• Outdoor Unit • RZQG-L(8)Y1
6
• Split - Sky Air • RZQG-L(8)Y1
22
6
Capacity tables
6 - 2
Cooling/Heating Capacity Tables
RZQG100L9V1
RZQG100L8Y1
Cooling
Heating
Symbols
AFR: Air flow rate [m³/min]
BF: Bypass factor
EWB: Entering wet-bulb temperature (°C WB)
EDB: Entering dry-bulb temperature (°C DB)
TC: Maximum total cooling/heating capacity [kW]
SHC: Sensible heat capacity [kW]
CPI: Coefficient of the power input
PI: Power input [kW]
comp indoor and outdoor fan motors
Cooling
Heating
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2.
= Maximum at standard conditions
= Rated capacity and rated coefficient of the power input
The maximum capacity is not guaranteed except at standard conditions.
3. SHC is based on indoor units EWB & EDB.
SHC for other dry-bulb temperatures = SHC + SHC*
SHC*
= SHC correction for other dry-bulb temperatures
= 0.02 x AFR (m³/min) x (1-BF) x (DB* - EDB)
4. The capacities are based on the following conditions:
Outdoor air: 85% RH
However, the outdoor ambient condition of the rated capacity during heating operation is 7°C DB / 6°C WB.
Corresponding refrigerant piping length: 5.0 m
Level difference: 0m
5. CPI is a percentage value compared to the rated value which is 1.00.
6. The error rate for this value is less than 5% and depends on the indoor unit type.
7. The heating performance takes into account the drop that occurs during defrost operation.
8. The air flow rate and bypass factor are mentioned in the table.
9. The rated power input for each model is mentioned in the table below.
Pair
Pair
FCQHG100F
FCQG100F
FBQ100C
FHQG100C
FAQ100C
FVQ100C
FHQ100CB
FUQ100C
FBQ100D
FCQHG100F
FCQG100F
FBQ100C
FHQG100C
FAQ100C
FVQ100C
FHQ100CB
FUQ100C
FBQ100D
Cooling
2,15
2,45
2,44
2,49
2,63
2,49
2,30
2,33
2,49
Heating
2,16
2,60
2,57
2,60
3,00
2,61
2,60
2,62
2,45
Twin
Twin
FCQG50F X 2
FBQ50C X 2
FHQ50CB X 2
FFQ50C X 2
FDXS50F9 X 2
FBQ50D X 2
FNQ50A X 2
FCQG50F X 2
FBQ50C X 2
FHQ50CB X 2
FFQ50C X 2
FDXS50F9 X 2
FBQ50D X 2
FNQ50A X 2
Cooling
2,32
2,51
2,93
2,65
2,51
2,87
2,51
Heating
2,46
2,86
3,28
2,89
2,96
2,73
2,96
Triple
Triple
FCQG35F X 3
FBQ35C X 3
FHQ35CB X 3
FFQ35C X 3
FDXS35F X 3
FBQ35D x 3
FNQ35A X 3
FCQG35F X 3
FBQ35C X 3
FHQ35CB X 3
FFQ35C X 3
FDXS35F X 3
FBQ35D x 3
FNQ35A X 3
Cooling
2,38
2,51
2,91
2,45
2,81
2,68
2,81
Heating
2,51
2,86
3,20
2,59
3,68
2,70
3,68
32.0
(0.13)
20.0
(0.09)
AFR
(BF)
32.3
(0.17)
32.0
(0.17)
26.0
(0.10)
28.0
(0.20)
28.0
(0.09)
31.0
(0.20)
29.0
(0.03)
AFR
(BF)
12.5 x 3
(0.4 x 3)
16 x3
(0.15 x 3)
14 x 3
(0.17 x 3)
10 x 3
(0.25 x 3)
15 x 3
(0.13 x 2)
16 x 2
(0.11 x 2)
AFR
(BF)
12.6 x 2
(0.22 x 2)
16 x2
(0.16 x 2)
15 x 2
(0.18 x 2)
12 x 2
(0.16 x 2)
16 x 2
(0.11 x 2)
8.7 x 3
(0.17 x 3)
15 x 3
(0.08 x 3)
8.7 x 3
(0.17 x 3)
TC
SHC
CPI
TC
SHC
CPI
TC
SHC
CPI
TC
SHC
CPI
Ԩ
WB
Ԩ
DB
kW
kW
㸫
kW
kW
㸫
kW
kW
㸫
kW
kW
㸫
16,0
22
11,20
7,61
1,01
10,85
7,44
1,11
10,50
7,29
1,22
10,11
7,09
1,32
18,0
25
11,80
7,59
1,01
11,37
7,49
1,12
11,00
7,27
1,23
10,55
7,09
1,33
19,0
27
12,00
7,57
1,02
11,62
7,44
1,12
11,20
7,26
1,23
10,80
7,04
1,33
19,5
27
12,15
7,59
1,02
11,74
7,37
1,13
11,43
7,34
1,23
10,91
7,04
1,34
22,0
30
12,80
7,52
1,02
12,37
7,36
1,13
11,90
7,16
1,24
11,52
7,03
1,35
24,0
32
13,30
7,42
1,03
12,88
7,27
1,14
12,40
7,06
1,25
11,97
6,91
1,36
25
30
35
40
Co
efficien
t
of the power
input
Co
efficient
of the power
input
Cooling capacity [kW]
Heating capacity [kW]
Capacity range
Rated point
Capacity range
Rated point
In
door
Outdoor temperature [°C WB]
Outdoor temperature [°C DB]
Indoor
3D076749G
Summary of Contents for RZQG-L8Y1 Series
Page 1: ...Air Conditioning Technical Data RZQG L 8 Y1 ...
Page 2: ......
Page 19: ...3 4 Split Sky Air RZQG L 8 Y1 17 Outdoor Unit RZQG L 8 Y1 4 Options 4 1 Options ...
Page 46: ......