On completion of installation work, check that there is no gas
leakage. Refer to the illustrations on the right hand side and be sure
to perform heat insulation work on the piping joints after gas leakage.
(Refer Fig.8)
Heat insulation procedure for liquid piping
-----�
Insulation for fitting (3)(accessory)
Insulation material
for piping
(on unit side)
Attached to
the surface.
Flare nut joint
Make sure that
the seam faces Middle sealing pad (6)
upward.
(accessory)
Main unit -�t-'--+---------va
Clamp (7)
(accessory)
Insulation material
for piping (field supply)
Wrap the insulation material
around the portion from the
surface of the main unit to the
upper part of the flare nut joint.
Gas pipe
Heat insulation procedure for gas piping
------�
Insulation for fitting (4) (accessory)
Insulation material
for piping
(on unit side)
Clamp (7
(accessory)
Insulation material
for piping (field supply)
Fig. 8
Middle sealing pad (6)
(accessory)
Wrap the insulation material
around the portion from the
surface of the main unit to the
upper part of the flare nut joint.
• Use the insulation for fitting (3) and (4)provided to
the liquid piping and gas piping,
respectively and conduct heat insulation work.
(Tighten both edges of the insulation for fitting(3)
and (4)for each joint with clamp(?}.
• Make sure that the joint of the insulation for
fitting(4)and(5)for the joint on the liquid piping
and gas pipingside faces upwards.
• Wrap the middle sealing material (6)around the
insulation for fitting (3)and(4)for the joint
(flare nut part).
• Before brazing refrigerant piping, have nitrogen flow
through the refrigerant piping and substitute air with nitro
gen (NOTE 1)
(Refer to Fig. 9).
Then, carry out brazing
(NOTE 2).
After all the brazing works are finished,carry out flare
connection with the indoor unit.
(Refer to Fig.
8)
Pressure reducing valve
Refrigerant piping
Fig.9
NOTE
-a-
Taping
Nitrogen
1. The proper pressure for having nitrogen flow through the
piping is approximately 0.02 MPa, a pressure that makes
one feel like slight breeze and can be obtained through a
pressure reducing valve.
2. Do not use flux when brazing refrigerant piping.
Use phosphor copper brazing filler metal (BCuP-2: JIS Z
3264/B-Cu93P-710/795: ISO 3677) that does not require
flux.
{If chlorinated flux is used, the piping will be corroded and,
in addition if fluorine is contained, the refrigerant oil will
be deteriorated and the refrigerant circuit will be affected
badly.)
3. When carrying out leakage test of refrigerant piping and
the indoor unit after the installation of indoor unit is fin
ished, confirm the connecting outdoor unit installation
manual for test pressure.
Refer to also the outdoor unit installation manual or techni
cal document for refrigerant piping.
4. In case of refrigerant shortage due to forgetting additional
refrigerant charge etc., it will result in malfunction such as
does not cool .
Refer to the outdoor unit installation manual or technical
document for refrigerant piping.
-&
CAUTION----------
Do not use antioxidant when brazing piping.
It may result in malfunction of components and clogging of
piping due to residue.
7. DRAIN PIPING WORK
(1) Carry out drain piping.
Carry out drain piping so that drainage is ensured.
• Select the piping diameter equal to or larger than
(except for riser) that of the connection piping (polyvi
nyl chloride piping, nominal diameter 25 mm, outside
diameter 32 mm).
• Install the drain piping as short as possible with down
ward inclination of 1/100 or more and without such that
air may not stagnate.
(Refer to Fig.10)
41
Summary of Contents for RZVF50
Page 1: ...1...
Page 2: ...2...
Page 3: ...3...
Page 4: ...4...
Page 5: ...5...
Page 6: ...6...
Page 7: ...7...
Page 8: ...8...
Page 9: ...9...
Page 10: ...10...
Page 11: ...11...
Page 12: ...12...
Page 13: ...13...
Page 14: ...14...
Page 15: ...15...
Page 16: ...16...
Page 17: ...17 17 19 20 20 22 23 27 27 28 31 31 32...
Page 18: ...18...
Page 19: ...19...
Page 20: ...20...
Page 21: ...21...
Page 22: ...22...
Page 23: ...23...
Page 24: ...24...
Page 25: ...255...
Page 26: ...26...
Page 27: ...27...
Page 28: ...28...
Page 29: ...299...
Page 30: ...30...
Page 31: ...31...
Page 32: ...32...
Page 33: ...DR18 1226C Daikin IM OM A 4 Size 3P542797 1 KA B 40P Dt 26 07 19 33...
Page 40: ...40...
Page 57: ...MEMO 57...