

Is the insulation of refrigerant 

piping and drain piping 

Water leakage 

completely carried out? 

Does the drain flow out 

Water leakage 

smoothly? 
Is the power supply voltage 

identical to that stated in the  Does not operate • 

manufacturer's label on the 

burnout 

air conditioner? 
Are you sure that there is no  Does not operate 

wrong wiring or piping or no  burnout 

loose wiring? 

Is earthing completed? 

Danger in case of 

leakage 

Are the sizes of electric 

Does not operate • 

wiring according to the 

specification? 

burnout 

Are any of air outlets or inlets 

of the indoor and outdoor 

units blocked with obstacles?  Does not cool 

(It may lead to capacity drop 

due to fan speed drop or 

malfunction of equipment.) 
Is the external static 

Does not cool 

pressure set correctly? 

Have you recorded the 

refrigerant piping length 

Refrigerant charge 

and the refrigerant charge 

amount is not clear 

amount added? 

Make sure to recheck the items of "SAFETY PRECAUTIONS". 

 

3

6

Summary of Contents for RZVF50

Page 1: ...1...

Page 2: ...2...

Page 3: ...3...

Page 4: ...4...

Page 5: ...5...

Page 6: ...6...

Page 7: ...7...

Page 8: ...8...

Page 9: ...9...

Page 10: ...10...

Page 11: ...11...

Page 12: ...12...

Page 13: ...13...

Page 14: ...14...

Page 15: ...15...

Page 16: ...16...

Page 17: ...17 17 19 20 20 22 23 27 27 28 31 31 32...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...24...

Page 25: ...255...

Page 26: ...26...

Page 27: ...27...

Page 28: ...28...

Page 29: ...299...

Page 30: ...30...

Page 31: ...31...

Page 32: ...32...

Page 33: ...DR18 1226C Daikin IM OM A 4 Size 3P542797 1 KA B 40P Dt 26 07 19 33...

Page 34: ...Operation Manual Ask the user to keep this manual in a handy place for future reference WARNING Do not use means to accelerate the defrosting process or to clean other than those recommended by the ma...

Page 35: ...itioner in places such as the following 1 Where there is mist of oil oil spray or vapour for example a kitchen Resin parts may deteriorate and fall out or water may leak 2 Where corrosive gas such as...

Page 36: ...quired for multi slave units in simultaneous multi operation There are 2 kinds of remote controller wired type and wireless type Install the remote controller to the place where the customer has given...

Page 37: ...mer read through the troubleshooting items while explaining the above items 3 SELECTION OF INSTALLATION LOCATION Hold the hangers at 4 locations to move the indoor unit when unpacking or after unpacke...

Page 38: ...uct Refer Fig 2 2 2 Inspection hatch 1 450 x 450 on the control box side and inspection hatch 2 on the bottom of the product Fig 2 3 arrow A 1 3 Inspection hatch 3 on the bottom of the product and on...

Page 39: ...al components before installing the indoor unit 5 INSTALLATION OF INDOOR UNIT Depending on the optional parts it may be easier to attach them beforeinstalling the indoor unit Refer to also the install...

Page 40: ...40...

Page 41: ...ing NOTE 2 After all the brazing works are finished carry out flare connection with the indoor unit Refer to Fig 8 Pressure reducing valve Refrigerant piping Fig 9 NOTE a Taping Nitrogen 1 The proper...

Page 42: ...maged with the clamp end or bend the tip of the metal clamp 1 inward as shown Refer to Fig 12 In case of sticking vinyl tape Vinyl tape Stick vinyl tape without tearing the sealing l material r _ 5 _...

Page 43: ...ing must be carried out by a qualified electrician If a qualified person is not present after the electric wir ing work is finished check the drainage according to the method specified in When the ele...

Page 44: ...circuit Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or a fire Make sure to install an earth leakage breaker Failure to do so may c...

Page 45: ...ctric shocks or a fire 1 Remove the control box lid Fig 20 2 Connect the wiring into the control box through the wiring intake beside the control box Low voltage wiring inlet Remote controller wiring...

Page 46: ...r and indoor units must be matched 2 1 Connect the remote controller only to the master unit 2 2 The remote controller needs to be wired only to the master unit it does not need to be connected to the...

Page 47: ...factory The method of setting procedure and operation is shown in the installation manual attached to the remote controller Note Though setting of ModeNo is carried out as a group if you intend to ca...

