CAUTION------------

• To avoid the attached drain hose (2) getting excessive

force, do not bend nor twist it.

It may cause water leakage.

• As for drain piping connection, do not connect the drain

hose directly to a sewage that gives off ammonia odor. 

(The ammonia in the sewage may go through the drain 

piping and corrode the heat exchanger of the indoor unit.)

• In case of centralized drain piping, carry out piping work

according to the procedure shown in the following 

Fig.14.

Centralized drain piping 

( Make a downward inclination of 1/100  )

or more to avoid stagnation of air. 

L'.ti, 

If water stagnates in the drain 

piping, it may cause clogging of 

drain piping. 

Fig.14 

• As for the size of centralized drain piping, select the size

that meets the capacity of indoor units to be connected.

(Refer to the technical document)

• Positioning the upward drain piping at an angle may cause 

float switch malfunction and lead to water leakage. 

• While replacing with new indoor unit, use the attached

new drain hose (2) and the metal clamp (1).

If an old drain hose or a metal clamp is used, it may

cause water leakage.

(2) After piping is finished, check if the drain flows

smoothly.
[When the electric wiring work is finished]

• Gradually pour 1 liter of water from the inspection port

at the bottom of the drain socket on the left side of the

drain socket into the drain pan giving caution to avoid

splashing water on the electric components such as

drain pump and confirm drainage by operating the

indoor unit under cooling mode according to

10. FIELD SETTING. (Refer to Fig.15)

Socket for maintenance 

(with rubber cap) 

Drain socket 

Refrigerant piping 

El. compo. box lid 

El. compo. box 

Terminal block for 

power supply 

Screw 

Plastic water container 

Fig.15 

[When the electric wiring work is not finished] 

• The electric wiring works (including earthing) must be

carried out by a qualified electrician.

• If a qualified person is not present,  after the electric wir­

ing work is finished, check the drainage according to the

method specified in 

[When the electric wiring work is

finished].

1. Open the control box lid and connect the single phase

230 V power supply to the terminal (L, N) on the

terminal block (X2M).

Connect the earth wiring to the earth terminal.

2. Make sure the control box lid is closed before turning

on the power supply.

• Throughout the whole process, carry out the work

giving caution to the wiring around the control box

so that the connectors may not come off.

3. Gradually pour 1 liter of water from the air outlet on

the left side of the drain socket into the drain pan

giving caution to avoid splashing water on the electric

components such as drain pump. 

(Refer to Fig. 15)

4. When the power supply is turned on, the drain pump

will operate. Drainage can be checked at the trans­

parent part of the drain socket.

{The drain pump will automatically stop after 10

minutes.)

The drainage of water can be confirmed with water level

change in the drain pan through the access window. 

• Do not connect the drain piping directly to the sew­

age that gives off ammonia odor.

The ammonia in the sewage may go through the

drain piping and corrode the heat exchanger of the

indoor unit.

• Do not apply external force to the float switch. (It

may result in malfunction)

• Do not touch the drain pump.

Touching the drain pump may cause electric shocks.

• Do not apply external force to the float switch.

External force may cause a float switch malfunction.

5. Turn off the power supply after checking drainage,

and remove the power supply wiring.

6. Attach the control box lid as before.

• On the completion of the drainage check, refer to the

following illustration, and use the provided large sealing pad

(5) and heat insulate the metal clamp (1) and drain hose (2)

Make sure that the 

seam faces upward. 

4 mm max. 

Fig.16 

Large sealing pad (5) 

( accessory) 

Metal clamp (1) 

(accessory) 

 43

Summary of Contents for RZVF50

Page 1: ...1...

Page 2: ...2...

Page 3: ...3...

Page 4: ...4...

Page 5: ...5...

Page 6: ...6...

Page 7: ...7...

Page 8: ...8...

Page 9: ...9...

Page 10: ...10...

Page 11: ...11...

Page 12: ...12...

Page 13: ...13...

Page 14: ...14...

Page 15: ...15...

Page 16: ...16...

Page 17: ...17 17 19 20 20 22 23 27 27 28 31 31 32...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...24...

Page 25: ...255...

Page 26: ...26...

Page 27: ...27...

Page 28: ...28...

Page 29: ...299...

Page 30: ...30...

Page 31: ...31...

Page 32: ...32...

Page 33: ...DR18 1226C Daikin IM OM A 4 Size 3P542797 1 KA B 40P Dt 26 07 19 33...

Page 34: ...Operation Manual Ask the user to keep this manual in a handy place for future reference WARNING Do not use means to accelerate the defrosting process or to clean other than those recommended by the ma...

Page 35: ...itioner in places such as the following 1 Where there is mist of oil oil spray or vapour for example a kitchen Resin parts may deteriorate and fall out or water may leak 2 Where corrosive gas such as...

Page 36: ...quired for multi slave units in simultaneous multi operation There are 2 kinds of remote controller wired type and wireless type Install the remote controller to the place where the customer has given...

Page 37: ...mer read through the troubleshooting items while explaining the above items 3 SELECTION OF INSTALLATION LOCATION Hold the hangers at 4 locations to move the indoor unit when unpacking or after unpacke...

Page 38: ...uct Refer Fig 2 2 2 Inspection hatch 1 450 x 450 on the control box side and inspection hatch 2 on the bottom of the product Fig 2 3 arrow A 1 3 Inspection hatch 3 on the bottom of the product and on...

Page 39: ...al components before installing the indoor unit 5 INSTALLATION OF INDOOR UNIT Depending on the optional parts it may be easier to attach them beforeinstalling the indoor unit Refer to also the install...

Page 40: ...40...

Page 41: ...ing NOTE 2 After all the brazing works are finished carry out flare connection with the indoor unit Refer to Fig 8 Pressure reducing valve Refrigerant piping Fig 9 NOTE a Taping Nitrogen 1 The proper...

Page 42: ...maged with the clamp end or bend the tip of the metal clamp 1 inward as shown Refer to Fig 12 In case of sticking vinyl tape Vinyl tape Stick vinyl tape without tearing the sealing l material r _ 5 _...

Page 43: ...ing must be carried out by a qualified electrician If a qualified person is not present after the electric wir ing work is finished check the drainage according to the method specified in When the ele...

Page 44: ...circuit Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or a fire Make sure to install an earth leakage breaker Failure to do so may c...

Page 45: ...ctric shocks or a fire 1 Remove the control box lid Fig 20 2 Connect the wiring into the control box through the wiring intake beside the control box Low voltage wiring inlet Remote controller wiring...

Page 46: ...r and indoor units must be matched 2 1 Connect the remote controller only to the master unit 2 2 The remote controller needs to be wired only to the master unit it does not need to be connected to the...

Page 47: ...factory The method of setting procedure and operation is shown in the installation manual attached to the remote controller Note Though setting of ModeNo is carried out as a group if you intend to ca...

Page 48: ...ring to the table below according to the external static pressure of the duct to be connected Table External static Mode No FIRST SECOND pressure CODE No CODE No 50Pa 05 60Pa 06 70Pa 07 80Pa 08 90Pa 0...

Page 49: ...the master unit The indoor unit does not operate properly when two or more remote controllers are attached to the unit in the simultaneous operation system mode 3 7 Earth leakage circuit breaker Eart...

Page 50: ...e the malfunction code NOTE _ DI 1 When the ON OFF button is kept pressed for 5 seconds or longer during the inspection mode the above trouble his tory indication disappears In this case after the mal...

Page 51: ...ct the adapter or Outdoor air thermistor Abnormal stop is applied the capacity is not set to the system malfunction depending on the model or data retention IC Outdoor unit condition The refrigerant m...

Page 52: ...he customer 12 DECLARED RATINGS Rated Values Please do not refer the Capacity Input Power Current Electricity Consumption mentioned on Outdoor unit rating label when this Outdoor is connected with Inv...

Page 53: ...caution to be given when connecting pipes IFi I I ur t e srace wit rutty or t ermal insulation field surrlY w ere t e rires t roug as s own elow If small animals li e insects enter into He outdoor un...

Page 54: ...tch to protectthe compressor I Caution I Never short circuit the high pressure switch duringpump down operation It is not allowed to let the refrigerant out into the air The refrigerant should be reco...

Page 55: ...itioner air conditioner Rework the flare For R32 see table on next page Use the supplied flare nut I Existing pi ping wort tor new air conditioner PRECAUTIONS ON REFRIGERANT PIPING Clean pipe if exist...

Page 56: ...LARE PROCESSING I Fi 9 I n oor t U ni t 7l Liq atop valve I I Fi 9 2 n oor i1 n 7 aa s pipe Liq stop valve I I Fi 9 3 n oor u ni Liq stop valve I I Ref recovery port Flare connection area of existed p...

Page 57: ...MEMO 57...

Page 58: ...DAIKIN SPLIT SYSTEM MODELS Ceiling mounted Duct type FDMF50BRV16 FDMF71BRV16 FDMF90BRV16 FDMF100BRV16 FDMF125BRV16 FDMF140BRV16 OPERATION MANUAL Air Conditioner 58...

Page 59: ...nd user maintenance shall only be done by persons described in manual The appliance is not intended for use by unattended young children or persons who are incompetent to operate air conditioners It m...

Page 60: ...oil vapor Oil vapor may cause crack damage to the air conditioner electric shocks or a fire Do not use flammable materials e g hairspray or insecticide near the air conditioner Do not clean the air c...

Page 61: ...result in electric shocks or fire Do not place water containers flower vases etc on the indoor unit as this may result in electric shocks or a fire Do not put flammable containers such as spray cans...

Page 62: ...r and call your local dealer for assistance After prolonged use check the unit stand and its mounts for damage If left in a damaged condition the unit may fall and cause injury Do not sit or place obj...

Page 63: ...ess remote controller kit If your installation has a customized control system ask your local dealer for the operation that corresponds to your system Names and functions of parts 2 7 3 D 6 d2b 13 10...

Page 64: ...and increased running noises If abnormal noises occur in use stop the operation of the air conditioner consult your local dealer Regarding drainage of drain piping Is the drain piping carried out prop...

Page 65: ...let of the air conditioner It may decrease the effect or stop the operation Set the airflow of the air discharge grille horizontally not to obstruct the wind Otherwise the wind will not come out and a...

Page 66: ...an air filter as a standard accessory Do not attach objects other than the genuine air filter e g kitchen paper to the air inlet Otherwise the performance of the air conditioner will be degraded and...

Page 67: ...inside of the air conditioner may become contaminated after several seasons of use potentially causing performance degradation and water leakage Ask your local dealer for details on cleaning the insi...

Page 68: ...operation from long resting time Dust absorbed by the unit blows out 7 THE INDOOR UNITS GIVE OFF ODORS During operation The unit absorbs the smell of rooms furniture cigarettes etc and then emits the...

Page 69: ...cooling Check if the heat source of the room is exces sive when cooling 4 Operation was performed or stopped al though the ON OFF button was not pressed Are you sure that the ON OFF timer operation is...

Page 70: ...DAIKIN AIRCONDITIONING IND A PVT LTD 12th Floor Building No 9 Tower A DLF Cyber City DLF Phase Ill Gurgaon 122002 Haryana India Tel 91 0124 4555444 Fax 91 0124 4555333 3P725250 2 70...

Reviews: