background image

13.2 CAUTION (RZMF50~71BRV16) 

THIS IS NECESSARY FOR AFTER 

SERVICE, SO PLEASE REQUEST 

CUSTOMER TO KEEP THIS PAPER. 

CAUTION (NEW REFRIGERANT (R32 SERIES) 

WARNING 

I � 

ELECTRIC SHOCK CAUTION

0 Caution about electric shock when do service inspection. 

1. After intercept power supply, do not open outside panel for 1 O minutes. 

2. Follow manufacturing label on electric box cover, please take off outdoor fan motor 

connector to confirm voltage and body static electricity discharge. 

0 General caution items when do service inspection 

Caution to confirm compressor and fan motor running 

Do not directly connect power input (3 Phase 50Hz) to compressor and fan motor. 

(If not connect to print board (PCB), compressor and fan motor will be burned cut.) 

Caution when recharge refigerant 

1. To prevent the mixing of impurities, pressure resistance and contamination mix, 

please use manifold gauge especially for R32. 

2. Make sure to do Nitrogen blow if brazing when flare connection. 

Apply ether oil or ester oil at inside flare only. 

3. Do air light test at 4.1 7MPa 

4. Do dry vaccum, make sure to charge refrigerant in liquid condition from liquid side 

service port. (Compressor will be broken if charge from gas side service port.) 

Caution when use outdoor PCB 

Make sure to touch earth terminal and earthed metal before touch pcb, 

to prevent electric shock. 

Caution when break down diagnosis from letter code in remote control 

Please refer to service guide or outdoor unit installation manual. 

I  Charging refrigerant  I 

• Charging the system with refrigerant 

(For more infom,ation such as calculation method of  additional refrigerant charge, additional 

charge method, refrigerant charge caution, refer to the Installation Manual and Technical Guide.) 

• For refrigerant charge, be sure to charge from the service port of the liquid side stop 

A.

valve in liquid states.(lf you charge from the service port of the gas side stop valve, 

£.!.l 

it may break the compressor.) 

• Never charge other than the specified refrigerant. (It may cause fire and bursting.) 

Table 1. Chargeless piping length 

Liquid piping size 

Pipe length which is not required additional charging 

¢  9.5 x tO.Bmm 

15m 

1. In case of additional refrigerant charging 

Please add refrigerant amount according to the following table. 

Pipe length which 

Piping  length over chargeless, 

Outdoor 

Liquid piping size 

is not required 

R32 additional amount (kg) 

additional 

charging 

+15 m or less 

RZMF 50,71 BRV16 

¢  9.5 x t0.8mm 

15m 

0.375 

2. Total refrigerant charging (Details please see service guide) 

1. Please recover the refrigerant until becoming 0.09 MPa (gauge pressure: -0.011 MPa) 

or less by the refrigerant recovery machine from slop valve service port 

Qi<µd·gas side) at the same time. 

2. Exchange service parts · modify leak point 

3. Perform airtightness test · airi)Urge. 

Please refer installation manual of outdoor unit or service guide. 

4. Charge refrigerant aroount selected by table 2 from li<µd stop valve service port 

Caution  Do not tum on pa,ver during ev!DJation. The motor may be damaged

due to vacuum dischage. 

Table 2  Charae refriaerant amount  (After a leak  etc  ) 

... 

Pipng length,  R32 complete 

Outdoor 

Liquid piping size 

additional amount (kg) 

,sm 

30m 

5~10m 

or less 

or less 

RZM F 50 BRV16 

¢  9.5 x t0.8mm 

1.09  1.09  1.465 

RZMF 71 BRV16 

¢  9.5 x t0.8mm 

1.30  1.30  1.675 

• Making a record of the added refrigerant charge amount 

Be sure to record the piping length and added refrigerant charge amount or refrigerant recharge amount 

with an oil-based or other indelible marker so the figures will not fade over time. 

This information is necessary for after service and maintenance. 

Liauid oioina size 

¢  9.5mm x tO.Bmm 

Refrioerant oioino lenath 

Additional refrigerant charging 

kg 

Recharge of refrigerant 

kg 

How to execute a pumping-down 

(for example,when moving or 

reinstalling an indoor or outdoor unit) 

The outdoor unit is equiped with a high pressure switch to protect the compressor. 

Caution 

I  Never short-circuit the high pressure switch during pump-down operation 

•  It is not allowed to let the refrigerant out into the air. 

The refrigerant should be recovered completely. 

•  Although pumping-down operation  allows most of the refrigerant to be recovered in a short 

period of time, some refrigerant will remain inside the indoor unit and the refrigerant piping. 

Using a refrigerant recovery  machine,  recover remaining refrigerant from the stop valve 

service port until the pressure falls to 0.09MPa (gauge pressure:-0.011 MPa) or less. 

•  Be sure to execute the pumping-down before refrigerant piping and wiring is taken off.

OFor pumping-down operation 

1. Please follow the 

caution about electric shock when service inspection J 

which attached on Top panel (Caution : Do not take off the connector X106A) 

2. To prevent electric shock, please protect power input terminal block by insulation sheet 

refer to below figure. 

3. Turn on the power supply and carry out pumping-down operation according to the following procedure. 

Insulation sheet 

Outdoor Unit figure 

Protection method 

hi.. 

To prevent electric shock when inspection, protect by use 

ill 

insulation sheet on  ower in  ut terminal block and print board  A2P 

OFor pumping-down operation 

hi.. 

Do not remove the indoor unit until pump down operation finish. 

ill 

(It is dangerous when indoor fan automatically starts the operation.) 

Pertom, pumping-down operation using the following  procedure 

Procedure 

1  Confirm that stop valves both on 

the liquid and gas sides are open. 

Push the pumping-down button (BS1) on the 

PC board of the outdoor unit for 5 seconds. 

Close the stop valve on the liquid side 

securely about 

minutes after the 

compressor started operation. 

Once the compressor operation stops after 

to 5 minutes, close the stop valve on the 

gas side securely. 

4  Turn off the power supply. 

• If after finishing pumping-down operation the 

outdoor unit does not operate, even when the 

remote controller switch is turned on, the remote 

controller may or may not indicate  "U4". 

But it is not a malfunction. 

• To force of operation, turn off the main 

power supply and turn it on again. Make sure 

that stop valves both on liquid and gas sides are 

open and be sure to operate the unit in cooling 

operation during test run. 

Precaution 

Compressor and outdoor unit fan will start 

operation automatically.  Indoor fan may auto-

matically start running. Pay attention to this. 

• Do never leave the outdoor unit unattended 

with opened front panel when power supply 

is on. 

• In case the stop valve on the liquid side is 

not securely closed during compressor 

operation, pumping-down operation cannot 

be executed. 

When you work alone,  carry out  after closing 

the front plate. After turning the power supply 

off,  remove  the insulation sheet. 

Liquid stop valve 

Close� 

Gas stop valve 

CloseEia 

A,..  When installing and relocating, be sure to install the earth leakage breaker to protect 

ill 

from the electric shock disaster and fire due to leakage of electricity. For installing the 

earth leakage breaker,  request to the qualified electrician. 

How to confirm of running condition by LED 

When the power supply turns "ON", you can check 

diagnosis of failure by service monitor (AP2) 

on the outdoor print board LED 

�  ... LED light on 

e  • • • LED light off 

LED 

* · · · 

LEDfrash 

•.. Not relate with diagnosis 

lc-c'-'HA�P

--c+

�H�1�P

,.., 

(ITEM) 

Green 

Red 

* • 

Normal 

¢-

Outdoor PCB defect  Note1 

...

• 

Power input abnormal or outdoor PCB defect (Note2) 

*

¢-

Protection device running (Note3) 

(NOTE 1)  Power off for more than 5 seconds, power ON again, 

and confim, the diagnosis again. 

(NOTE 2)  Power off for more than 5 seconds, take OFF connection wiring 

( indoor transmittion ) and power ON again. If after 10 seconds, 

outdoor PCB shows 

HAP 

it means indoor PCB defected. 

(NOTE 3)  There is phase internuption. 