Page 48: ...ring to the table below according to the external static pressure of the duct to be connected Table External static Mode No FIRST SECOND pressure CODE No CODE No 50Pa 05 60Pa 06 70Pa 07 80Pa 08 90Pa 0...

Page 49: ...the master unit The indoor unit does not operate properly when two or more remote controllers are attached to the unit in the simultaneous operation system mode 3 7 Earth leakage circuit breaker Eart...

Page 50: ...e the malfunction code NOTE _ DI 1 When the ON OFF button is kept pressed for 5 seconds or longer during the inspection mode the above trouble his tory indication disappears In this case after the mal...

Page 51: ...ct the adapter or Outdoor air thermistor Abnormal stop is applied the capacity is not set to the system malfunction depending on the model or data retention IC Outdoor unit condition The refrigerant m...

Page 52: ...he customer 12 DECLARED RATINGS Rated Values Please do not refer the Capacity Input Power Current Electricity Consumption mentioned on Outdoor unit rating label when this Outdoor is connected with Inv...

Page 53: ...caution to be given when connecting pipes IFi I I ur t e srace wit rutty or t ermal insulation field surrlY w ere t e rires t roug as s own elow If small animals li e insects enter into He outdoor un...

Page 54: ...tch to protectthe compressor I Caution I Never short circuit the high pressure switch duringpump down operation It is not allowed to let the refrigerant out into the air The refrigerant should be reco...

Page 55: ...itioner air conditioner Rework the flare For R32 see table on next page Use the supplied flare nut I Existing pi ping wort tor new air conditioner PRECAUTIONS ON REFRIGERANT PIPING Clean pipe if exist...

Page 56: ...LARE PROCESSING I Fi 9 I n oor t U ni t 7l Liq atop valve I I Fi 9 2 n oor i1 n 7 aa s pipe Liq stop valve I I Fi 9 3 n oor u ni Liq stop valve I I Ref recovery port Flare connection area of existed p...

Page 57: ...MEMO 57...

Page 58: ...DAIKIN SPLIT SYSTEM MODELS Ceiling mounted Duct type FDMF50BRV16 FDMF71BRV16 FDMF90BRV16 FDMF100BRV16 FDMF125BRV16 FDMF140BRV16 OPERATION MANUAL Air Conditioner 58...

Page 59: ...nd user maintenance shall only be done by persons described in manual The appliance is not intended for use by unattended young children or persons who are incompetent to operate air conditioners It m...

Page 60: ...oil vapor Oil vapor may cause crack damage to the air conditioner electric shocks or a fire Do not use flammable materials e g hairspray or insecticide near the air conditioner Do not clean the air c...

Page 61: ...result in electric shocks or fire Do not place water containers flower vases etc on the indoor unit as this may result in electric shocks or a fire Do not put flammable containers such as spray cans...

Page 62: ...r and call your local dealer for assistance After prolonged use check the unit stand and its mounts for damage If left in a damaged condition the unit may fall and cause injury Do not sit or place obj...

Page 63: ...ess remote controller kit If your installation has a customized control system ask your local dealer for the operation that corresponds to your system Names and functions of parts 2 7 3 D 6 d2b 13 10...

Page 64: ...and increased running noises If abnormal noises occur in use stop the operation of the air conditioner consult your local dealer Regarding drainage of drain piping Is the drain piping carried out prop...

Page 65: ...let of the air conditioner It may decrease the effect or stop the operation Set the airflow of the air discharge grille horizontally not to obstruct the wind Otherwise the wind will not come out and a...

Page 66: ...an air filter as a standard accessory Do not attach objects other than the genuine air filter e g kitchen paper to the air inlet Otherwise the performance of the air conditioner will be degraded and...

Page 67: ...inside of the air conditioner may become contaminated after several seasons of use potentially causing performance degradation and water leakage Ask your local dealer for details on cleaning the insi...

Page 68: ...operation from long resting time Dust absorbed by the unit blows out 7 THE INDOOR UNITS GIVE OFF ODORS During operation The unit absorbs the smell of rooms furniture cigarettes etc and then emits the...

Page 69: ...cooling Check if the heat source of the room is exces sive when cooling 4 Operation was performed or stopped al though the ON OFF button was not pressed Are you sure that the ON OFF timer operation is...

Page 70: ...DAIKIN AIRCONDITIONING IND A PVT LTD 12th Floor Building No 9 Tower A DLF Cyber City DLF Phase Ill Gurgaon 122002 Haryana India Tel 91 0124 4555444 Fax 91 0124 4555333 3P725250 2 70...

Reviews: