Specifications
Standard Accessories : Tie-wraps; Quantity : 2;
Standard Accessories : Installation manual; Quantity : 1;
Notes
(1) 3 with re-charging
PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
See separate drawing for electrical data
Contains fluorinated greenhouse gases
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the
electrical data drawing.
2-10 Electrical Specifications
RZQG71L8Y1
RZQG100L8Y1
RZQG125L8Y1
RZQG140LY1
Power supply
Name
Y1
Phase
3N~
Frequency
Hz
50
Voltage
V
380-415
Voltage range
Min.
%
10
Max.
%
10
Current - 50Hz
Maximum fuse amps (MFA)
A
16
25
Current
Zmax
List
Complies to EN61000-3-11
Recommended fuses
A
16
25
Current - 60Hz
Maximum fuse amps (MFA)
A
-
Wiring connections
For power supply
Remark
See installation manual outdoor unit
For connection with
indoor
Remark
See installation manual outdoor unit
Power supply intake
Outdoor unit only