(NOTE 4)  Previous abnormal history will be continuing display until power OFF. 

After inspection, please power OFF. 

Ocaution about break down diagnosis by remote control letter code. 

Please refer to service guide or outdoor unit installation manual. 

 54

Summary of Contents for RZVF50

Page 1: ...1...

Page 2: ...2...

Page 3: ...3...

Page 4: ...4...

Page 5: ...5...

Page 6: ...6...

Page 7: ...7...

Page 8: ...8...

Page 9: ...9...

Page 10: ...10...

Page 11: ...11...

Page 12: ...12...

Page 13: ...13...

Page 14: ...14...

Page 15: ...15...

Page 16: ...16...

Page 17: ...17 17 19 20 20 22 23 27 27 28 31 31 32...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...24...

Page 25: ...255...

Page 26: ...26...

Page 27: ...27...

Page 28: ...28...

Page 29: ...299...

Page 30: ...30...

Page 31: ...31...

Page 32: ...32...

Page 33: ...DR18 1226C Daikin IM OM A 4 Size 3P542797 1 KA B 40P Dt 26 07 19 33...

Page 34: ...Operation Manual Ask the user to keep this manual in a handy place for future reference WARNING Do not use means to accelerate the defrosting process or to clean other than those recommended by the ma...

Page 35: ...itioner in places such as the following 1 Where there is mist of oil oil spray or vapour for example a kitchen Resin parts may deteriorate and fall out or water may leak 2 Where corrosive gas such as...

Page 36: ...quired for multi slave units in simultaneous multi operation There are 2 kinds of remote controller wired type and wireless type Install the remote controller to the place where the customer has given...

Page 37: ...mer read through the troubleshooting items while explaining the above items 3 SELECTION OF INSTALLATION LOCATION Hold the hangers at 4 locations to move the indoor unit when unpacking or after unpacke...

Page 38: ...uct Refer Fig 2 2 2 Inspection hatch 1 450 x 450 on the control box side and inspection hatch 2 on the bottom of the product Fig 2 3 arrow A 1 3 Inspection hatch 3 on the bottom of the product and on...

Page 39: ...al components before installing the indoor unit 5 INSTALLATION OF INDOOR UNIT Depending on the optional parts it may be easier to attach them beforeinstalling the indoor unit Refer to also the install...

Page 40: ...40...

Page 41: ...ing NOTE 2 After all the brazing works are finished carry out flare connection with the indoor unit Refer to Fig 8 Pressure reducing valve Refrigerant piping Fig 9 NOTE a Taping Nitrogen 1 The proper...

Page 42: ...maged with the clamp end or bend the tip of the metal clamp 1 inward as shown Refer to Fig 12 In case of sticking vinyl tape Vinyl tape Stick vinyl tape without tearing the sealing l material r _ 5 _...

Page 43: ...ing must be carried out by a qualified electrician If a qualified person is not present after the electric wir ing work is finished check the drainage according to the method specified in When the ele...

Page 44: ...circuit Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or a fire Make sure to install an earth leakage breaker Failure to do so may c...

Page 45: ...ctric shocks or a fire 1 Remove the control box lid Fig 20 2 Connect the wiring into the control box through the wiring intake beside the control box Low voltage wiring inlet Remote controller wiring...

Page 46: ...r and indoor units must be matched 2 1 Connect the remote controller only to the master unit 2 2 The remote controller needs to be wired only to the master unit it does not need to be connected to the...

Page 47: ...factory The method of setting procedure and operation is shown in the installation manual attached to the remote controller Note Though setting of ModeNo is carried out as a group if you intend to ca...

Page 48: ...ring to the table below according to the external static pressure of the duct to be connected Table External static Mode No FIRST SECOND pressure CODE No CODE No 50Pa 05 60Pa 06 70Pa 07 80Pa 08 90Pa 0...

Page 49: ...the master unit The indoor unit does not operate properly when two or more remote controllers are attached to the unit in the simultaneous operation system mode 3 7 Earth leakage circuit breaker Eart...

Page 50: ...e the malfunction code NOTE _ DI 1 When the ON OFF button is kept pressed for 5 seconds or longer during the inspection mode the above trouble his tory indication disappears In this case after the mal...

Page 51: ...ct the adapter or Outdoor air thermistor Abnormal stop is applied the capacity is not set to the system malfunction depending on the model or data retention IC Outdoor unit condition The refrigerant m...

Page 52: ...he customer 12 DECLARED RATINGS Rated Values Please do not refer the Capacity Input Power Current Electricity Consumption mentioned on Outdoor unit rating label when this Outdoor is connected with Inv...

Page 53: ...caution to be given when connecting pipes IFi I I ur t e srace wit rutty or t ermal insulation field surrlY w ere t e rires t roug as s own elow If small animals li e insects enter into He outdoor un...

Page 54: ...tch to protectthe compressor I Caution I Never short circuit the high pressure switch duringpump down operation It is not allowed to let the refrigerant out into the air The refrigerant should be reco...

Page 55: ...itioner air conditioner Rework the flare For R32 see table on next page Use the supplied flare nut I Existing pi ping wort tor new air conditioner PRECAUTIONS ON REFRIGERANT PIPING Clean pipe if exist...

Page 56: ...LARE PROCESSING I Fi 9 I n oor t U ni t 7l Liq atop valve I I Fi 9 2 n oor i1 n 7 aa s pipe Liq stop valve I I Fi 9 3 n oor u ni Liq stop valve I I Ref recovery port Flare connection area of existed p...

Page 57: ...MEMO 57...

Page 58: ...DAIKIN SPLIT SYSTEM MODELS Ceiling mounted Duct type FDMF50BRV16 FDMF71BRV16 FDMF90BRV16 FDMF100BRV16 FDMF125BRV16 FDMF140BRV16 OPERATION MANUAL Air Conditioner 58...

Page 59: ...nd user maintenance shall only be done by persons described in manual The appliance is not intended for use by unattended young children or persons who are incompetent to operate air conditioners It m...

Page 60: ...oil vapor Oil vapor may cause crack damage to the air conditioner electric shocks or a fire Do not use flammable materials e g hairspray or insecticide near the air conditioner Do not clean the air c...

Page 61: ...result in electric shocks or fire Do not place water containers flower vases etc on the indoor unit as this may result in electric shocks or a fire Do not put flammable containers such as spray cans...

Page 62: ...r and call your local dealer for assistance After prolonged use check the unit stand and its mounts for damage If left in a damaged condition the unit may fall and cause injury Do not sit or place obj...

Page 63: ...ess remote controller kit If your installation has a customized control system ask your local dealer for the operation that corresponds to your system Names and functions of parts 2 7 3 D 6 d2b 13 10...

Page 64: ...and increased running noises If abnormal noises occur in use stop the operation of the air conditioner consult your local dealer Regarding drainage of drain piping Is the drain piping carried out prop...

Page 65: ...let of the air conditioner It may decrease the effect or stop the operation Set the airflow of the air discharge grille horizontally not to obstruct the wind Otherwise the wind will not come out and a...

Page 66: ...an air filter as a standard accessory Do not attach objects other than the genuine air filter e g kitchen paper to the air inlet Otherwise the performance of the air conditioner will be degraded and...

Page 67: ...inside of the air conditioner may become contaminated after several seasons of use potentially causing performance degradation and water leakage Ask your local dealer for details on cleaning the insi...

Page 68: ...operation from long resting time Dust absorbed by the unit blows out 7 THE INDOOR UNITS GIVE OFF ODORS During operation The unit absorbs the smell of rooms furniture cigarettes etc and then emits the...

Page 69: ...cooling Check if the heat source of the room is exces sive when cooling 4 Operation was performed or stopped al though the ON OFF button was not pressed Are you sure that the ON OFF timer operation is...

Page 70: ...DAIKIN AIRCONDITIONING IND A PVT LTD 12th Floor Building No 9 Tower A DLF Cyber City DLF Phase Ill Gurgaon 122002 Haryana India Tel 91 0124 4555444 Fax 91 0124 4555333 3P725250 2 70...

Reviews: