3
6
• Split - Sky Air • RZQG-L(8)Y1
21
• Outdoor Unit • RZQG-L(8)Y1
6
Capacity tables
6 - 2
Cooling/Heating Capacity Tables
RZQG71L9V1
RZQG71L8Y1
Cooling
Heating
Symbols
AFR: Air flow rate [m³/min]
BF: Bypass factor
EWB: Entering wet-bulb temperature (°C WB)
EDB: Entering dry-bulb temperature (°C DB)
TC: Maximum total cooling/heating capacity [kW]
SHC: Sensible heat capacity [kW]
CPI: Coefficient of the power input
PI: Power input [kW]
comp indoor and outdoor fan motors
Cooling
Heating
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2.
= Maximum at standard conditions
= Rated capacity and rated coefficient of the power input
The maximum capacity is not guaranteed except at standard conditions.
3. SHC is based on indoor units EWB & EDB.
SHC for other dry-bulb temperatures = SHC + SHC*
SHC*
= SHC correction for other dry-bulb temperatures
= 0.02 x AFR (m³/min) x (1-BF) x (DB* - EDB)
4. The capacities are based on the following conditions:
Outdoor air: 85% RH
However, the outdoor ambient condition of the rated capacity during heating operation is 7°C DB / 6°C WB.
Corresponding refrigerant piping length: 5.0 m
Level difference: 0m
5. CPI is a percentage value compared to the rated value which is 1.00.
6. The error rate for this value is less than 5% and depends on the indoor unit type.
7. The heating performance takes into account the drop that occurs during defrost operation.
8. The air flow rate and bypass factor are mentioned in the table.
9. The rated power input for each model is mentioned in the table below.
Pair
Pair
FCQHG71F
FCQG71F
FBQ71C
FHQG71C
FAQ71C
FVQ71C
FHQ71CB
FUQ71C
FBQ71D
FCQHG71F
FCQG71F
FBQ71C
FHQG71C
FAQ71C
FVQ71C
FHQ71CB
FUQ71C
FBQ71D
Cooling
1,66
2,01
1,94
1,78
2,00
2,02
1,78
1,67
1,89
Heating
1,56
1,89
2,05
1,82
2,03
2,06
1,82
1,68
1,87
Twin
Twin
FCQG35F X 2
FBQ35C X 2
FHQ35CB X 2
FFQ35C X 2
FDXS35F X 2
FBQ35D X 2
FNQ35A X 2
FCQG35F X 2
FBQ35C X 2
FHQ35CB X 2
FFQ35C X 2
FDXS35F x 2
FBQ35D X 2
FNQ35A X 2
Cooling
2,04
1,98
2,34
2,02
2,23
2,01
2,23
Heating
1,92
2,16
2,70
1,88
2,55
2,08
2,55
18.0
(0.08)
20.5
(0.13)
AFR
(BF)
21.2
( 0.2)
21.5
(0.14)
18.0
(0.16)
18.0
(0.16)
20.5
(0.13)
23.0
(0.24)
18.0
(0.13)
15 x 2
(0.08 x 2)
8,7 x 2
(0.17 x 2)
AFR
(BF)
12.5 x 2
(0.4 x 2)
16 x2
(0.15 x 2)
14 x 2
(0.17 x 2)
10 x 2
(0.25 x 2)
8,7 x 2
(0.17 x 2)
TC
SHC
CPI
TC
SHC
CPI
TC
SHC
CPI
TC
SHC
CPI
Ԩ
WB
Ԩ
DB
kW
kW
㸫
kW
kW
㸫
kW
kW
㸫
kW
kW
㸫
16,0
22
8,03
5,45
1,00
7,76
5,32
1,11
7,48
5,20
1,21
7,21
5,06
1,32
18,0
25
8,40
5,45
1,00
8,11
5,32
1,11
7,83
5,19
1,22
7,54
5,05
1,33
19,0
27
8,59
5,44
1,01
8,30
5,32
1,12
8,00
5,18
1,22
7,70
5,05
1,33
19,5
27
8,68
5,43
1,01
8,39
5,31
1,12
8,09
5,17
1,22
7,79
5,05
1,33
22,0
30
9,15
5,38
1,01
8,84
5,25
1,12
8,52
5,13
1,23
8,21
4,99
1,34
24,0
32
9,53
5,31
1,03
9,20
5,19
1,13
8,87
5,06
1,25
8,54
4,92
1,35
25
30
35
40
Co
efficien
t
of
t
he p
ower
in
pu
t
Coefficient of
the
power
input
Cooling capacity [kW]
Heating capacity [kW]
Capacity range
Rated point
Capacity range
Rated point
Indo
o
r
Outdoor temperature [ °C DB]
Indoor
3D076748G